Permit Comments
 
Permit #B1702047
Address1119 N HUDSON ST
TypeCTBO
StatusFINALED
Permit HolderTOP SERVICES INC.
OwnerCLARENDON ALLEY LLC % EBR PROP LLC
Applied Date15/08/2017
Approved Date25/10/2017
Date Issued25/10/2017
DescriptionNEW TENANT LAYOUT - RESTUARANT

ReviewReview DateStatusComments
Accessibility Review03/19/2018No review required--N/A--
Accessibility Review06/15/2018No review required--N/A--
Accessibility Review09/07/2017ApprovedACF marked box #1. VIF
Accessibility Review09/20/2017No review required--N/A--
Accessibility Review10/04/2017No review requiredrevision dated 10-2-17
Building03/23/2018ApprovedActive revision, 7 March 2018 Mechanical, Electrical revisions
Building06/15/2018Approved as NotedRevision for construction type change to IIIB
Building09/07/2017Approved--N/A--
Building09/29/2017Approvedrevisions to patio roof, shortening it. some structural changes to patio structure signed and sealed by xiaoyin zhang 029548
Building10/10/2017ApprovedResubmittal, 2 October 2017 Electrical, Mechanical
DES:Water/Sewer Engineering04/05/2018ApprovedACTIVE REVISION - NO PLUMBING
DES:Water/Sewer Engineering06/15/2018ApprovedACTIVE REVISION NO PLUMBING
DES:Water/Sewer Engineering10/25/2017ApprovedCTBO INT ALT ALL DFUS COUNTED AND APPROVED 4 DFU CREDITS
DHS: Health Plan Review08/24/2017Rejected--N/A--
DHS: Health Plan Review09/22/2017Approved--N/A--
Electrical03/19/2018ApprovedRevisons dated 3-7-18.
Electrical06/15/2018No review required--N/A--
Electrical08/21/2017Rejected COMMERCIAL PLAN REVIEW All projects are reviewed under the requirements outlined in the Virginia Uniform Statewide Building Code. A written response letter must accompany plan revisions. Please contact the Plan Examiner for any clarification of the comments. A detailed correction letter must be attached to the drawings for re-submittal. Permit: B1702047 Applicable Code: 2012 VUSBC Project: Gyu Kaku Restaurant Plan Examiner: Williams Address: 1119 N Hudson St Discipline: Electrical Review Date: 8-21-17 Phone Number: Email: 703-228-3973 Crawilliams@arlingtonva.us Sheet Comments Code Reference 1 E00 Why is the Virginia Power 600 ampe
Electrical09/20/2017RejectedCOMMERCIAL PLAN REVIEW All projects are reviewed under the requirements outlined in the Virginia Uniform Statewide Building Code. A written response letter must accompany plan revisions. Please contact the Plan Examiner for any clarification of the comments. A detailed correction letter must be attached to the drawings for re-submittal. Permit: B1702047 Applicable Code: 2012 VUSBC Project: Gyu Kaku Plan Examiner: Williams Address: 1119 N Hudson Street Discipline: Electrical 2nd Review Date: 9-20-17 Phone Number: Email: 703-228-3973 Crawilliams@arlingtonva.us Sheet Comments Code Reference 1 E1.1, E00 Now that the 'existing' mai
Electrical10/09/2017Approved as NotedInspector's Note: Per phone conversation with Mr.Khalifa (RDP), he said that the 'new' SE conductors to the new 225 ampere service disconnect (feeding panel board B), will be installed in the slab.This is in reference to the length of 'unfused' SE conductor inside of building. NEC Article 230.70 (A) (1). Riser shown on sheet E00, shows the conductors over head. Also, each service disconnect switch (exisiting and new), must be properly identified per NEC Article 230.2 (E)
Fire Prevention03/23/2018ApprovedActive revision, 7 March 2018 Mechanical, Electrical revisions
Fire Prevention06/15/2018No review required--N/A--
Fire Prevention08/28/2017No review required--N/A--
Fire Prevention10/10/2017No review requiredResubmittal, 2 October 2017
Mechanical03/19/2018ApprovedRevisions Dated 3-7-18
Mechanical06/15/2018No review required--N/A--
Mechanical08/22/2017RejectedCOMMERCIAL PLAN REVIEW All projects are reviewed under the requirements outlined in the Virginia Uniform Statewide Building Code. A written response letter must accompany plan revisions. Please contact the Plan Examiner for any clarification of the comments. Permit #: B1702047 Applicable Code: VUSBC 2012 Edition Project Name: GYU-KAKU Plan Examiner: Chris Martin Address: 1119 N. Hudson St. Discipline: Mechanical Review Date: 8/22/17 Phone Number: 703-228-3854 Review #: 1st Fax Number: 703-228-7046 Revision Date: Email: cmmartin@arlingtonva.us Sheet Comments Code Reference Mechanical plan review comments 1 M1.1 Note states see Hood Shop Drawings. There is no reference to the Type 1 hood with this submission VC
Mechanical09/20/2017ApprovedRevisions Dated 9-19-17
Mechanical10/04/2017No review requiredrevision dated 10-2-17
Plumbing03/19/2018No review required--N/A--
Plumbing06/15/2018No review required--N/A--
Plumbing08/21/2017RejectedCOMMERCIAL PLAN REVIEW Applicable Code: 2012 VPC, VMC, VFGC VUSBC 2012 Project Name:GYU-KAKU Plan Examiner: James Hemphill Address:1119 N Hudson St Arlington Va Discipline: PLM Review Date: 8-21-17 Phone Number: 703-228-3873 Review #:1 Fax Number: 703-228-7046 Revision Date: Email: jhemphill@arlingtonva.us Sheet Comments Code Reference P1 Please advise or correct, Gas piping size seems to be incorrect. Total BTU is 2311.5 as stated. 2012 VFGC 402.4 (2) 150Ft , starting run is 3". 2012 VFGC P1.3 Please supply complete existing GI calculations P1.3 What is the 4th drain at the 3 compartment sink? P1.3 Does the cooking Hood have a wash down system? P1.3 Please advise intent for
Plumbing09/20/2017RejectedCOMMERCIAL PLAN REVIEW Applicable Code: 2012 VPC, VMC, VFGC VUSBC 2012 Project Name: GYU-KAKU Plan Examiner: James Hemphill Address:1119 N Hudson St Arlington Va Discipline: PLM Review Date: 9-20-17 Phone Number: 703-228-3873 Review #:1 Fax Number: 703-228-7046 Revision Date: Email: jhemphill@arlingtonva.us Sheet Comments Code Reference Thank you for addressing past comments P1.2 BFP device required at inlet of Water filters. A 1022 BFP will be required at Beverage Disp 2012 VPC 608.3 / 608.16.1
Plumbing10/04/2017Approvedrevision dated 10-20-17
Special Inspection Required06/13/2018ApprovedSubmitted SSI packet. Originally no structural review was assigned.
Zoning03/08/2018NOTATIONThis plan was distributed to Liliana Rios - lrios@arlingtonva.us at 703 228 3889. Comments should be posted in approximately 10 Days.
Zoning03/16/2018ApprovedResubmittal, 2 October 2017 Electrical, Mechanical
Zoning06/15/2018ApprovedRevision dated: 6/15/2018 Sheet: A1.0 ISD revision.
Zoning08/16/2017NOTATIONThis plan was distributed to Liliana Rios at lrios@arlingtonva.us 703 228 3889. First Round comments should be posted in approximately 10 Days.
Zoning08/23/2017ApprovedNew Tenant Layout for a new restaurant - By-right building
Zoning09/20/2017NOTATIONThis plan was distributed to Liliana Rios at lrios@arlingtonva.us at 703 228 3889. Revision comments should be posted in approximately 10 Days.
Zoning09/29/2017ApprovedNew Tenant Layout for a new restaurant - By-right building "Separate approval is required for the outdoor café. For all site plan buildings, at least an administrative change is required. A CO for the main restaurant is required prior to the approval of this accessory use.
Zoning10/03/2017NOTATIONThis plan was distributed to Liliana Rios at lrios@arlingtonva.us . Revision comments should be posted in approximately 10 Days.
Zoning10/05/2017ApprovedRevisions dated 10-02-17 New Tenant Layout for a new restaurant - By-right building "Separate approval is required for the outdoor café. For all site plan buildings, at least an administrative change is required. A CO for the main restaurant is required prior to the approval of this accessory use.
Zoning10/25/2017ApprovedEWT per LOR office and builders set