Building | 05/25/2022 | Approved |
Plan review cycle ended and plans returned at submitter's request to add new revision..
|
Building | 05/25/2022 | Approved |
Plan review cycle ended and plans returned at submitter's request to add new revision..
|
Building | 04/14/2022 | Approved |
Sheet A106 DOOR AND WALL TYPES: DEADBOLTS AT RESTROOM DOORS TO HAVE ELONGATED (ACCESSIBLE) THUMBTURNS
|
Building | 04/14/2022 | Approved |
Sheet A106 DOOR AND WALL TYPES: REFER TO A117.1, SECTION 404.2.10. VISION PANELS ON DOORS TO BE 43" AFF MAX TO BOTTOM OF PANEL
|
Building | 04/14/2022 | Approved |
Sheet 00 CERTIFICATE OF OCCUPANCY APPLICATION: CERTIFICATE FOR OCCUPANCY APPLICATION IS NOT APPLIED THROUGH THE BUILDING PERMIT. A SEPARATE SUBMISSION IS REQUIRED
|
Building | 04/14/2022 | Approved |
Sheet A000 COVER SHEET: SUBMIT FIRE ALARM SHOP DRAWINGS FOR APPROVAL
|
Building | 04/14/2022 | Approved |
Sheet A106 DOOR AND WALL TYPES: DEADBOLTS AT RESTROOM DOORS TO HAVE ELONGATED (ACCESSIBLE) THUMBTURNS
|
Building | 04/14/2022 | Approved |
Sheet A106 DOOR AND WALL TYPES: REFER TO A117.1, SECTION 404.2.10. VISION PANELS ON DOORS TO BE 43" AFF MAX TO BOTTOM OF PANEL
|
Building | 04/14/2022 | Approved |
Sheet 00 CERTIFICATE OF OCCUPANCY APPLICATION: CERTIFICATE FOR OCCUPANCY APPLICATION IS NOT APPLIED THROUGH THE BUILDING PERMIT. A SEPARATE SUBMISSION IS REQUIRED
|
Building | 04/14/2022 | Approved |
Sheet A000 COVER SHEET: SUBMIT FIRE ALARM SHOP DRAWINGS FOR APPROVAL
|
Building | 04/14/2022 | Approved |
Sheet A106 DOOR AND WALL TYPES: DEADBOLTS AT RESTROOM DOORS TO HAVE ELONGATED (ACCESSIBLE) THUMBTURNS
|
Building | 04/14/2022 | Approved |
Sheet A106 DOOR AND WALL TYPES: REFER TO A117.1, SECTION 404.2.10. VISION PANELS ON DOORS TO BE 43" AFF MAX TO BOTTOM OF PANEL
|
Building | 04/14/2022 | Approved |
Sheet 00 CERTIFICATE OF OCCUPANCY APPLICATION: CERTIFICATE FOR OCCUPANCY APPLICATION IS NOT APPLIED THROUGH THE BUILDING PERMIT. A SEPARATE SUBMISSION IS REQUIRED
|
Building | 04/14/2022 | Approved |
Sheet A000 COVER SHEET: SUBMIT FIRE ALARM SHOP DRAWINGS FOR APPROVAL
|
Building | 03/11/2022 | Approved |
Sheet A106 DOOR AND WALL TYPES: Refer to Section 603 and Section 803.13. Building construction type shown as 2B construction. Non combustible or FRT required for underlayment/sheathing on partitions.
****************03/11/22 - Narrative states change was made to this sheet, but this sheet has not been updated. Comment remains
|
Building | 03/11/2022 | Approved |
Sheet A106 DOOR AND WALL TYPES: Refer to Section 1010.1.1. Min 32" clear door opening required measured door face to jamb. Both restroom doors (type 1)scheduled as 30" wide. In addition, BOH door (type 2) is a double door with 2 - 1'-6" leaves. One leaf in a pair is required to meet the 32" clearance requirement.
***************03/11/22 - Narrative states revision change, but no change more...
|
Building | 03/11/2022 | Approved |
Sheet A104-1 SITE AND INTERIOR PLANS: Stair to new door is new. Provide framing/ structural information and details to show compliance. Provide dimensions for stair and landing (landing does not appear compliant). Comply with Section 1011. Handrails and guard (if required) to Comply with Sections 1014 and 1015, including handrail extensions
*******************03/11/22 - New structural and more...
|
Building | 03/11/2022 | Approved |
Sheet A400 RESTROOM PLAN: Door approach from inside ADA WC is not adequate if door has a closer. I don't see a closer specified on current door hardware., but it is typically added when a door is spec'd with push/ pull hardware. Please coordinate and confirm
|
Building | 03/11/2022 | Approved |
Sheet A106 DOOR AND WALL TYPES: Door 3 is marked as exit only on plans. No operating hardware is permitted on exterior if this door is required to be exit only
|
Building | 03/11/2022 | Approved |
Sheet A003 LIFE SAFETY: Refer to Section 1011.2 - Stair to be min. 44" wide.
|