Review | Review Date | Status | Comments |
Building | 01/21/2022 | Approved | A700 - Architectural Schedules 21 January 2022
SEPARATE PLAN AND PERMIT REQUIRED FOR DOORS WITH SPECIAL LOCKING HARDWARE
|
Building | 01/21/2022 | Approved | A700 - Architectural Schedules 21 January 2022
SEPARATE PLAN AND PERMIT REQUIRED FOR DOORS WITH SPECIAL LOCKING HARDWARE
|
Building | 06/13/2022 | Approved | CTBO-34518-A 13 June 2022
The removal of the toilet rooms for tenant reconstruction is acceptable so long as the affected toilet rooms serve only the proposed tenant upgrade, and do not serve as part of the existing Accessible Route which serves other existing occupied tenant spaces.
2018 VCC §1104; 2018 VEBC §404.3
|
Building | 08/02/2021 | Approved | Sheet A001 - Architectural Code Summary & Egress Plans: A001 -Architectural Code Summary 30 July 2021
Prior permit activity in this building specify the construction type as being 1B or 2B construction.
Please verify the actual construction characteristics. |
Building | 08/02/2021 | Approved | Sheet A001 - Architectural Code Summary & Egress Plans: A001 -Architectural Code Summary 30 July 2021
The existing open stair serves as an 'exit access' stairway.
VCC §1019.3 |
Building | 08/02/2021 | Approved | Sheet A400 - Architectural Stair 1 Plans: PROVIDE TESTING LABORATORY DESIGN NUMBER FOR THE DESIRED FIRE RESISTANCE RATING.
TYPICAL |
Building | 08/02/2021 | Approved | Sheet A400 - Architectural Stair 1 Plans: STRUCTURAL COLUMNS SHALL BE INDIVIDUALLY ENCASED WITHIN FIRE RATED ENVELOPES. |
Building | 08/02/2021 | Approved | Sheet A001 - Architectural Code Summary & Egress Plans: A001 -Architectural Code Summary 30 July 2021
Prior permit activity in this building specify the construction type as being 1B or 2B construction.
Please verify the actual construction characteristics. |
Building | 08/02/2021 | Approved | Sheet A001 - Architectural Code Summary & Egress Plans: A001 -Architectural Code Summary 30 July 2021
The existing open stair serves as an 'exit access' stairway.
VCC §1019.3 |
Building | 08/02/2021 | Approved | Sheet A400 - Architectural Stair 1 Plans: PROVIDE TESTING LABORATORY DESIGN NUMBER FOR THE DESIRED FIRE RESISTANCE RATING.
TYPICAL |
Building | 08/02/2021 | Approved | Sheet A400 - Architectural Stair 1 Plans: STRUCTURAL COLUMNS SHALL BE INDIVIDUALLY ENCASED WITHIN FIRE RATED ENVELOPES. |
Building | 08/02/2021 | Additional | Sheet A001 - Architectural Code Summary & Egress Plans: A001 -Architectural Code Summary 30 July 2021
Prior permit activity in this building specify the construction type as being 1B or 2B construction.
Please verify the actual construction characteristics. |
Building | 08/02/2021 | Additional | Sheet A001 - Architectural Code Summary & Egress Plans: A001 -Architectural Code Summary 30 July 2021
The existing open stair serves as an 'exit access' stairway.
VCC §1019.3 |
Building | 08/02/2021 | Additional | Sheet A400 - Architectural Stair 1 Plans: PROVIDE TESTING LABORATORY DESIGN NUMBER FOR THE DESIRED FIRE RESISTANCE RATING.
TYPICAL |
Building | 08/02/2021 | Additional | Sheet A400 - Architectural Stair 1 Plans: STRUCTURAL COLUMNS SHALL BE INDIVIDUALLY ENCASED WITHIN FIRE RATED ENVELOPES. |
Building | 08/02/2021 | Approved | Sheet A001 - Architectural Code Summary & Egress Plans: A001 -Architectural Code Summary 30 July 2021
Prior permit activity in this building specify the construction type as being 1B or 2B construction.
Please verify the actual construction characteristics. |
Building | 08/02/2021 | Approved | Sheet A001 - Architectural Code Summary & Egress Plans: A001 -Architectural Code Summary 30 July 2021
The existing open stair serves as an 'exit access' stairway.
VCC §1019.3 |
Building | 08/02/2021 | Approved | Sheet A400 - Architectural Stair 1 Plans: PROVIDE TESTING LABORATORY DESIGN NUMBER FOR THE DESIRED FIRE RESISTANCE RATING.
TYPICAL |
Building | 08/02/2021 | Approved | Sheet A400 - Architectural Stair 1 Plans: STRUCTURAL COLUMNS SHALL BE INDIVIDUALLY ENCASED WITHIN FIRE RATED ENVELOPES. |
Building | 08/02/2021 | Approved | Sheet A001 - Architectural Code Summary & Egress Plans: A001 -Architectural Code Summary 30 July 2021
Prior permit activity in this building specify the construction type as being 1B or 2B construction.
Please verify the actual construction characteristics. |
Building | 08/02/2021 | Approved | Sheet A001 - Architectural Code Summary & Egress Plans: A001 -Architectural Code Summary 30 July 2021
The existing open stair serves as an 'exit access' stairway.
VCC §1019.3 |
Building | 08/02/2021 | Approved | Sheet A400 - Architectural Stair 1 Plans: PROVIDE TESTING LABORATORY DESIGN NUMBER FOR THE DESIRED FIRE RESISTANCE RATING.
TYPICAL |
Building | 08/02/2021 | Approved | Sheet A400 - Architectural Stair 1 Plans: STRUCTURAL COLUMNS SHALL BE INDIVIDUALLY ENCASED WITHIN FIRE RATED ENVELOPES. |
Building | 08/02/2021 | Approved | Sheet A001 - Architectural Code Summary & Egress Plans: A001 -Architectural Code Summary 30 July 2021
Prior permit activity in this building specify the construction type as being 1B or 2B construction.
Please verify the actual construction characteristics. |
Building | 08/02/2021 | Approved | Sheet A001 - Architectural Code Summary & Egress Plans: A001 -Architectural Code Summary 30 July 2021
The existing open stair serves as an 'exit access' stairway.
VCC §1019.3 |
Building | 08/02/2021 | Approved | Sheet A400 - Architectural Stair 1 Plans: PROVIDE TESTING LABORATORY DESIGN NUMBER FOR THE DESIRED FIRE RESISTANCE RATING.
TYPICAL |
Building | 08/02/2021 | Approved | Sheet A400 - Architectural Stair 1 Plans: STRUCTURAL COLUMNS SHALL BE INDIVIDUALLY ENCASED WITHIN FIRE RATED ENVELOPES. |
Building | 08/02/2021 | Rejected | Sheet A001 - Architectural Code Summary & Egress Plans: A001 -Architectural Code Summary 30 July 2021
Prior permit activity in this building specify the construction type as being 1B or 2B construction.
Please verify the actual construction characteristics. |
Building | 08/02/2021 | Rejected | Sheet A001 - Architectural Code Summary & Egress Plans: A001 -Architectural Code Summary 30 July 2021
The existing open stair serves as an 'exit access' stairway.
VCC §1019.3 |
Building | 08/02/2021 | Rejected | Sheet A400 - Architectural Stair 1 Plans: PROVIDE TESTING LABORATORY DESIGN NUMBER FOR THE DESIRED FIRE RESISTANCE RATING.
TYPICAL |
Building | 08/02/2021 | Rejected | Sheet A400 - Architectural Stair 1 Plans: STRUCTURAL COLUMNS SHALL BE INDIVIDUALLY ENCASED WITHIN FIRE RATED ENVELOPES. |
Building | 08/02/2021 | Rejected | Sheet A001 - Architectural Code Summary & Egress Plans: A001 -Architectural Code Summary 30 July 2021
Prior permit activity in this building specify the construction type as being 1B or 2B construction.
Please verify the actual construction characteristics. |
Building | 08/02/2021 | Rejected | Sheet A001 - Architectural Code Summary & Egress Plans: A001 -Architectural Code Summary 30 July 2021
The existing open stair serves as an 'exit access' stairway.
VCC §1019.3 |
Building | 08/02/2021 | Rejected | Sheet A400 - Architectural Stair 1 Plans: PROVIDE TESTING LABORATORY DESIGN NUMBER FOR THE DESIRED FIRE RESISTANCE RATING.
TYPICAL |
Building | 08/02/2021 | Rejected | Sheet A400 - Architectural Stair 1 Plans: STRUCTURAL COLUMNS SHALL BE INDIVIDUALLY ENCASED WITHIN FIRE RATED ENVELOPES. |
Building | 09/07/2021 | Additional | Sheet A000 - Architectural Cover Sheet: SUBMIT AUTOMATIC SUPPRESSION SHOP DRAWINGS FOR APPROVAL
SUBMIT FIRE ALARM SYSTEM SHOP DRAWINGS FOR APPROVAL
|
Building | 09/07/2021 | Approved | Sheet A000 - Architectural Cover Sheet: SUBMIT AUTOMATIC SUPPRESSION SHOP DRAWINGS FOR APPROVAL
SUBMIT FIRE ALARM SYSTEM SHOP DRAWINGS FOR APPROVAL
|
Building | 09/07/2021 | Approved | Sheet A000 - Architectural Cover Sheet: SUBMIT AUTOMATIC SUPPRESSION SHOP DRAWINGS FOR APPROVAL
SUBMIT FIRE ALARM SYSTEM SHOP DRAWINGS FOR APPROVAL
|
Building | 12/18/2021 | Rejected | Sheet A000 - Architectural Cover Sheet: CTBO-34518-A 3 December 2021
SUBMIT AUTOMATIC SUPPRESSION SHOP DRAWINGS FOR APPROVAL
SUBMIT FIRE ALARM SYSTEM SHOP DRAWINGS FOR APPROVAL |
Building | 12/18/2021 | Rejected | A000 - Architectural Cover Sheet 18 December 2021
The revision date for this drawing precedes the date of the original permit submittal.
Revise. |
Building | 12/18/2021 | Rejected | Sheet A001 - Architectural Code Summary & Egress Plans: A001 -Architectural Code Summary 30 July 2021
It is preferable to call out the changes made to this drawing, rather than applying a stamp saying the entire sheet has been revised. Clarify.
TYPICAL |
Building | 12/18/2021 | Rejected | Sheet A001 - Architectural Code Summary & Egress Plans: A001 -Architectural Code Summary 30 July 2021
Portions of the drawing are now smeary and less legible. Please restore crisp text.
TYPICAL |
Building | 12/18/2021 | Approved | Sheet A000 - Architectural Cover Sheet: CTBO-34518-A 3 December 2021
SUBMIT AUTOMATIC SUPPRESSION SHOP DRAWINGS FOR APPROVAL
SUBMIT FIRE ALARM SYSTEM SHOP DRAWINGS FOR APPROVAL |
Building | 12/18/2021 | Approved | A000 - Architectural Cover Sheet 18 December 2021
The revision date for this drawing precedes the date of the original permit submittal.
Revise. |
Building | 12/18/2021 | Approved | Sheet A001 - Architectural Code Summary & Egress Plans: A001 -Architectural Code Summary 30 July 2021
It is preferable to call out the changes made to this drawing, rather than applying a stamp saying the entire sheet has been revised. Clarify.
TYPICAL |
Building | 12/18/2021 | Approved | Sheet A001 - Architectural Code Summary & Egress Plans: A001 -Architectural Code Summary 30 July 2021
Portions of the drawing are now smeary and less legible. Please restore crisp text.
TYPICAL |
Building | 12/18/2021 | Approved | Sheet A000 - Architectural Cover Sheet: CTBO-34518-A 3 December 2021
SUBMIT AUTOMATIC SUPPRESSION SHOP DRAWINGS FOR APPROVAL
SUBMIT FIRE ALARM SYSTEM SHOP DRAWINGS FOR APPROVAL |
Building | 12/18/2021 | Approved | A000 - Architectural Cover Sheet 18 December 2021
The revision date for this drawing precedes the date of the original permit submittal.
Revise. |
Building | 12/18/2021 | Approved | Sheet A001 - Architectural Code Summary & Egress Plans: A001 -Architectural Code Summary 30 July 2021
It is preferable to call out the changes made to this drawing, rather than applying a stamp saying the entire sheet has been revised. Clarify.
TYPICAL |
Building | 12/18/2021 | Approved | Sheet A001 - Architectural Code Summary & Egress Plans: A001 -Architectural Code Summary 30 July 2021
Portions of the drawing are now smeary and less legible. Please restore crisp text.
TYPICAL |
Building | 12/18/2021 | Approved | Sheet A000 - Architectural Cover Sheet: CTBO-34518-A 3 December 2021
SUBMIT AUTOMATIC SUPPRESSION SHOP DRAWINGS FOR APPROVAL
SUBMIT FIRE ALARM SYSTEM SHOP DRAWINGS FOR APPROVAL |
Building | 12/18/2021 | Approved | A000 - Architectural Cover Sheet 18 December 2021
The revision date for this drawing precedes the date of the original permit submittal.
Revise. |
Building | 12/18/2021 | Approved | Sheet A001 - Architectural Code Summary & Egress Plans: A001 -Architectural Code Summary 30 July 2021
It is preferable to call out the changes made to this drawing, rather than applying a stamp saying the entire sheet has been revised. Clarify.
TYPICAL |
Building | 12/18/2021 | Approved | Sheet A001 - Architectural Code Summary & Egress Plans: A001 -Architectural Code Summary 30 July 2021
Portions of the drawing are now smeary and less legible. Please restore crisp text.
TYPICAL |
DES:Water/Sewer Engineering | 08/01/2021 | Approved | NO NEW DFU'S |
Electrical | 07/29/2021 | Approved | Please provide the ampere rating for 'existing' panel board '2L'. Refer to sheets E2.01 and E2.02. Section 109.3 of the Virginia Construction Code. |
Electrical | 07/29/2021 | Approved | Please clarify why the 'MDP' directory indicates 600 ampere MCB, while being fed by 500kcmil feeders (rated for 380 amperes), and protected by 400 ampere fuses in the service disconnect switch? Refer to sheet E2.02. |
Electrical | 07/29/2021 | Approved | Please clarify on the drawings the total number of electrical services are located in this building. The electrical service equipment shown on the 'basement level' (sheet E2.02), show (2) services that are identified as existing. One rated at 200 ampere and the other rated at 400 ampere, that do not appear to be on the load side of the 800 ampere CT cabinet. How are these (2) service disconnect switches being fed from the Dominion Virginia Power? Also, refer to sheet E1.05. |
Electrical | 07/29/2021 | Approved | Based on the lack of information provided, additional comments may be forthcoming. |
Electrical | 07/29/2021 | Approved | Please provide the ampere rating for 'existing' panel board '2L'. Refer to sheets E2.01 and E2.02. Section 109.3 of the Virginia Construction Code. |
Electrical | 07/29/2021 | Approved | Please clarify why the 'MDP' directory indicates 600 ampere MCB, while being fed by 500kcmil feeders (rated for 380 amperes), and protected by 400 ampere fuses in the service disconnect switch? Refer to sheet E2.02. |
Electrical | 07/29/2021 | Approved | Please clarify on the drawings the total number of electrical services are located in this building. The electrical service equipment shown on the 'basement level' (sheet E2.02), show (2) services that are identified as existing. One rated at 200 ampere and the other rated at 400 ampere, that do not appear to be on the load side of the 800 ampere CT cabinet. How are these (2) service disconnect switches being fed from the Dominion Virginia Power? Also, refer to sheet E1.05. |
Electrical | 07/29/2021 | Approved | Based on the lack of information provided, additional comments may be forthcoming. |
Electrical | 07/29/2021 | Approved | Please provide the ampere rating for 'existing' panel board '2L'. Refer to sheets E2.01 and E2.02. Section 109.3 of the Virginia Construction Code. |
Electrical | 07/29/2021 | Approved | Please clarify why the 'MDP' directory indicates 600 ampere MCB, while being fed by 500kcmil feeders (rated for 380 amperes), and protected by 400 ampere fuses in the service disconnect switch? Refer to sheet E2.02. |
Electrical | 07/29/2021 | Approved | Please clarify on the drawings the total number of electrical services are located in this building. The electrical service equipment shown on the 'basement level' (sheet E2.02), show (2) services that are identified as existing. One rated at 200 ampere and the other rated at 400 ampere, that do not appear to be on the load side of the 800 ampere CT cabinet. How are these (2) service disconnect switches being fed from the Dominion Virginia Power? Also, refer to sheet E1.05. |
Electrical | 07/29/2021 | Approved | Based on the lack of information provided, additional comments may be forthcoming. |
Electrical | 07/29/2021 | Approved | Please provide the ampere rating for 'existing' panel board '2L'. Refer to sheets E2.01 and E2.02. Section 109.3 of the Virginia Construction Code. |
Electrical | 07/29/2021 | Approved | Please clarify why the 'MDP' directory indicates 600 ampere MCB, while being fed by 500kcmil feeders (rated for 380 amperes), and protected by 400 ampere fuses in the service disconnect switch? Refer to sheet E2.02. |
Electrical | 07/29/2021 | Approved | Please clarify on the drawings the total number of electrical services are located in this building. The electrical service equipment shown on the 'basement level' (sheet E2.02), show (2) services that are identified as existing. One rated at 200 ampere and the other rated at 400 ampere, that do not appear to be on the load side of the 800 ampere CT cabinet. How are these (2) service disconnect switches being fed from the Dominion Virginia Power? Also, refer to sheet E1.05. |
Electrical | 07/29/2021 | Approved | Based on the lack of information provided, additional comments may be forthcoming. |
Electrical | 07/29/2021 | Approved | Please provide the ampere rating for 'existing' panel board '2L'. Refer to sheets E2.01 and E2.02. Section 109.3 of the Virginia Construction Code. |
Electrical | 07/29/2021 | Approved | Please clarify why the 'MDP' directory indicates 600 ampere MCB, while being fed by 500kcmil feeders (rated for 380 amperes), and protected by 400 ampere fuses in the service disconnect switch? Refer to sheet E2.02. |
Electrical | 07/29/2021 | Approved | Please clarify on the drawings the total number of electrical services are located in this building. The electrical service equipment shown on the 'basement level' (sheet E2.02), show (2) services that are identified as existing. One rated at 200 ampere and the other rated at 400 ampere, that do not appear to be on the load side of the 800 ampere CT cabinet. How are these (2) service disconnect switches being fed from the Dominion Virginia Power? Also, refer to sheet E1.05. |
Electrical | 07/29/2021 | Approved | Based on the lack of information provided, additional comments may be forthcoming. |
Electrical | 07/29/2021 | Rejected | Please provide the ampere rating for 'existing' panel board '2L'. Refer to sheets E2.01 and E2.02. Section 109.3 of the Virginia Construction Code. |
Electrical | 07/29/2021 | Rejected | Please clarify why the 'MDP' directory indicates 600 ampere MCB, while being fed by 500kcmil feeders (rated for 380 amperes), and protected by 400 ampere fuses in the service disconnect switch? Refer to sheet E2.02. |
Electrical | 07/29/2021 | Rejected | Please clarify on the drawings the total number of electrical services are located in this building. The electrical service equipment shown on the 'basement level' (sheet E2.02), show (2) services that are identified as existing. One rated at 200 ampere and the other rated at 400 ampere, that do not appear to be on the load side of the 800 ampere CT cabinet. How are these (2) service disconnect switches being fed from the Dominion Virginia Power? Also, refer to sheet E1.05. |
Electrical | 07/29/2021 | Rejected | Based on the lack of information provided, additional comments may be forthcoming. |
Electrical | 07/29/2021 | Additional | Please provide the ampere rating for 'existing' panel board '2L'. Refer to sheets E2.01 and E2.02. Section 109.3 of the Virginia Construction Code. |
Electrical | 07/29/2021 | Additional | Please clarify why the 'MDP' directory indicates 600 ampere MCB, while being fed by 500kcmil feeders (rated for 380 amperes), and protected by 400 ampere fuses in the service disconnect switch? Refer to sheet E2.02. |
Electrical | 07/29/2021 | Additional | Please clarify on the drawings the total number of electrical services are located in this building. The electrical service equipment shown on the 'basement level' (sheet E2.02), show (2) services that are identified as existing. One rated at 200 ampere and the other rated at 400 ampere, that do not appear to be on the load side of the 800 ampere CT cabinet. How are these (2) service disconnect switches being fed from the Dominion Virginia Power? Also, refer to sheet E1.05. |
Electrical | 07/29/2021 | Additional | Based on the lack of information provided, additional comments may be forthcoming. |
EPlan Review | 12/01/2021 | Approved | |
Mechanical | 07/21/2021 | Approved | Sheet M1.02 Mechanical First Floor: Combination fire/smoke damper is required where duct penetrate a rated shaft. |
Mechanical | 07/21/2021 | Rejected | Sheet M1.02 Mechanical First Floor: Combination fire/smoke damper is required where duct penetrate a rated shaft. |
Mechanical | 07/21/2021 | Rejected | Sheet M1.02 Mechanical First Floor: Combination fire/smoke damper is required where duct penetrate a rated shaft. |
Mechanical | 07/21/2021 | Approved | Sheet M1.02 Mechanical First Floor: Combination fire/smoke damper is required where duct penetrate a rated shaft. |
Mechanical | 07/21/2021 | Approved | Sheet M1.02 Mechanical First Floor: Combination fire/smoke damper is required where duct penetrate a rated shaft. |
Mechanical | 08/23/2021 | Approved | Sheet M1.01 Mechanical Basement: 1-Please provide return grills for mechanical/storage room and office.
2- Smoke damper is not required where building is equipped throughout with an automatic sprinkler system
(IBC section 903.3.1.1). |
Mechanical | 08/23/2021 | Approved | Sheet M1.01 Mechanical Basement: 1-Please provide return grills for mechanical/storage room and office.
2- Smoke damper is not required where building is equipped throughout with an automatic sprinkler system
(IBC section 903.3.1.1). |
Mechanical | 08/23/2021 | Rejected | Sheet M1.01 Mechanical Basement: 1-Please provide return grills for mechanical/storage room and office.
2- Smoke damper is not required where building is equipped throughout with an automatic sprinkler system
(IBC section 903.3.1.1). |
Mechanical | 08/23/2021 | Approved | Sheet M1.01 Mechanical Basement: 1-Please provide return grills for mechanical/storage room and office.
2- Smoke damper is not required where building is equipped throughout with an automatic sprinkler system
(IBC section 903.3.1.1). |
Plumbing | 07/26/2021 | Approved | 7-26-21 Please provide Gas riser Diagram to include lengths, size , total BTU. 2015 VFGC 402 |
Plumbing | 07/26/2021 | Approved | 7-26-21 Please provide Gas riser Diagram to include lengths, size , total BTU. 2015 VFGC 402 |
Plumbing | 07/26/2021 | Rejected | 7-26-21 Please provide Gas riser Diagram to include lengths, size , total BTU. 2015 VFGC 402 |
Plumbing | 07/26/2021 | Approved | 7-26-21 Please provide Gas riser Diagram to include lengths, size , total BTU. 2015 VFGC 402 |
Plumbing | 07/26/2021 | Approved | 7-26-21 Please provide Gas riser Diagram to include lengths, size , total BTU. 2015 VFGC 402 |
Plumbing | 07/26/2021 | Approved | 7-26-21 Please provide Gas riser Diagram to include lengths, size , total BTU. 2015 VFGC 402 |
Structural | 07/28/2021 | Rejected | Special Inspections: REJECTED.
The statement of special inspection is used by the structural engineer of record (SER) to identify the structural items that require special inspection. This is a legal statement that shall be filled out by the Structural Engineer of Record (SER). All applicable item lines of inspection shall be initialed by both the structural engineer of record (SER) and the special inspection engineer of record (SIER). This statement must contain signatures from the following parties.
• Owner
• Structural Engineer of Record (SER)
• Geotechnical Engineer of Record (GER)
• Precast Concrete Engineer of Record (PER) (if applicable)
• Special Inspection Engineer of Record (SIER)
• Testing Agency Engineer of Record (if |
Structural | 07/28/2021 | Approved | Special Inspections: REJECTED.
The statement of special inspection is used by the structural engineer of record (SER) to identify the structural items that require special inspection. This is a legal statement that shall be filled out by the Structural Engineer of Record (SER). All applicable item lines of inspection shall be initialed by both the structural engineer of record (SER) and the special inspection engineer of record (SIER). This statement must contain signatures from the following parties.
• Owner
• Structural Engineer of Record (SER)
• Geotechnical Engineer of Record (GER)
• Precast Concrete Engineer of Record (PER) (if applicable)
• Special Inspection Engineer of Record (SIER)
• Testing Agency Engineer of Record (if |
Structural | 07/28/2021 | Approved | Special Inspections: REJECTED.
The statement of special inspection is used by the structural engineer of record (SER) to identify the structural items that require special inspection. This is a legal statement that shall be filled out by the Structural Engineer of Record (SER). All applicable item lines of inspection shall be initialed by both the structural engineer of record (SER) and the special inspection engineer of record (SIER). This statement must contain signatures from the following parties.
• Owner
• Structural Engineer of Record (SER)
• Geotechnical Engineer of Record (GER)
• Precast Concrete Engineer of Record (PER) (if applicable)
• Special Inspection Engineer of Record (SIER)
• Testing Agency Engineer of Record (if |
Structural | 07/28/2021 | Rejected | Special Inspections: REJECTED.
The statement of special inspection is used by the structural engineer of record (SER) to identify the structural items that require special inspection. This is a legal statement that shall be filled out by the Structural Engineer of Record (SER). All applicable item lines of inspection shall be initialed by both the structural engineer of record (SER) and the special inspection engineer of record (SIER). This statement must contain signatures from the following parties.
• Owner
• Structural Engineer of Record (SER)
• Geotechnical Engineer of Record (GER)
• Precast Concrete Engineer of Record (PER) (if applicable)
• Special Inspection Engineer of Record (SIER)
• Testing Agency Engineer of Record (if |
Structural | 07/28/2021 | Rejected | Special Inspections: REJECTED.
The statement of special inspection is used by the structural engineer of record (SER) to identify the structural items that require special inspection. This is a legal statement that shall be filled out by the Structural Engineer of Record (SER). All applicable item lines of inspection shall be initialed by both the structural engineer of record (SER) and the special inspection engineer of record (SIER). This statement must contain signatures from the following parties.
• Owner
• Structural Engineer of Record (SER)
• Geotechnical Engineer of Record (GER)
• Precast Concrete Engineer of Record (PER) (if applicable)
• Special Inspection Engineer of Record (SIER)
• Testing Agency Engineer of Record (if |
Structural | 09/07/2021 | Rejected | Special Inspections: REJECTED
missing SIER and GC information and signatures. |
Structural | 09/07/2021 | Rejected | Special Inspections: REJECTED
missing SIER and GC information and signatures. |
Structural | 09/07/2021 | Approved | Special Inspections: REJECTED
missing SIER and GC information and signatures. |
Structural | 09/07/2021 | Approved | Special Inspections: REJECTED
missing SIER and GC information and signatures. |
Structural | 10/26/2021 | Approved | Please fill in the SIER information.
Approval pending on GC info. |
Structural | 10/26/2021 | Rejected | Please fill in the SIER information.
Approval pending on GC info. |
Structural | 10/26/2021 | Approved | Please fill in the SIER information.
Approval pending on GC info. |
Zoning | 01/06/2022 | Approved | Rejected: Submitted plan does not match the original and admin change plans . Please revise to match or submit an admin change amendment.
Reviewer:
Mudoh Mbah SAM
Tel: 703-228-3727
Email: mmbah@arlingtonva.us
|
Zoning | 01/06/2022 | Approved | Interior alteration in blding in sp397. Proposed work includes demo of existing stair and building of two new stair cases. No admin change approval is identified. No use is proposed yet. Admin change for proposed work zadm210110 is approved
APPROVAL NOTE:
1. Work must be done as shown on the plan and plat submitted for zoning review. Any alteration to the above will need zoning review and approval.
2. A copy of wall check is required upon completion of the foundation.
Reviewer:
Mudoh Mbah SAM
Tel: 703-228-3727
Email: mmbah@arlingtonva.us |
Zoning | 01/06/2022 | Rejected | Rejected: Submitted plan does not match the original and admin change plans . Please revise to match or submit an admin change amendment.
Reviewer:
Mudoh Mbah SAM
Tel: 703-228-3727
Email: mmbah@arlingtonva.us
|
Zoning | 01/06/2022 | Rejected | Interior alteration in blding in sp397. Proposed work includes demo of existing stair and building of two new stair cases. No admin change approval is identified. No use is proposed yet. Admin change for proposed work zadm210110 is approved
APPROVAL NOTE:
1. Work must be done as shown on the plan and plat submitted for zoning review. Any alteration to the above will need zoning review and approval.
2. A copy of wall check is required upon completion of the foundation.
Reviewer:
Mudoh Mbah SAM
Tel: 703-228-3727
Email: mmbah@arlingtonva.us |
Zoning | 01/06/2022 | Approved | Interior alteration in blding in sp397. Proposed work includes demo of existing stair and building of two new stair cases. No admin change approval is identified. No use is proposed yet. Admin change for proposed work zadm210110 is approved
APPROVAL NOTE:
1. Work must be done as shown on the plan and plat submitted for zoning review. Any alteration to the above will need zoning review and approval.
2. A copy of wall check is required upon completion of the foundation.
Reviewer:
Mudoh Mbah SAM
Tel: 703-228-3727
Email: mmbah@arlingtonva.us |
Zoning | 01/06/2022 | Approved | Rejected: Submitted plan does not match the original and admin change plans . Please revise to match or submit an admin change amendment.
Reviewer:
Mudoh Mbah SAM
Tel: 703-228-3727
Email: mmbah@arlingtonva.us
|
Zoning | 01/20/2022 | Approved | Admin change ACHG22-00009 is approved for the proposed revision.
No zoning issues. |
Zoning | 01/20/2022 | Approved | Admin change ACHG22-00009 is approved for the proposed revision.
No zoning issues. |
Zoning | 06/07/2022 | Approved | No zoning issues |
Zoning | 08/02/2021 | Rejected | Interior alteration in blding in sp397. Proposed work includes demo of existing stair and building of two new stair cases. No admin change approval.
Rejected:
1. Proposed change is susbstantial. An admin change approval is required. Use the link below to download the Administrative change application or contact the zoning department at 703-228-3883 for assistance. https://arlingtonva.s3.dualstack.us-east-1.amazonaws.com/wp-content/uploads/sites/38/2016/07/Administrative-Change-Application.pdf
2. Further review shall be done after change is approve. Please attach a zoning comment response letter when submitting revisions.
Reviewer:
Mudoh Mbah SAM
Tel: 703-228-3727
Email: mmbah@arlingtonva.us
|
Zoning | 08/06/2021 | Rejected | Interior alteration in blding in sp397. Proposed work includes demo of existing stair and building of two new stair cases. No admin change approval.
Rejected:
1. Proposed change is substantial. An admin change approval is required. Use the link below to download the Administrative change application or contact the zoning department at 703-228-3883 for assistance. https://arlingtonva.s3.dualstack.us-east-1.amazonaws.com/wp-content/uploads/sites/38/2016/07/Administrative-Change-Application.pdf
2. Further review shall be done after change is approve. Please attach a zoning comment response letter when submitting revisions.
Reviewer:
Mudoh Mbah SAM
Tel: 703-228-3727
Email: mmbah@arlingtonva.us |
Zoning | 08/12/2021 | Rejected | Interior alteration in blding in sp397. Proposed work includes demo of existing stair and building of two new stair cases. No admin change approval.
Rejected:
1. Proposed change is substantial. An admin change approval is required. Use the link below to download the Administrative change application or contact the zoning department at 703-228-3883 for assistance. https://arlingtonva.s3.dualstack.us-east-1.amazonaws.com/wp-content/uploads/sites/38/2016/07/Administrative-Change-Application.pdf
2. Further review shall be done after change is approve. Please attach a zoning comment response letter when submitting revisions.
Reviewer:
Mudoh Mbah SAM
Tel: 703-228-3727
Email: mmbah@arlingtonva.us |
Zoning | 08/13/2021 | Rejected | Interior alteration in blding in sp397. Proposed work includes demo of existing stair and building of two new stair cases. No admin change approval is identified. No use is proposed yet.
Rejected:
1. Proposed change is substantial. An admin change approval is required. Use the link below to download the Administrative change application or contact the zoning department at 703-228-3883 for assistance. https://arlingtonva.s3.dualstack.us-east-1.amazonaws.com/wp-content/uploads/sites/38/2016/07/Administrative-Change-Application.pdf
2. Further review shall be done after change is approve. Please attach a zoning comment response letter when submitting revisions.
Reviewer:
Mudoh Mbah SAM
Tel: 703-228-3727
Email: mmbah@arlingtonva.us |
Zoning | 09/07/2021 | Rejected | Interior alteration in blding in sp397. Proposed work includes demo of existing stair and building of two new stair cases. No admin change approval is identified. No use is proposed yet.
Rejected:
1. Proposed change is substantial. An admin change approval is required. Use the link below to download the Administrative change application or contact the zoning department at 703-228-3883 for assistance. https://arlingtonva.s3.dualstack.us-east-1.amazonaws.com/wp-content/uploads/sites/38/2016/07/Administrative-Change-Application.pdf
2. Further review shall be done after change is approve. Please attach a zoning comment response letter when submitting revisions.
Reviewer:
Mudoh Mbah SAM
Tel: 703-228-3727
Email: mmbah@arlingtonva.us |
Zoning | 09/07/2021 | Rejected | Admin change required. Please submit and get admin approval for the proposed work. This permit is rejected because it has been rejected by atleast one other reviewer. |
Zoning | 09/07/2021 | Approved | Interior alteration in blding in sp397. Proposed work includes demo of existing stair and building of two new stair cases. No admin change approval is identified. No use is proposed yet.
Rejected:
1. Proposed change is substantial. An admin change approval is required. Use the link below to download the Administrative change application or contact the zoning department at 703-228-3883 for assistance. https://arlingtonva.s3.dualstack.us-east-1.amazonaws.com/wp-content/uploads/sites/38/2016/07/Administrative-Change-Application.pdf
2. Further review shall be done after change is approve. Please attach a zoning comment response letter when submitting revisions.
Reviewer:
Mudoh Mbah SAM
Tel: 703-228-3727
Email: mmbah@arlingtonva.us |
Zoning | 09/07/2021 | Approved | Admin change required. Please submit and get admin approval for the proposed work. This permit is rejected because it has been rejected by atleast one other reviewer. |
Zoning | 09/07/2021 | Rejected | Interior alteration in blding in sp397. Proposed work includes demo of existing stair and building of two new stair cases. No admin change approval is identified. No use is proposed yet.
Rejected:
1. Proposed change is substantial. An admin change approval is required. Use the link below to download the Administrative change application or contact the zoning department at 703-228-3883 for assistance. https://arlingtonva.s3.dualstack.us-east-1.amazonaws.com/wp-content/uploads/sites/38/2016/07/Administrative-Change-Application.pdf
2. Further review shall be done after change is approve. Please attach a zoning comment response letter when submitting revisions.
Reviewer:
Mudoh Mbah SAM
Tel: 703-228-3727
Email: mmbah@arlingtonva.us |
Zoning | 09/07/2021 | Rejected | Admin change required. Please submit and get admin approval for the proposed work. This permit is rejected because it has been rejected by atleast one other reviewer. |
Zoning | 09/07/2021 | Approved | Interior alteration in blding in sp397. Proposed work includes demo of existing stair and building of two new stair cases. No admin change approval is identified. No use is proposed yet.
Rejected:
1. Proposed change is substantial. An admin change approval is required. Use the link below to download the Administrative change application or contact the zoning department at 703-228-3883 for assistance. https://arlingtonva.s3.dualstack.us-east-1.amazonaws.com/wp-content/uploads/sites/38/2016/07/Administrative-Change-Application.pdf
2. Further review shall be done after change is approve. Please attach a zoning comment response letter when submitting revisions.
Reviewer:
Mudoh Mbah SAM
Tel: 703-228-3727
Email: mmbah@arlingtonva.us |
Zoning | 09/07/2021 | Approved | Admin change required. Please submit and get admin approval for the proposed work. This permit is rejected because it has been rejected by atleast one other reviewer. |
Zoning | 09/07/2021 | Additional | Admin change required. Please submit and get admin approval for the proposed work. This permit is rejected because it has been rejected by atleast one other reviewer. |
Zoning | 09/07/2021 | Additional | Interior alteration in blding in sp397. Proposed work includes demo of existing stair and building of two new stair cases. No admin change approval is identified. No use is proposed yet.
Rejected:
1. Proposed change is substantial. An admin change approval is required. Use the link below to download the Administrative change application or contact the zoning department at 703-228-3883 for assistance. https://arlingtonva.s3.dualstack.us-east-1.amazonaws.com/wp-content/uploads/sites/38/2016/07/Administrative-Change-Application.pdf
2. Further review shall be done after change is approve. Please attach a zoning comment response letter when submitting revisions.
Reviewer:
Mudoh Mbah SAM
Tel: 703-228-3727
Email: mmbah@arlingtonva.us |
Zoning | 09/07/2021 | Rejected | Interior alteration in blding in sp397. Proposed work includes demo of existing stair and building of two new stair cases. No admin change approval is identified. No use is proposed yet.
Rejected:
1. Proposed change is substantial. An admin change approval is required. Use the link below to download the Administrative change application or contact the zoning department at 703-228-3883 for assistance. https://arlingtonva.s3.dualstack.us-east-1.amazonaws.com/wp-content/uploads/sites/38/2016/07/Administrative-Change-Application.pdf
2. Further review shall be done after change is approve. Please attach a zoning comment response letter when submitting revisions.
Reviewer:
Mudoh Mbah SAM
Tel: 703-228-3727
Email: mmbah@arlingtonva.us |
Zoning | 09/07/2021 | Rejected | Admin change required. Please submit and get admin approval for the proposed work. This permit is rejected because it has been rejected by atleast one other reviewer. |
Zoning | 09/07/2021 | Approved | Interior alteration in blding in sp397. Proposed work includes demo of existing stair and building of two new stair cases. No admin change approval is identified. No use is proposed yet.
Rejected:
1. Proposed change is substantial. An admin change approval is required. Use the link below to download the Administrative change application or contact the zoning department at 703-228-3883 for assistance. https://arlingtonva.s3.dualstack.us-east-1.amazonaws.com/wp-content/uploads/sites/38/2016/07/Administrative-Change-Application.pdf
2. Further review shall be done after change is approve. Please attach a zoning comment response letter when submitting revisions.
Reviewer:
Mudoh Mbah SAM
Tel: 703-228-3727
Email: mmbah@arlingtonva.us |
Zoning | 09/07/2021 | Approved | Admin change required. Please submit and get admin approval for the proposed work. This permit is rejected because it has been rejected by atleast one other reviewer. |
Zoning | 11/23/2021 | Rejected | Interior alteration in blding in sp397. Proposed work includes demo of existing stair and building of two new stair cases. No admin change approval is identified. No use is proposed yet. Admin change for proposed work zadm210110 is approved
APPROVAL NOTE:
1. Work must be done as shown on the plan and plat submitted for zoning review. Any alteration to the above will need zoning review and approval.
2. A copy of wall check is required upon completion of the foundation.
Reviewer:
Mudoh Mbah SAM
Tel: 703-228-3727
Email: mmbah@arlingtonva.us |
Zoning | 11/23/2021 | Approved | Interior alteration in blding in sp397. Proposed work includes demo of existing stair and building of two new stair cases. No admin change approval is identified. No use is proposed yet. Admin change for proposed work zadm210110 is approved
APPROVAL NOTE:
1. Work must be done as shown on the plan and plat submitted for zoning review. Any alteration to the above will need zoning review and approval.
2. A copy of wall check is required upon completion of the foundation.
Reviewer:
Mudoh Mbah SAM
Tel: 703-228-3727
Email: mmbah@arlingtonva.us |
Zoning | 12/10/2021 | Rejected | Revision to change previously approved design in admin change.
Rejected:
1. Revision to the plan set does not match the plans approved in the admin change. Please submit an admin change application to match the new proposal.
2. Please attach a zoning comment response letter when submitting revisions.
Reviewer:
Mudoh Mbah SAM
Tel: 703-228-3727
Email: mmbah@arlingtonva.us
|
Zoning | 12/10/2021 | Approved | Revision to change previously approved design in admin change.
Rejected:
1. Revision to the plan set does not match the plans approved in the admin change. Please submit an admin change application to match the new proposal.
2. Please attach a zoning comment response letter when submitting revisions.
Reviewer:
Mudoh Mbah SAM
Tel: 703-228-3727
Email: mmbah@arlingtonva.us |
Zoning | 12/10/2021 | Rejected | Revision to change previously approved design in admin change.
Rejected:
1. Revision to the plan set does not match the plans approved in the admin change. Please submit an admin change application to match the new proposal.
2. Please attach a zoning comment response letter when submitting revisions.
Reviewer:
Mudoh Mbah SAM
Tel: 703-228-3727
Email: mmbah@arlingtonva.us
|
Zoning | 12/10/2021 | Approved | Revision to change previously approved design in admin change.
Rejected:
1. Revision to the plan set does not match the plans approved in the admin change. Please submit an admin change application to match the new proposal.
2. Please attach a zoning comment response letter when submitting revisions.
Reviewer:
Mudoh Mbah SAM
Tel: 703-228-3727
Email: mmbah@arlingtonva.us |