Permit #B2100260
Address2805 CLARENDON BLVD
TypeCTBO
StatusFINALED
Permit HolderPOTOMAC CONSTRUCTION SERVICES INC
OwnerCLARENDON REGENCY IV LLC % REGENCY CENTERS LP
Applied Date02/03/2021
Approved Date03/30/2021
Date Issued03/30/2021
DescriptionTENANT BUILD-OUT OF A NEW TATTE BAKERY WITHIN EXISTING CORE AND SHELL SPACE. THE WORK WILL CONSIST OF NEW INTERIOR PARTITIONS, FINISHES AND NEW MEP THROUGHOUT TO CONNECT TO BUILDING SERVICES. SPECIAL INSPECTIONS REQUIRED

View Event Log.      View Status.    View Required Plan Review       View Printer Version.

Review   Review       Date Status   Comments   
Building04/29/2021Approved Sheet Revision Narrative of Changes to Permit: Revision Narrative 15 April 2021 29 April 2021 Item 2: There is no requirement that the affected wall be fire rated.
Building03/25/2021Approved A-000 Architectural Cover Sheet 15 March 2021 SUBMIT AUTOMATIC SUPPRESSION SHOP DRAWINGS FOR APPROVAL SUBMIT FIRE ALARM SYSTEM SHOP DRAWINGS FOR APPROVAL
Building03/25/2021Approved A-000 Architectural Cover Sheet 15 March 2021 SUBMIT AUTOMATIC SUPPRESSION SHOP DRAWINGS FOR APPROVAL SUBMIT FIRE ALARM SYSTEM SHOP DRAWINGS FOR APPROVAL
DES:Water/Sewer Engineering02/17/2021Approved 40 NEW DFU'S
Electrical 02/09/2021Approved Code cycle is 2014 NEC. shown as NEC 2011 on sheet A-000,
Electrical 02/09/2021Approved Drawing list shows 7 electrical sheets, E sheets show 8 electrical sheets, Sheet E-104 Electrical roof plan is missing from the drawing List.
Electrical 02/09/2021Rejected Code cycle is 2014 NEC. shown as NEC 2011 on sheet A-000,
Electrical 02/09/2021Rejected Drawing list shows 7 electrical sheets, E sheets show 8 electrical sheets, Sheet E-104 Electrical roof plan is missing from the drawing List.
Electrical02/09/2021Approved Code cycle is 2014 NEC. shown as NEC 2011 on sheet A-000,
Electrical02/09/2021Approved Drawing list shows 7 electrical sheets, E sheets show 8 electrical sheets, Sheet E-104 Electrical roof plan is missing from the drawing List.
Energy02/17/2021Approved The architectural drawings indicate that new building thermal envelope (BTE) doors (101 and 102) are part of the scope of the permit. It is unclear if these doors satisfy the U-factor and SHGC requirements of Table C402.4 of the 2015 Virginia Energy Conservation Code (VECC). In addition, it is unclear if the new BTE doors will satisfy the air infiltration requirements of Table C402.5.2 of the  more...
Energy02/17/2021Approved Sheet E-703 includes an interior lighting COMcheck. The COMcheck appears to be incorrect in the following ways. First, there are exemptions claimed for several fixtures of the K and D type. Section C405.4 of the 2015 VECC does not allow for these fixtures to be exempt from the calculation. These emergency lighting fixtures are not exempt from the calculation because they are also used for  more...
Energy02/17/2021Approved Sheet P-702 includes a water heater detail. This drawing indicates that a hot water recirculation system is part of the scope of the permit. The pump is required by section C404.6.1 of the 2015 VECC to be fitted with automatic controls to turn off the recirculation pump when there is no hot water demand. In the resubmission, show automatic controls that will shut down the hot water  more...
Energy02/17/2021Approved The drawings indicate that walk-in coolers are part of the scope of the permit. The drawings do not call for cooler walls, floors and ceilings with R-values that satisfy the minimum requirements of section C403.2.16 of the 2015 VECC. In the resubmission, revise the drawings to satisfy the minimum R-value requirements of section C403.2.16 of the 2015 VECC for the walk-in cooler/freezers.
Energy02/17/2021Approved The drawings indicate new lighting and lighting controls for the walk-in coolers. It is unclear how the new lighting controls satisfy the requirements of section C405.2.1 (Occupant sensor controls) of the 2015 VECC. In the resubmission show a design that satisfies the requirements of section C405.2.1 of the 2015 VECC.
Energy 02/17/2021Rejected The drawings indicate that walk-in coolers are part of the scope of the permit. The drawings do not call for cooler walls, floors and ceilings with R-values that satisfy the minimum requirements of section C403.2.16 of the 2015 VECC. In the resubmission, revise the drawings to satisfy the minimum R-value requirements of section C403.2.16 of the 2015 VECC for the walk-in cooler/freezers.
Energy 02/17/2021Rejected The architectural drawings indicate that new building thermal envelope (BTE) doors (101 and 102) are part of the scope of the permit. It is unclear if these doors satisfy the U-factor and SHGC requirements of Table C402.4 of the 2015 Virginia Energy Conservation Code (VECC). In addition, it is unclear if the new BTE doors will satisfy the air infiltration requirements of Table C402.5.2 of the  more...
Energy 02/17/2021Rejected Sheet E-703 includes an interior lighting COMcheck. The COMcheck appears to be incorrect in the following ways. First, there are exemptions claimed for several fixtures of the K and D type. Section C405.4 of the 2015 VECC does not allow for these fixtures to be exempt from the calculation. These emergency lighting fixtures are not exempt from the calculation because they are also used for  more...
Energy 02/17/2021Rejected Sheet P-702 includes a water heater detail. This drawing indicates that a hot water recirculation system is part of the scope of the permit. The pump is required by section C404.6.1 of the 2015 VECC to be fitted with automatic controls to turn off the recirculation pump when there is no hot water demand. In the resubmission, show automatic controls that will shut down the hot water  more...
Energy 02/17/2021Rejected The drawings indicate new lighting and lighting controls for the walk-in coolers. It is unclear how the new lighting controls satisfy the requirements of section C405.2.1 (Occupant sensor controls) of the 2015 VECC. In the resubmission show a design that satisfies the requirements of section C405.2.1 of the 2015 VECC.