Search for Permits

Use the search below to get details on plan review activities and review comments on your plans. This information is updated Monday through Friday at 12:30 p.m. and 5:30 p.m.

Information returned on this page is valid through 6/27/2022. Incorporating the new permitting system data into this website is in progress. For current data requests, please contact PermitTechSupport@arlingtonva.us

 
Permit #B1900888
Address3101 WILSON BLVD
TypeCTBO
StatusFINALED
Permit HolderWATERPROOFING INC
Owner3101 WILSON LLC % THE JOHN AKRIDGE COMPANIES
Applied Date04/02/2019
Approved Date07/02/2019
Date Issued07/02/2019
DescriptionFIT-OUT OF EXISTING TENANT SPACE FOR COFFE SHOP. TO INCLUDE : MODIFICATION OF EXISTING REST ROOMS, INSTALLATION OF NEW FLOOR, CELLIN, CASEWORK. TO THE 1ST FLOOR FOR *EAST WEST CAFE** TENANT: EAST WEST CAFE FLOOR 1 SUITE -

  View Event Log.      View Status.       View Required Plan Review       View Printer Version.   
  
  
Search Again

 
ReviewPlumbing
Review Date04/10/2019
StatusRejected
Comments
COMMERCIAL PLAN REVIEW
All projects are reviewed under the requirements outlined in the Virginia Uniform Statewide Building Code. A written response letter must accompany plan revisions. Please contact the Plan Examiner for any clarification of the comments.
    
Permit #:     B1900888    Applicable Code:    VUSBC 2012 Edition
Project Name:    Cities Coffee    Plan Examiner:    Chris Martin
Address:    3101 Wilson Blvd    Discipline:     Plumbing
Review Date:    4/10/19    Phone Number:    703-228-3854
Review #:        Fax Number:    703-228-7046
Revision Date:    NA    Email:    cmmartin@arlingtonva.us
            
    Sheet    Comments    Code Reference
        Plumbing plan review comments    
1    A100     An occupancy of 154 requires 2 water closets for male and 2 water closets for females.     VPC 2015 Table 403.1
2    A100    Separate toilet facilities are required for each sex.    VPC 2015 403.2
3     P300    The gas riser diagram does not reference the gas fired make-up air unit as shown on K004. There is no BTU specified. Please Clarify     VPC 109
            
            
        Further comments may be forthcoming upon plan resubmission.    
            
  



  
 
Search Permits By:   Address
Permit Number
Date