ReviewMechanical
Review Date03/24/2017
StatusApproved
Comments
Review Date: 3/24/17
Sheet M-1.1 Provide a plan and elevation show kitchen exhaust in relation to property lines.
VMC 506.3.13.2 Termination through an exterior wall.
Exhaust outlets shall be permitted to terminate through exterior walls where the smoke, grease, gases, vapors and odors in the discharge from such terminations do not create a public nuisance or a fire hazard. Such terminations shall not be located where protected openings are required by the International Building Code. Other exterior openings shall not be located within 3 feet (914 mm) of such terminations.
VMC 506.3.13.3 Termination location.
Exhaust outlets shall be located not less than 10 feet (3048 mm) horizontally from parts of the same or contiguous buildings, adjacent buildings and adjacent property lines and shall be located not less than 10 feet (3048 mm) above the adjoining grade level. Exhaust outlets shall be located not less than 10 feet (3048 mm) horizontally from or not less than 3 feet (914 mm) above air intake openings into any building.
  



  
 