Review | Review Date | Status | Comments |
Building | 10/26/2019 | Approved | Sheet A-7.2-Schedules and Details: Hardware sets HWS-01 through HWS-07 are not provided. Please show on the plans the different hardware sets used. |
Building | 12/02/2019 | Approved | Sheet 0CS_Cover Sheet: SUBMIT FIRE ALARM SHOP DRAWINGS FOR APPROVAL |
Building | 12/02/2019 | Approved | Sheet 0CS_Cover Sheet: SEPARATE PLAN AND PERMIT REQUIRED FOR DOORS WITH SPECIAL LOCKING HARDWARE |
Building | 12/02/2019 | Approved | Sheet 0CS_Cover Sheet: SUBMIT AUTOMATIC SUPPRESSION SHOP DRAWINGS FOR APPROVAL |
DES:Engineering | 11/05/2019 | Approved | CTBO INT ALT REMOVE AND REPLACE FIXTURES NO NEW DFUS |
DES:Water/Sewer Engineering | 09/21/2020 | Approved | ACTIVE REVISION NO DES CHANGES |
DES:Water/Sewer Engineering | 11/04/2020 | Approved | ACTIVE REVISION NO DES CHANGES |
DES:Water/Sewer Engineering | 12/10/2019 | Approved | CTBO INT ALT REMOVE AND REPLACE FIXTURES NO NEW DFUS |
Electrical | 10/08/2020 | No review required | --N/A-- |
EPlan Review | 07/08/2020 | Approved | --N/A-- |
Fire Prevention | 10/08/2020 | No review required | --N/A-- |
Mechanical | 10/08/2020 | No review required | --N/A-- |
Plumbing | 10/08/2020 | No review required | --N/A-- |
Public Health Division | 10/29/2019 | Approved | Sheet A-7.3-Floor Finish Plan: Confirm all refrigerators and freezers will be provided with accurate thermometers (± 2° F) and maintained at proper temperature. |
Public Health Division | 10/29/2019 | Approved | Sheet A-7.3-Floor Finish Plan: Complete and upload the Application for Foodservice Plan Review found on the Arlington County webpage.
https://health.arlingtonva.us/wp-content/uploads/sites/25/2013/12/PHD-Food-Service-Plan-Review-Application_Fillable.pdf |
Public Health Division | 10/29/2019 | Approved | Sheet A-7.3-Floor Finish Plan: Confirm there will be a certified food protection manager or certified food handler provided at the pre-opening inspection and at all hours of operation. |
Public Health Division | 10/29/2019 | Approved | Sheet A-7.3-Floor Finish Plan: Provide the food service equipment layout, with all food service identified in the equipment schedule. |
Special Inspection Required | 10/21/2020 | Rejected | Special Inspection required for the added canopy in the active revision. |
Special Inspection Required | 11/18/2020 | Approved | SSI - for canopy submitted. |
Structural | 10/21/2020 | Approved | The Statement of Special Inspection needs to be filled-in & submitted:
MUST HAVE:
1). OWNER, SIER, SER, & GC Contact information & Signatures, correct permit #, project address.
2). Initialed inspection boxes (applicable inspections) by SER & SIER
3). Owner, SIER, & SER signatures on inspections sheets.
The statement of special inspection is used by the structural engineer of record (SER) to identify the structural items that require special inspection. This is a legal statement that shall be filled out by the Structural Engineer of Record (SER). All applicable item lines of inspection shall be initialed by both the structural engineer of record (SER) and the special inspection engineer of record (SIER). This statement must contain |
Structural | 11/18/2020 | Approved | A-1.2 Plan Sheet: Need Structural Engineer's PE Seal for the structural design notes. |
Structural | 11/18/2020 | Approved | "A-4.1-Canopy..." drawing -
A). This scope of work requires a Structural Engineer's seal. Steel connections, welding, bolting, etc.
B). |
Zoning | 10/18/2020 | Approved | ZADM200196 submitted 10/7/2020 under review. |
Zoning | 11/04/2019 | Approved | Please be advised that additional comments may be forthcoming upon submission of revised plans. A comment response letter is required. |
Zoning | 11/04/2019 | Approved | 1. Please provide a location map indicating this space on the site plan. |
Zoning | 11/04/2019 | Approved | 3. Please provide a plan showing that the space will have access to trash collection areas and loading docks. |
Zoning | 11/04/2019 | Approved | 4. Are there any exterior changes to be made? Are you changing out the vestibule doors? Please note facade changes would require an administrative change. |
Zoning | 11/04/2019 | Approved | 5. Please provide an existing floor plan and a demolition plan. |
Zoning | 12/10/2019 | Approved | No signs are approved with this permit. A separate Certificate of Occupancy will be required for this space. |