ReviewElectrical
Review Date08/21/2017
StatusRejected
Comments
COMMERCIAL PLAN REVIEW
All projects are reviewed under the requirements outlined in the Virginia Uniform Statewide Building Code. A written response letter must accompany plan revisions. Please contact the Plan Examiner for any clarification of the comments. A detailed correction letter must be attached to the drawings for re-submittal.
Permit: B1702047        Applicable Code:     2012 VUSBC
Project: Gyu Kaku Restaurant        Plan Examiner:     Williams
Address: 1119 N Hudson St        Discipline:      Electrical
Review Date:
8-21-17
        Phone Number:
Email:      703-228-3973
Crawilliams@arlingtonva.us
            
            
            
            
            
            
    Sheet    Comments    Code Reference
1    
E00    
Why is the Virginia Power 600 ampere CT / Meter Base shown to be grounded? Please clarify.    109.3 of the Virginia Construction Code
2    E00    
New panel board 'B', being fed directly from the utility company, is 'required' to be properly grounded as an electrical service. NEC Article 250.20 (B) and 250. 24 (A) (1).    109.3 of the Virginia Construction Code
3    E00    The 'existing' 400 ampere service disconnect is 'required' to be properly grounded as an electrical service. NEC Article 250.20 (B) and 250.24 (A) (1).    109.3 of the Virginia Construction Code
4    E00    Please clarify why 'existing' panel board 'P' is shown to be grounded as an electrical service? The electrical riser diagram clearly shows this panel board being fed from the 'existing' 400 ampere service switch.    109.3 of the Virginia Construction Code
5    E00    Indicate on the drawings the ampere rating of the fuses located in the 'existing' 400 ampere service disconnect. NEC Article 240.6 (A) and 90.4.    109.3 of the Virginia Construction Code
6    E1.1    Show the location of the 'existing' 600 ampere CT / Meter Base and the 'existing' 400 ampere main service switch on the electrical floor plan.    109.3 of the Virginia Construction Code
7        
Based on the lack of information provided, the above comments may not constitute a complete list of requested information. Additional design information is required for the county to review for code compliance.    109.3 of the Virginia Construction Code
  



  
 