Permit #B1803426
Address4201 WILSON BLVD
TypeCTBO
StatusFINALED
Permit HolderGR RESTORATION PAINTING INC.
OwnerJAMESTOWN PREMIER STAFFORD I LLC
Applied Date12/14/2018
Approved Date04/12/2019
Date Issued04/16/2019
DescriptionINTERIOR ALTERATION OF AN EXISTING SPACE FOR NEW TENANT, THAT INCLUDES NON-STRUCTURAL PARTITIONS, DOORS, FIXTURES AND RELATED. UNIT 140 - COREPOWER YOGA

  View Event Log.      View Status.       View Required Plan Review       View Printer Version.   
  
  
Search Again

 
ReviewEnergy
Review Date02/04/2019
StatusApproved
Comments
Sheet P002 indicates that a hot water recirculation system is part of the scope of the permit. The pump is required by section C404.6.1 of the 2015 VECC to be fitted with automatic controls to turn off when there is no hot water demand.
In the resubmission, show automatic controls that will shut down the hot water recirculation pump when there is no hot water demand.
***02/04/2019*** Comment not addressed. The aqua stat in note D maintains the temperature of the hot water in the loop, 24/7. It does not satisfy the code requirement to shut down the hot water loop during periods of no hot water demand. Typically a programmable timer is required to turn off the hot water recirculation pump and override the aqua stat so that hot water is not circulating in the system when not in use, such as in the middle of the night.
  



  
 