Review | Review Date | Status | Comments |
Accessibility Review | 03/19/2018 | No review required | --N/A-- |
Accessibility Review | 06/15/2018 | No review required | --N/A-- |
Accessibility Review | 09/07/2017 | Approved | ACF marked box #1. VIF |
Accessibility Review | 09/20/2017 | No review required | --N/A-- |
Accessibility Review | 10/04/2017 | No review required | revision dated 10-2-17 |
Building | 03/23/2018 | Approved | Active revision, 7 March 2018
Mechanical, Electrical revisions |
Building | 06/15/2018 | Approved as Noted | Revision for construction type change to IIIB |
Building | 09/07/2017 | Approved | --N/A-- |
Building | 09/29/2017 | Approved | revisions to patio roof, shortening it. some structural changes to patio structure signed and sealed by xiaoyin zhang 029548 |
Building | 10/10/2017 | Approved | Resubmittal, 2 October 2017 Electrical, Mechanical |
DES:Water/Sewer Engineering | 04/05/2018 | Approved | ACTIVE REVISION - NO PLUMBING |
DES:Water/Sewer Engineering | 06/15/2018 | Approved | ACTIVE REVISION NO PLUMBING |
DES:Water/Sewer Engineering | 10/25/2017 | Approved | CTBO INT ALT ALL DFUS COUNTED AND APPROVED 4 DFU CREDITS |
DHS: Health Plan Review | 08/24/2017 | Rejected | --N/A-- |
DHS: Health Plan Review | 09/22/2017 | Approved | --N/A-- |
Electrical | 03/19/2018 | Approved | Revisons dated 3-7-18. |
Electrical | 06/15/2018 | No review required | --N/A-- |
Electrical | 08/21/2017 | Rejected |
COMMERCIAL PLAN REVIEW
All projects are reviewed under the requirements outlined in the Virginia Uniform Statewide Building Code. A written response letter must accompany plan revisions. Please contact the Plan Examiner for any clarification of the comments. A detailed correction letter must be attached to the drawings for re-submittal.
Permit: B1702047 Applicable Code: 2012 VUSBC
Project: Gyu Kaku Restaurant Plan Examiner: Williams
Address: 1119 N Hudson St Discipline: Electrical
Review Date:
8-21-17
Phone Number:
Email: 703-228-3973
Crawilliams@arlingtonva.us
Sheet Comments Code Reference
1
E00
Why is the Virginia Power 600 ampe |
Electrical | 09/20/2017 | Rejected | COMMERCIAL PLAN REVIEW
All projects are reviewed under the requirements outlined in the Virginia Uniform Statewide Building Code. A written response letter must accompany plan revisions. Please contact the Plan Examiner for any clarification of the comments. A detailed correction letter must be attached to the drawings for re-submittal.
Permit: B1702047 Applicable Code: 2012 VUSBC
Project: Gyu Kaku Plan Examiner: Williams
Address: 1119 N Hudson Street Discipline: Electrical
2nd Review Date:
9-20-17
Phone Number:
Email: 703-228-3973
Crawilliams@arlingtonva.us
Sheet Comments Code Reference
1
E1.1, E00
Now that the 'existing' mai |
Electrical | 10/09/2017 | Approved as Noted | Inspector's Note: Per phone conversation with Mr.Khalifa (RDP), he said that the 'new' SE conductors to the new 225 ampere service disconnect (feeding panel board B), will be installed in the slab.This is in reference to the length of 'unfused' SE conductor inside of building. NEC Article 230.70 (A) (1). Riser shown on sheet E00, shows the conductors over head. Also, each service disconnect switch (exisiting and new), must be properly identified per NEC Article 230.2 (E) |
Fire Prevention | 03/23/2018 | Approved | Active revision, 7 March 2018
Mechanical, Electrical revisions |
Fire Prevention | 06/15/2018 | No review required | --N/A-- |
Fire Prevention | 08/28/2017 | No review required | --N/A-- |
Fire Prevention | 10/10/2017 | No review required | Resubmittal, 2 October 2017 |
Mechanical | 03/19/2018 | Approved | Revisions Dated 3-7-18 |
Mechanical | 06/15/2018 | No review required | --N/A-- |
Mechanical | 08/22/2017 | Rejected | COMMERCIAL PLAN REVIEW
All projects are reviewed under the requirements outlined in the Virginia Uniform Statewide Building Code. A written response letter must accompany plan revisions. Please contact the Plan Examiner for any clarification of the comments.
Permit #: B1702047 Applicable Code: VUSBC 2012 Edition
Project Name: GYU-KAKU Plan Examiner: Chris Martin
Address: 1119 N. Hudson St. Discipline: Mechanical
Review Date: 8/22/17 Phone Number: 703-228-3854
Review #: 1st Fax Number: 703-228-7046
Revision Date: Email: cmmartin@arlingtonva.us
Sheet Comments Code Reference
Mechanical plan review comments
1 M1.1 Note states see Hood Shop Drawings. There is no reference to the Type 1 hood with this submission VC |
Mechanical | 09/20/2017 | Approved | Revisions Dated 9-19-17 |
Mechanical | 10/04/2017 | No review required | revision dated 10-2-17 |
Plumbing | 03/19/2018 | No review required | --N/A-- |
Plumbing | 06/15/2018 | No review required | --N/A-- |
Plumbing | 08/21/2017 | Rejected | COMMERCIAL PLAN REVIEW
Applicable Code: 2012 VPC, VMC, VFGC VUSBC 2012
Project Name:GYU-KAKU
Plan Examiner: James Hemphill
Address:1119 N Hudson St
Arlington Va
Discipline: PLM
Review Date: 8-21-17 Phone Number: 703-228-3873
Review #:1
Fax Number: 703-228-7046
Revision Date:
Email: jhemphill@arlingtonva.us
Sheet Comments Code Reference
P1 Please advise or correct, Gas piping size seems to be incorrect. Total BTU is 2311.5 as stated. 2012 VFGC 402.4 (2) 150Ft , starting run is 3". 2012 VFGC
P1.3 Please supply complete existing GI calculations
P1.3 What is the 4th drain at the 3 compartment sink?
P1.3 Does the cooking Hood have a wash down system?
P1.3 Please advise intent for |
Plumbing | 09/20/2017 | Rejected | COMMERCIAL PLAN REVIEW
Applicable Code: 2012 VPC, VMC, VFGC VUSBC 2012
Project Name: GYU-KAKU
Plan Examiner: James Hemphill
Address:1119 N Hudson St
Arlington Va
Discipline: PLM
Review Date: 9-20-17 Phone Number: 703-228-3873
Review #:1
Fax Number: 703-228-7046
Revision Date:
Email: jhemphill@arlingtonva.us
Sheet Comments Code Reference
Thank you for addressing past comments
P1.2 BFP device required at inlet of Water filters. A 1022 BFP will be required at Beverage Disp 2012 VPC 608.3 / 608.16.1
|
Plumbing | 10/04/2017 | Approved | revision dated 10-20-17 |
Special Inspection Required | 06/13/2018 | Approved | Submitted SSI packet. Originally no structural review was assigned. |
Zoning | 03/08/2018 | NOTATION | This plan was distributed to Liliana Rios - lrios@arlingtonva.us at 703 228 3889. Comments should be posted in approximately 10 Days. |
Zoning | 03/16/2018 | Approved | Resubmittal, 2 October 2017 Electrical, Mechanical |
Zoning | 06/15/2018 | Approved | Revision dated: 6/15/2018
Sheet: A1.0 ISD revision. |
Zoning | 08/16/2017 | NOTATION | This plan was distributed to Liliana Rios at lrios@arlingtonva.us 703 228 3889. First Round comments should be posted in approximately 10 Days. |
Zoning | 08/23/2017 | Approved | New Tenant Layout for a new restaurant - By-right building |
Zoning | 09/20/2017 | NOTATION | This plan was distributed to Liliana Rios at lrios@arlingtonva.us at 703 228 3889. Revision comments should be posted in approximately 10 Days. |
Zoning | 09/29/2017 | Approved | New Tenant Layout for a new restaurant - By-right building
"Separate approval is required for the outdoor café. For all site plan buildings, at least an administrative change is required. A CO for the main restaurant is required prior to the approval of this accessory use. |
Zoning | 10/03/2017 | NOTATION | This plan was distributed to Liliana Rios at lrios@arlingtonva.us . Revision comments should be posted in approximately 10 Days. |
Zoning | 10/05/2017 | Approved | Revisions dated 10-02-17
New Tenant Layout for a new restaurant - By-right building
"Separate approval is required for the outdoor café. For all site plan buildings, at least an administrative change is required. A CO for the main restaurant is required prior to the approval of this accessory use. |
Zoning | 10/25/2017 | Approved | EWT per LOR office and builders set |