Review   Review       Date Status   Comments   
Building02/25/2022Approved Sheet A020 - DOORS AND WINDOWS: Doors must comply with 1010.1.1 VCC 2018 with a clear opening width of 32". I don't see an exception for door 102 here. ------------------------------------------------------------------------------------------------------------- UPDATED REVIEW COMMENT 2/25/2022: A 36" wide door yields a 32" clear width. A 34" wide door may also, depending on the jamb and  more...
Building02/25/2022Approved Sheet A020 - DOORS AND WINDOWS: Doors must comply with 1010.1.1 VCC 2018 with a clear opening width of 32". I don't see an exception for door 102 here. ------------------------------------------------------------------------------------------------------------- UPDATED REVIEW COMMENT 2/25/2022: A 36" wide door yields a 32" clear width. A 34" wide door may also, depending on the jamb and  more...
Building01/14/2022Approved Sheet A020 - DOORS AND WINDOWS: With occupant load over 50, exit doors must have panic hardware or fire exit hardware if latching. Also, door 108 is in a 2 hour fire rated separation and must comply with Table 716.1(2). Fire rated hardware required.
Building01/14/2022Approved Sheet A103 - PATIO PLANS: Maintain a 44" min. clear width egress path to the public way. No response required.
Building01/14/2022Approved Sheet A020 - DOORS AND WINDOWS: Door type D3 (two doors in the Kitchen) - one leaf must meet the 32" min. opening clear width requirement of 1010.1.1 VCC 2018. I don't see an exception here.
Building01/14/2022Approved Sheet A020 - DOORS AND WINDOWS: With occupant load over 50, exit doors must have panic hardware or fire exit hardware if latching. Also, door 108 is in a 2 hour fire rated separation and must comply with Table 716.1(2). Fire rated hardware required.
Building01/14/2022Approved Sheet A103 - PATIO PLANS: Maintain a 44" min. clear width egress path to the public way. No response required.
Building01/14/2022Approved Sheet A020 - DOORS AND WINDOWS: Door type D3 (two doors in the Kitchen) - one leaf must meet the 32" min. opening clear width requirement of 1010.1.1 VCC 2018. I don't see an exception here.
Building01/14/2022Approved Sheet A701 - INT DTLS: Detail 6 - construction must be non-combustible or FRT Class A to comply with 603.1 VCC 2018.
Building01/14/2022Approved Sheet A701 - INT DTLS: Detail 6 - construction must be non-combustible or FRT Class A to comply with 603.1 VCC 2018.
Building01/14/2022Rejected Sheet A701 - INT DTLS: Detail 6 - construction must be non-combustible or FRT Class A to comply with 603.1 VCC 2018.
Building01/14/2022Rejected Sheet A020 - DOORS AND WINDOWS: Doors must comply with 1010.1.1 VCC 2018 with a clear opening width of 32". I don't see an exception for door 102 here.
Building01/14/2022Rejected Sheet A020 - DOORS AND WINDOWS: With occupant load over 50, exit doors must have panic hardware or fire exit hardware if latching. Also, door 108 is in a 2 hour fire rated separation and must comply with Table 716.1(2). Fire rated hardware required.
Building01/14/2022Rejected Sheet A103 - PATIO PLANS: Maintain a 44" min. clear width egress path to the public way. No response required.
Building01/14/2022Rejected Sheet A020 - DOORS AND WINDOWS: Door type D3 (two doors in the Kitchen) - one leaf must meet the 32" min. opening clear width requirement of 1010.1.1 VCC 2018. I don't see an exception here.
Building01/13/2022Rejected Sheet A003 - EGRESS - OCCUP: Provide a matrix or list interior seats separately from exterior seats, so that the quantity of accessible seating can be calculated independently. Show accessible seats on plan. The total accessible seating for exterior should be equally distributed as well as in the interior.
Building01/13/2022Approved Sheet A003 - EGRESS - OCCUP: Provide a matrix or list interior seats separately from exterior seats, so that the quantity of accessible seating can be calculated independently. Show accessible seats on plan. The total accessible seating for exterior should be equally distributed as well as in the interior.
Building01/13/2022Approved Sheet A003 - EGRESS - OCCUP: Provide a matrix or list interior seats separately from exterior seats, so that the quantity of accessible seating can be calculated independently. Show accessible seats on plan. The total accessible seating for exterior should be equally distributed as well as in the interior.
DES:Water/Sewer Engineering01/07/2022Approved CTBO INT ALT DFUS COUNTED AND APPROVED 42 NEW DFUS
Electrical01/18/2022Approved There appears to be a discrepancy in regards to the electrical equipment located in the 'Office Area'. The electrical riser diagram indicates 'existing', however, the electrical floor plan indicates 'new'. Please clarify. Refer to sheets E201 and E302.