Search for Permits

Use the search below to get details on plan review activities and review comments on your plans. This information is updated Monday through Friday at 12:30 p.m. and 5:30 p.m.

Information returned on this page is valid through 6/27/2022. Incorporating the new permitting system data into this website is in progress. For current data requests, please contact PermitTechSupport@arlingtonva.us

 
Permit #B1702047
Address1119 N HUDSON ST
TypeCTBO
StatusFINALED
Permit HolderTOP SERVICES INC.
OwnerCLARENDON ALLEY LLC % EBR PROP LLC
Applied Date08/15/2017
Approved Date10/25/2017
Date Issued10/25/2017
DescriptionNEW TENANT LAYOUT - RESTUARANT

  View Event Log.      View Status.       View Required Plan Review       View Printer Version.   
  
  
Search Again

 
ReviewElectrical
Review Date09/20/2017
StatusRejected
Comments
COMMERCIAL PLAN REVIEW
All projects are reviewed under the requirements outlined in the Virginia Uniform Statewide Building Code. A written response letter must accompany plan revisions. Please contact the Plan Examiner for any clarification of the comments. A detailed correction letter must be attached to the drawings for re-submittal.
Permit: B1702047        Applicable Code:     2012 VUSBC
Project: Gyu Kaku        Plan Examiner:     Williams
Address: 1119 N Hudson Street        Discipline:      Electrical
2nd Review Date:
9-20-17
        Phone Number:
Email:      703-228-3973
Crawilliams@arlingtonva.us
            
            
            
            
            
            
    Sheet    Comments    Code Reference
1    
E1.1, E00    
Now that the 'existing' main electrical service equipment has been added to the floor plan, there appears to be approximately 10-20' (including bending radius'), of 'unfused' service entrance conductors located inside of the building to feed 'new' panel board 'B'. Service entrance conductors are 'required' to be terminated in a service disconnect means at the "nearest point of entrance of the service conductors". NEC Article 230.70 (A) (1) and 90.4.    109.3 of the Virginia Construction Code
2    E1.1, E00    
Additional design information is required for the county to review for code compliance. Additional comments may be forthcoming.    109.3 of the Virginia Construction Code
  



  
 
Search Permits By:   Address
Permit Number
Date