Permit #B2200196
Address4710 LANGSTON BLVD
TypeCTBO
StatusAPPLIED
Permit HolderCONTRACTOR TBD
OwnerJAMES WILSON CONSTITUTIONAL SOCIETY LLC
Applied Date02/01/2022
Approved Date 
Date Issued 
DescriptionNEW TENANT BUILD OUT FOR COFFEE CAFE, INTERIOR DEMO, NEW MECHANICAL, PLUMBING, ELECTRICAL, COFFEE EQUIPMENT, FIXTURES, AND FURNITURE. CHANGE OF USE FROM B TO A-2.

View Event Log.      View Status.    View Required Plan Review       View Printer Version.

Review   Review       Date Status   Comments   
Building05/25/2022Approved Plan review cycle ended and plans returned at submitter's request to add new revision..
Building05/25/2022Approved Plan review cycle ended and plans returned at submitter's request to add new revision..
Building04/14/2022Approved Sheet A106 DOOR AND WALL TYPES: DEADBOLTS AT RESTROOM DOORS TO HAVE ELONGATED (ACCESSIBLE) THUMBTURNS
Building04/14/2022Approved Sheet A106 DOOR AND WALL TYPES: REFER TO A117.1, SECTION 404.2.10. VISION PANELS ON DOORS TO BE 43" AFF MAX TO BOTTOM OF PANEL
Building04/14/2022Approved Sheet 00 CERTIFICATE OF OCCUPANCY APPLICATION: CERTIFICATE FOR OCCUPANCY APPLICATION IS NOT APPLIED THROUGH THE BUILDING PERMIT. A SEPARATE SUBMISSION IS REQUIRED
Building04/14/2022Approved Sheet A000 COVER SHEET: SUBMIT FIRE ALARM SHOP DRAWINGS FOR APPROVAL
Building04/14/2022Approved Sheet A106 DOOR AND WALL TYPES: DEADBOLTS AT RESTROOM DOORS TO HAVE ELONGATED (ACCESSIBLE) THUMBTURNS
Building04/14/2022Approved Sheet A106 DOOR AND WALL TYPES: REFER TO A117.1, SECTION 404.2.10. VISION PANELS ON DOORS TO BE 43" AFF MAX TO BOTTOM OF PANEL
Building04/14/2022Approved Sheet 00 CERTIFICATE OF OCCUPANCY APPLICATION: CERTIFICATE FOR OCCUPANCY APPLICATION IS NOT APPLIED THROUGH THE BUILDING PERMIT. A SEPARATE SUBMISSION IS REQUIRED
Building04/14/2022Approved Sheet A000 COVER SHEET: SUBMIT FIRE ALARM SHOP DRAWINGS FOR APPROVAL
Building04/14/2022Approved Sheet A106 DOOR AND WALL TYPES: DEADBOLTS AT RESTROOM DOORS TO HAVE ELONGATED (ACCESSIBLE) THUMBTURNS
Building04/14/2022Approved Sheet A106 DOOR AND WALL TYPES: REFER TO A117.1, SECTION 404.2.10. VISION PANELS ON DOORS TO BE 43" AFF MAX TO BOTTOM OF PANEL
Building04/14/2022Approved Sheet 00 CERTIFICATE OF OCCUPANCY APPLICATION: CERTIFICATE FOR OCCUPANCY APPLICATION IS NOT APPLIED THROUGH THE BUILDING PERMIT. A SEPARATE SUBMISSION IS REQUIRED
Building04/14/2022Approved Sheet A000 COVER SHEET: SUBMIT FIRE ALARM SHOP DRAWINGS FOR APPROVAL
Building03/11/2022Approved Sheet A106 DOOR AND WALL TYPES: Refer to Section 603 and Section 803.13. Building construction type shown as 2B construction. Non combustible or FRT required for underlayment/sheathing on partitions. ****************03/11/22 - Narrative states change was made to this sheet, but this sheet has not been updated. Comment remains
Building03/11/2022Approved Sheet A106 DOOR AND WALL TYPES: Refer to Section 1010.1.1. Min 32" clear door opening required measured door face to jamb. Both restroom doors (type 1)scheduled as 30" wide. In addition, BOH door (type 2) is a double door with 2 - 1'-6" leaves. One leaf in a pair is required to meet the 32" clearance requirement. ***************03/11/22 - Narrative states revision change, but no change  more...
Building03/11/2022Approved Sheet A104-1 SITE AND INTERIOR PLANS: Stair to new door is new. Provide framing/ structural information and details to show compliance. Provide dimensions for stair and landing (landing does not appear compliant). Comply with Section 1011. Handrails and guard (if required) to Comply with Sections 1014 and 1015, including handrail extensions *******************03/11/22 - New structural and  more...
Building03/11/2022Approved Sheet A400 RESTROOM PLAN: Door approach from inside ADA WC is not adequate if door has a closer. I don't see a closer specified on current door hardware., but it is typically added when a door is spec'd with push/ pull hardware. Please coordinate and confirm
Building03/11/2022Approved Sheet A106 DOOR AND WALL TYPES: Door 3 is marked as exit only on plans. No operating hardware is permitted on exterior if this door is required to be exit only
Building03/11/2022Approved Sheet A003 LIFE SAFETY: Refer to Section 1011.2 - Stair to be min. 44" wide.