ReviewEnergy
Review Date12/20/2016
StatusApproved
Comments
The drawings indicate that new storefront will be installed. However, no information is presented regarding the Solar Heat Gain Coefficient (SHGC) of the glass used in the storefront system. Table C402.3 of the 2012 VECC requires that the storefront system glazing have an SHGC of not more than 0.40. In the resubmission, include additional information in the drawings that states the SHGC of the storefront glazing systems.
  



  
 