Permit #B1802418
Address2800 CLARENDON BLVD
TypeCTBO
StatusFINALED
Permit HolderTESLA
OwnerCLARENDON REGENCY I LLC % REGENCY CENTERS
Applied Date08/29/2018
Approved Date11/26/2018
Date Issued11/26/2018
DescriptionTESLA IS PROPOSING TO INSTALL AN ELECTRIC VEHICLE CHARGING STATION AT THE TOP LEVEL OF THE PARKING GARAGE AND THEN EQUIPMENT CABINETS ON 2 FLOORS AND SWITCHGEAR IN THE ELECTRIC ROOM SPECIAL INSPECTIONS REQUIRED.

View Event Log.      View Status.    View Required Plan Review       View Printer Version.

Review   Review       Date Status   Comments   
Building10/17/2018Approved Plans rejected and returned to customer to complete uploads.
Building09/04/2018Approved Sheet E-003 Electrical Overall Utility Plan: Sheet E-1: Confirm that the proposed ceiling mounted conduits to proposed distribution panels shall not decrease the clear ceiling height to less than 98 inches on the vehicular path to the accessible parking spaces (Section 502.6 of the ICC A117.1-2009).
Building09/04/2018Approved Sheet C-006 Civil Site Plan: Clarify whether the existing door shown on Sheet C-3 SITE PLAN- LEVEL 1 is : - An EXIT door? - Serving an occupied space? It is important to know this because all exit doors must provide a minimum maneuvering space of at least 60 inches measured perpendicular from the hinge side of door (See Fig. (a) of 404.2.3.2/ ICC A117.1-2009.
Building09/04/2018Approved Sheet E-003 Electrical Overall Utility Plan: Sheet E-1: The Scope of work includes Core drilling through the existing 12 inch concrete Shear Wall: Provide a clear statement which must indicate that the proposed core drilling through the structural shear wall shall not affect the structural integrity nor the structural functionality of the Shear wall.
Building09/04/2018Approved Sheet E-004 Electrical Equipment Plan: Please clearly show the location and number of the new/proposed ACCESSIBLE electrical Charging stations. Thank you,
Building09/04/2018Approved Sheet E-008 Electrical Details: Sheet E-008: Note 2 Drawing number 3: Please specify the EXACT clear height of head room. Bear in mind that the minimum clear height that must be maintained from Parking entrance to Accessible VAN parking space shall not be less that 8 feet- 2 inches (98 inches) in accordance with Section 502.6 of the ICC A117.1-2009.
Building09/04/2018Approved Sheet C-008 Civil Civil Details: Sheet C-5: Provide/show exact location of proposed chain link fence (show on plan and elevation views please).
Building09/04/2018Approved Sheet C-010 Civil Pergola Detail: all SUBMITTED PLANS: Please remove the note stating: FOR REFERENCE ONLY
Building09/04/2018Approved Sheet C-008 Civil Civil Details: Sheet C-008: Bollards: Bollards shall be designed in accordance with the loading requirements of Section 1607.8.3 of the VCC 2012.
Building09/04/2018Approved Sheet C-010 Civil Pergola Detail: Sheet C-7: PERGOLA CONSTRUCTION: The use of combustible materials (pergola) in Non-Combustible type of construction (Type I and II construction) is included in Section 603 of the Virginia Construction Code (VCC 2012). The new Pergola includes combustible materials which is NOT permitted in type I and II construction. Reference; Section 603.1 and the list of 25  more...
Building09/04/2018Approved Sheet E-004 Electrical Equipment Plan: Existing electrical rooms on ALL floors where the scope of this project includes electrical equipment rated at 1200 amperes or more: ** Provide Panic Hardware for the electrical equipment room, throughout ALL floors showing that door shall swing in direction of egress; Section 1008.1.10 of the VCC 2012.
Building09/04/2018Approved Sheet C-001 Civil Cover Sheet General Information: Sheet C-001: 1- Please reference the Building and MEP codes as Amended by Virginia: Virginia Construction Code VCC 2012 Mechanical: VMC 2012 Electrical: NEC 2011 Plumbing: VPC 2012 Accessibility: ICC A117.1-2009. 2- Remove the statement "In the event of conflict, the most restrictive code shall apply": This statement is redundant and is  more...
Building09/04/2018Approved Sheet C-010 Civil Pergola Detail: ALL SHEETS SUBMITTED SHALL BE SIGNED AND SEALED BY A VIRGINIA REGISTERED DESIGN PROFESSIONAL.
Building09/04/2018Approved Sheet X-001 Survey Topographic Survey: 1- ALL SHEETS MUST BEAR THE ORIGINAL SIGNED SEAL OF A VIRGINIA REGISTERED DESIGN PROFESSIONAL. 2- REMOVE/DELETE THE STATEMENT "FOR REFERENCE ONLY" FROM ALL SHEETS.
DES:Water/Sewer Engineering10/30/2018Eplan Review Note INSTALLING AN ELECTRICAL VEHICLE CHARGNG STATION. NO PLUMBING. APPROVED
Electrical 09/04/2018Approved Provide a layout of the Panels on the parking decks, Clearances, Illumination,
Electrical 09/04/2018Approved Provide a room layout of the MDP, 2500A NEW Service.
EPlan Review11/26/2018Approved --N/A--
Structural 10/26/2018Approved Special Inspections: REJECTED. Only one sheet was submitted. Please submit the whole packet. For items that are not relevant to the project either mark N/A or leave blank. Provide the following: 1. Sheet 43: Provide Owner, SER, SIER, and GC information. This includes address, license, email, and phone number. 2. Sheet 54: SIER signature on the bottom of the sheet 3. Sheet 60 and 61:  more...
Structural 09/05/2018Approved Arlington county statement of special inspection prepare by the SER shall be submitted, the statement shall be sign and initial by all appropriate parties
1 2