| Review | Building |
| Review Date | 04/20/2012 |
| Status | Rejected |
| Comments |
| 1. The response letter submitted does not address the comments made for Revision 1. It appears that the previous letter (with a different date) was resubmitted? Please submit written responses to confirm changes made. | | | 2. Acknowledge the changes made from 1 exit to 2 exits on Sheet G-001 and the change in notations from "existing 1 HR rated partition, by landlord" to "existing 2 HR rated partition, by landlord" on Sheet I-111. However, the calculated load is still 90, thus it is an A2 use and not a B. Show correctly on code analysis and plumbing fixture calculations for final review. | | | 3. Further comments may be forthcoming upon plan resubmission. | | | |
|