Permit #B1900888
Address3101 WILSON BLVD
TypeCTBO
StatusFINALED
Permit HolderWATERPROOFING INC
Owner3101 WILSON LLC % THE JOHN AKRIDGE COMPANIES
Applied Date04/02/2019
Approved Date07/02/2019
Date Issued07/02/2019
DescriptionFIT-OUT OF EXISTING TENANT SPACE FOR COFFE SHOP. TO INCLUDE : MODIFICATION OF EXISTING REST ROOMS, INSTALLATION OF NEW FLOOR, CELLIN, CASEWORK. TO THE 1ST FLOOR FOR *EAST WEST CAFE** TENANT: EAST WEST CAFE FLOOR 1 SUITE -

  View Event Log.      View Status.       View Required Plan Review       View Printer Version.   
  
  
Search Again

 
ReviewBuilding
Review Date04/11/2019
StatusRejected
Comments
COMMERCIAL PLAN REVIEW
All projects are reviewed under the requirements outlined in the Virginia Uniform Statewide Building Code. A written response letter must accompany plan revisions. Please contact the Plans Examiner for any clarification of the comments.
Permit #:    B1900888    Applicable Code:    VUSBC 2015 Edition
Project Name :    EAST WEST CAFE    Plans Examiner:    Mohamed Ghiwane
Address:    3101 Wilson Blvd    Discipline:     Building
Review Date:    04/11/19    Phone Number:    703-228-0578
Review #:    1st    Fax Number:    703-228-7046
Revision Date:    NA    Email:    mghiwane@arlingtonva.us
            
    Sheet    Comments    Code Reference
1.    A100    Please provide elevation/construction details for the raised floor slabs.    
2.    A1/A500    Ramps shall be provided with edge protection complying with Section 1012.10. the bottom railing should prevent the passage of a 4" diameter sphere.    1012.10.1
3.    A100    A closer will be required at both restroom doors 105 and 106 per health department requirement. Therefore, a 54" maneuvering clearance from the pull side is required at both doors.    404.2.3.2 of the 2009 ICC A117.1
4.    A100    Please show the location of the required accessible seats on the plan.    1108.2.9.1
5.    A100    A portion of the service counter must be accessible. Please show elevation details for the accessible portion of the service counter.    904.3 of the 2009 ICC A117.1.
6.    A601    Doors 110 and 111 must be provided with panic hardware.    1010.1.10
7.    A100/A601    Please provide hardware set for the existing back of the house exit door. Please note that this door must be provided with a panic hardware.    1010.1.10
  



  
 