Permit #B1801397
Address4150 CAMPBELL AVE
TypeCTBO
StatusFINALED
Permit HolderI-CE-NY JIE C. LI
OwnerUDR DELANCEY AT SHIRLINGTON LLC
Applied Date05/23/2018
Approved Date07/30/2018
Date Issued08/02/2018
DescriptionTEANT IMPROVMENT PLAN ICE CREAM TAKE OUT

View Event Log.      View Status.    View Required Plan Review       View Printer Version.

Review   Review       Date Status   Comments   
Building07/27/2018Approved Sheet AG-000 COVER SHEET: SUBMIT FIRE ALARM SHOP DRAWINGS FOR APPROVAL
Building07/27/2018Approved Sheet AG-000 COVER SHEET: SEPARATE PLAN AND PERMIT REQUIRED FOR DOORS WITH SPECIAL LOCKING HARDWARE
Building07/27/2018Approved Sheet AG-000 COVER SHEET: SUBMIT AUTOMATIC SUPPRESSION SHOP DRAWINGS FOR APPROVAL
Building07/13/2018Approved Sheet A-101 CODE PLAN: Please note that if restroom doors are provided with a closer and latch, 48" maneuvering clearance will be required at the push side of the doors, Section 404.2.3.2 of the 2009 ICC A117.1. FYI, closers are always required at food establishments by the Health department.*************** 06/26/18 As previously mentioned, a closer is required by the health department  more...
Building07/13/2018Approved Sheet AG-000 COVER SHEET: Please delete Sheet G1 as it is substituted with AG-000.
Building06/26/2018Approved Sheet A-101 CODE PLAN: The Accessibility Compliance Form is missing. ******************* 06/26/18 The form is still missing. Please upload the form.
Building06/26/2018Approved Sheet A-101 CODE PLAN: Provide a door hardware schedule for all existing and new doors.*************** 06/26/18 The response letter states that door hardware schedule is provided in sheet A-104. Sheet A-104 does not exist and the index does not show it as well. Please clarify.
Building06/26/2018Approved Sheet A-105 REFLECTED CEILING PLAN _ Layout: This Sheet (named A-105) has multiple sheets (12 others) attached to it. Please make sure to upload one sheet at a time.
Building06/26/2018Approved Sheet A-101 CODE PLAN: If the occupant load is less than 50, the tenant use group shall be classified as B use, Section 303.1.1.*********** 06/26/18 Section 303.1.1 states that an assembly tenant that is less than 50 occupants "shall" be classified as a Group B occupancy.
Building06/26/2018Approved Sheet G-1 COVER SHEET: The Sheet Index is missing the MEP sheets. Please revise.*************** 06/26/18 The revised sheets shall be named exactly as the original sheets submitted. A duplicate sheet that has been renamed creates an issue when the approved plan set is created. Both the original and the revised sheet will receive an approval stamp and create confusion on which is the correct sheet.  more...
Building05/31/2018Approved Sheet A-101 CODE PLAN: Occupant load calculations are incorrect. Please use the right load factors based on the function of each space in the tenant. For example, dining tables should be done at 15 SF/Occp, kitchen should be done at 200 SF/Occp, restrooms and circulation areas should be done at 100 SF/Occp, if queuing is anticipated it should be done at 5 SF/Occp. Please revise and show on the  more...
Building05/31/2018Approved Sheet G-1 COVER SHEET: Sheet A-104 Partition Plan is missing.
Building05/31/2018Approved Sheet A-105 REFLECTED CEILING PLAN _ Layout: It appears to be that the wrong sheet has been uploaded. Instead of G-1, this sheet should show A-105 Reflected Ceiling Plan. Please revise.
DES:Water/Sewer Engineering08/02/2018No review required --N/A--
DES:Water/Sewer Engineering06/07/2018Eplan Review Note TEANT IMPROVMENT (NEW) PLAN ICE CREAM TAKE OUT**APPROVED FOR 22.00 NEW DFUS
EPlan Review08/02/2018Approved --N/A--
Fire Prevention07/30/2018No review required no fire review required
Zoning 06/04/2018Approved Status: Rejected Note: Provide the information of the storefront changes approved on admin change ZADM180368 or explain if the storefront work will be submitted on a separate permit. Site Plan: 106 Zoning District: C-O-1.5 Work Area: 1,167 ft² Description: Tenant improvement plan ice cream takeout. Reviewer: José Gómez E-mail: jgomez-acevedo@arlingtonva.us