Review | Review Date | Status | Comments |
Building | 05/02/2019 | Approved | Sheet A-004 ACCESSIBILITY STANDARDS: Sheet A-004:
On the interior view showing the accessible restroom toilet seat and grab bars. Show the toilet paper dispenser location in accordance with Section and Figure 604.7 of the A117.1-2009 (18" minimum from floor; 42" maximum from rear wall for surface mounted toilet paper dispenser. |
Building | 05/02/2019 | Approved | Sheet A-004 ACCESSIBILITY STANDARDS: Sheet A-004:
On the interior view showing the accessible restroom toilet seat and grab bars. You need to show the min. and max. height of the toilet seat measured form the rim of the seat. nit including the seat drop cover.
(Figure 604.4/A117.1-2009). |
Building | 05/03/2019 | Approved | Sheet A-016 PATIO DETAIL PLAN AND ELEVATIONS: Sheet A-016:
Note 4 mentions Civil Drawings; Do you have sheets under Civil Plans set? |
Building | 05/03/2019 | Approved | Sheet S-100 FRAMING PLAN SECTIONS AND DETAILS: Sheet S-100:
Please describe the method of attachment for the the canopy to the exterior wall (top and bottom). |
Building | 05/03/2019 | Approved | Sheet AI-301 RESTROOM PLAN and ELEVATIONS: Sheet AI-301:
You must show (on these drawings) Compliance with the following code sections for accessibility:
Section 604.5.1: FIXED SIDE WALL GRAB BARS (A117.1-2009)
Section 604.7; DISPENSERS
Section 606.3 HEIGHT (of lavatories)
|
Building | 05/03/2019 | Approved | Sheet E-003 ENERGY CODE CALCULATIONS: Sheet E-003:
NO CONTENT? |
Building | 05/03/2019 | Approved | Sheet A-701 WINDOW AND DOOR SCHEDULES and DETAILS: Tempered glazing in Hazardous Locations are described in Section 2406.4/VCC 2012 must be labeled in accordance with Section 2406.3/VCC 2012. |
Building | 05/03/2019 | Approved | Sheet A-013 ARCHITECTURAL SITE DETAILS: Architectural Site Details:
Provide detailed structural drawings for all concrete footings shown. |
Building | 05/03/2019 | Approved | Sheet A-101 BUILDING FLOOR PLAN: According to Section 2902.2 of the VCC 2012 Separate facilities are required for an occupant load exceeding 15. Therefore, please label each restroom according to gender. |
Building | 05/30/2019 | Approved | Sheet A-701 WINDOW AND DOOR SCHEDULES and DETAILS: Any Exit doors serving an assembly use with more than 49 occupants must comply with Section 1008.1.10 and be equipped with panic hardware (if door has a lath and/or lock).
|
DES:Engineering | 05/13/2019 | Approved | PULL & REPLACE LAVS & WC'S. REMOVING DF, INSTALLING 4 SINKS (3-HAND, 1 MOP) & 3-COMP SINK. 11.5 NEW DFUS COUNTED |
DES:Water/Sewer Engineering | 07/09/2019 | Approved | NO NEW DFU'S |
Energy | 05/13/2019 | Approved | EN-1) comment dated 5-13-19: Sheet A202, Note 8 - State in note 8, for the new infill wall areas, that new insulation to match the existing insulation's location and R-value shall be provided, per Virginia Rehab Code (VRC) section 403.1 General - Alterations shall be such that the existing building or structure is no less conforming to the provisions of the International Building Code than the existing building or structure was prior to the alteration. |
Energy | 05/13/2019 | Approved | EN-3) comment dated 5-13-19: Sheet A701 Window and Door Schedule - state on the drawing the air infiltration rates for all new windows and doors in the building thermal envelope, to comply with TABLE C402.4.3 MAXIMUM AIR INFILTRATION RATE FOR FENESTRATION ASSEMBLIES |
Energy | 05/13/2019 | Approved | EN-4) comment dated 5-13-19: Sheet A701 Window and Door Schedule - state on the drawing the U-factor and the SHGC for the DT storefront, to comply with section C402.3.3 Maximum U-factor and SHGC. It is not clear from the way the U-factor and SHGC are written for the storefront doors whether it also applies to the windows or not. |
Energy | 05/13/2019 | Approved | EN-5) comment dated 5-13-19: Sheet E401 Lighting Plan - clarify how the 2 workrooms meet the requirements for occupancy sesnors in section C405.2.2.2 Occupancy sensors. State on the drawings the max time before the occupancy sensors turn off, and state whether the occupancy sensors are manual on, or automatic on, and whether they are on to 100% power or 50% power. |
Energy | 05/13/2019 | Approved | EN-2) comment dated 5-13-19: Sheet A202, Note 8 - State in note 8, for the new infill wall areas, that new air barrier shall be provided to be made continuous with existing air barrier, per Virginia Rehab Code (VRC) section 403.1 General - Alterations shall be such that the existing building or structure is no less conforming to the provisions of the International Building Code than the existing building or structure was prior to the alteration. |
Energy | 05/13/2019 | Approved | EN-7) comment dated 5-13-19: Sheet P701 - Plumbing risers - schedule on the drawing the water heater, including its efficiency, to comply with TABLE C404.2 MINIMUM PERFORMANCE OF WATER-HEATING EQUIPMENT. |
Energy | 05/13/2019 | Approved | EN-8) comment dated 5-13-19: Resubmittal may result in additional comments . If you have questions regarding this energy code review, you can contact me via email at lbaskerville@arlingtonva.us, or on my work number 703-244-0479. |
Energy | 05/13/2019 | Approved | EN-9) comment dated 5-13-19: The Virginia Energy Conservation Code can be found free online at https://codes.iccsafe.org/content/VECC2012/chapter-4-ce-commercial-energy-efficiency |
Energy | 05/13/2019 | Approved | EN-10) comment dated 5-13-19: Please number your narrative responses with the identical EN-X number indicated in my comments. This significantly reduces the time required for review of your responses. Per VECC 109.4. |
Energy | 06/06/2019 | Approved | Sheet P-701 PLUMBING ISOMETRICS: EN-11 - Energy Plan Review Note - APPROVED AS NOTED - 6/6/19: Water heater shall meet or exceed the minimum efficiency requirement of Table C404.2 of the 2012 VECC. For the gas water heater listed in the schedule, the minimum efficiency is 80% thermal efficiency. |
Energy | 06/06/2019 | Approved | Sheet A-701 WINDOW AND DOOR SCHEDULES and DETAILS: EN-12 Energy Plan Reviewer note - APPROVED AS NOTED - Table C402.4.3 added to the drawing for reference for the energy inspector. |
Energy | 06/07/2019 | Approved |
EN-6) comment dated 6-7-19: The previous comment has not been addressed. Per our prior discussion, the central areas between the two doors may be considered as one daylighting zone, rather than 2 separate DZs with a couple lights requiring general lighting control sandwiched between the zones. Or you may choose to have 2 separate zones that abut each other so there is not a couple of track heads required to be on non-daylight zone control between the zones. But the manual daylight zone control(s) needs to be in the daylight zone area per the code section C405.2.2.3.
EN-6) comment dated 5-13-19: Sheet E401 Lighting Plan - clarify how the daylighting controls are met within the daylight zones, per section C405.2.2.3 Daylight zone |
EPlan Review | 08/08/2019 | Approved | --N/A-- |
Plumbing | 05/09/2019 | Approved | 5-9-19 Please advise or provide location of Tempering Device. 2012 VPC 607.1.2 |
Plumbing | 05/09/2019 | Approved | 5-9-19 Please provide complete Grab Bar dimensions. |
Plumbing | 05/09/2019 | Approved | 5-9-19 Please advise or provide location of BFP at the Water Filtration system. 2012 VPC 608.3 |
Structural | 06/10/2019 | Approved | Structural Review: REJECTED.
Please provide the live load for the canopy. |
Zoning | 05/09/2019 | Approved | Any reference to an outdoor seating need to be removed from the permit. An application for an outdoor seating can be requested after a certificate of occupancy for the interior seating is approved. |
Zoning | 05/09/2019 | Approved | On this permit no signs are approved. |
Zoning | 05/13/2019 | Approved | A determination letter by the ZA was found for the drive through. |
Zoning | 06/04/2019 | Approved | Fixed fencing for the future outdoor pad is not allowed. Only movable fencing is allowed for outdoor seating. Remove the fencing from the permit for the pad at the front of the retail space. |
Zoning | 06/04/2019 | Approved | The pad at the front of the retail space encroach on the front setback of the property. Due to that, the height of the pad must be less than 8 inches from the grade. |