Permit #B2100260
Address2805 CLARENDON BLVD
TypeCTBO
StatusFINALED
Permit HolderPOTOMAC CONSTRUCTION SERVICES INC
OwnerCLARENDON REGENCY IV LLC % REGENCY CENTERS LP
Applied Date02/03/2021
Approved Date03/30/2021
Date Issued03/30/2021
DescriptionTENANT BUILD-OUT OF A NEW TATTE BAKERY WITHIN EXISTING CORE AND SHELL SPACE. THE WORK WILL CONSIST OF NEW INTERIOR PARTITIONS, FINISHES AND NEW MEP THROUGHOUT TO CONNECT TO BUILDING SERVICES. SPECIAL INSPECTIONS REQUIRED

  View Event Log.      View Status.       View Required Plan Review       View Printer Version.   
  
  
Search Again

 
ReviewEnergy
Review Date02/17/2021
StatusApproved
Comments
Sheet P-702 includes a water heater detail. This drawing indicates that a hot water recirculation system is part of the scope of the permit. The pump is required by section C404.6.1 of the 2015 VECC to be fitted with automatic controls to turn off the recirculation pump when there is no hot water demand. In the resubmission, show automatic controls that will shut down the hot water recirculation pump when there is no hot water demand. State the sequence of operations for the controls on the drawings.
  



  
 