Permit #B2102067
Address4238 WILSON BLVD
TypeCTBO
StatusFINALED
Permit HolderEXCELL CONTRACTORS INC
OwnerFC BALLSTON COMMON LLC
Applied Date08/26/2021
Approved Date12/17/2021
Date Issued12/22/2021
DescriptionAPPROX. 2,217 SF INTERIOR TENANT BUILD-OUT FOR AN IMMERSIVE GROUP GAMING ENTERTAINMENT FACILITY. TENANT SPACE IS LOCATED ON THE SECOND FLOOR OF AN EXISTING SHOPPING MALL. SUITE 2233

View Event Log.      View Status.    View Required Plan Review       View Printer Version.

Review   Review       Date Status   Comments   
Building10/25/2021Approved Sheet A2-1 - FLOOR PLAN: It appears that the existing restroom may not be in full compliance of the accessibility requirements of the VCC. Please verify fixture clearances, grab bars and other provision for accessible toilets per 2009 ICC A117.1 Section 604. Modify Accessible Compliance Form as needed to reflect the condition of the tenant space. Code Reference: VCC Section 1102.1; 2009 ICC  more...
Building10/25/2021Approved Sheet A2-1 - FLOOR PLAN: It appears that the existing restroom may not be in full compliance of the accessibility requirements of the VCC. Please verify fixture clearances, grab bars and other provision for accessible toilets per 2009 ICC A117.1 Section 604. Modify Accessible Compliance Form as needed to reflect the condition of the tenant space. Code Reference: VCC Section 1102.1; 2009 ICC  more...
Building10/11/2021Additional Review Date: 10/11/21 The revised documents shall be named exactly as the original documents submitted. A duplicate document that has been renamed creates an issue when the approved plan set is created. Both the original and the revised documents will receive an approval stamp and create confusion on which is the correct document.
Building10/11/2021Approved Review Date: 10/11/21 The revised documents shall be named exactly as the original documents submitted. A duplicate document that has been renamed creates an issue when the approved plan set is created. Both the original and the revised documents will receive an approval stamp and create confusion on which is the correct document.
Building10/11/2021Approved Review Date: 10/11/21 The revised documents shall be named exactly as the original documents submitted. A duplicate document that has been renamed creates an issue when the approved plan set is created. Both the original and the revised documents will receive an approval stamp and create confusion on which is the correct document.
Building09/02/2021Approved Sheet A4-1 - DOOR SCHEDULE- DOOR DETAILS: Please specify accessible hardware to meet the accessible provision of the VCC and the ICC A117.1. Please note this requirement on the drawings. Code Reference: VCC Section 1010.1.9.1; 2009 ICC A117.1 Section 404.2.6,
Building09/02/2021Approved Sheet A4-1 - DOOR SCHEDULE- DOOR DETAILS: Please populate hardware set column on the door schedule to facilitate plan review.
Building09/02/2021Approved Sheet T1-1 - COVER SHEET: Please note the correct construction type on the drawing. Construction type is Type II-B and not Type III-B.
Building09/02/2021Approved Sheet T1-1 - COVER SHEET: Minimum required corridor width shall be not less than 44” as required by Table 1020.2 of the Virginia Construction Code. Code Reference: VCC Section 1020.2
Building09/02/2021Approved Sheet A2-1 - FLOOR PLAN: The plans show an occupant load of 55 for the tenant space. The space requires a minimum of 2 means of egress with egress doors opening in the direction of travel. Please show egress doors swing open in the direction of travel. Code Reference: VCC Section 1010.1.2
Building09/02/2021Additional Sheet A4-1 - DOOR SCHEDULE- DOOR DETAILS: Please specify accessible hardware to meet the accessible provision of the VCC and the ICC A117.1. Please note this requirement on the drawings. Code Reference: VCC Section 1010.1.9.1; 2009 ICC A117.1 Section 404.2.6,
Building09/02/2021Additional Sheet A4-1 - DOOR SCHEDULE- DOOR DETAILS: Please populate hardware set column on the door schedule to facilitate plan review.
Building09/02/2021Additional Sheet T1-1 - COVER SHEET: Please note the correct construction type on the drawing. Construction type is Type II-B and not Type III-B.
Building09/02/2021Additional Sheet T1-1 - COVER SHEET: Minimum required corridor width shall be not less than 44” as required by Table 1020.2 of the Virginia Construction Code. Code Reference: VCC Section 1020.2
Building09/02/2021Additional Sheet A2-1 - FLOOR PLAN: The plans show an occupant load of 55 for the tenant space. The space requires a minimum of 2 means of egress with egress doors opening in the direction of travel. Please show egress doors swing open in the direction of travel. Code Reference: VCC Section 1010.1.2
Building09/02/2021Additional Sheet A2-1 - FLOOR PLAN: It appears that the existing restroom may not be in full compliance of the accessibility requirements of the VCC. Please verify fixture clearances, grab bars and other provision for accessible toilets per 2009 ICC A117.1 Section 604. Modify Accessible Compliance Form as needed to reflect the condition of the tenant space. Code Reference: VCC Section 1102.1; 2009 ICC  more...
Building09/02/2021Additional Reviewed under the 2018 Virginia Construction Code and the Virginia Uniform Statewide Building Code (VUSBC). Please correct any references to VUSRC. The 2018 Virginia Construction Code can be found for free online at https://codes.iccsafe.org/category/Virginia If you have questions regarding this building plan review, please contact me via email at aawofisayo@arlingtonva.us or by telephone at  more...
Building09/02/2021Approved Reviewed under the 2018 Virginia Construction Code and the Virginia Uniform Statewide Building Code (VUSBC). Please correct any references to VUSRC. The 2018 Virginia Construction Code can be found for free online at https://codes.iccsafe.org/category/Virginia If you have questions regarding this building plan review, please contact me via email at aawofisayo@arlingtonva.us or by telephone at  more...
Building09/02/2021Approved Reviewed under the 2018 Virginia Construction Code and the Virginia Uniform Statewide Building Code (VUSBC). Please correct any references to VUSRC. The 2018 Virginia Construction Code can be found for free online at https://codes.iccsafe.org/category/Virginia If you have questions regarding this building plan review, please contact me via email at aawofisayo@arlingtonva.us or by telephone at  more...
Building09/02/2021Approved Sheet A4-1 - DOOR SCHEDULE- DOOR DETAILS: Please specify accessible hardware to meet the accessible provision of the VCC and the ICC A117.1. Please note this requirement on the drawings. Code Reference: VCC Section 1010.1.9.1; 2009 ICC A117.1 Section 404.2.6,
1 2 3 4 5