Permit Comments
 
Permit #B2101706
Address3028 WILSON BLVD
TypeCTBO
StatusFINALED
Permit HolderTECH 24 CONSTRUCTION
OwnerC P ONE ASSOCIATES LP %VA MGMT INC #1002
Applied Date15/07/2021
Approved Date01/12/2021
Date Issued01/12/2021
DescriptionINTERIOR RENOVATIONS ON THE BASEMENT, 1ST FL AND 2ND FL. PROVIDE NEW EXIT STAIR FROM 2ND FL TO AN EXISTING EXTERIOR EXIT DOOR ON 1ST FL. ENCLOSE EXISTING EXIT FROM THE BASEMENT TO 1ST FL AND ADD CONNECTING STAIR FROM BASEMENT TO 1ST FL. SPECIAL INSPECTIONS REQUIRED

ReviewReview DateStatusComments
Building01/21/2022ApprovedA700 - Architectural Schedules 21 January 2022 SEPARATE PLAN AND PERMIT REQUIRED FOR DOORS WITH SPECIAL LOCKING HARDWARE
Building01/21/2022ApprovedA700 - Architectural Schedules 21 January 2022 SEPARATE PLAN AND PERMIT REQUIRED FOR DOORS WITH SPECIAL LOCKING HARDWARE
Building06/13/2022ApprovedCTBO-34518-A 13 June 2022 The removal of the toilet rooms for tenant reconstruction is acceptable so long as the affected toilet rooms serve only the proposed tenant upgrade, and do not serve as part of the existing Accessible Route which serves other existing occupied tenant spaces. 2018 VCC §1104; 2018 VEBC §404.3
Building08/02/2021ApprovedSheet A001 - Architectural Code Summary & Egress Plans: A001 -Architectural Code Summary 30 July 2021 Prior permit activity in this building specify the construction type as being 1B or 2B construction. Please verify the actual construction characteristics.
Building08/02/2021ApprovedSheet A001 - Architectural Code Summary & Egress Plans: A001 -Architectural Code Summary 30 July 2021 The existing open stair serves as an 'exit access' stairway. VCC §1019.3
Building08/02/2021ApprovedSheet A400 - Architectural Stair 1 Plans: PROVIDE TESTING LABORATORY DESIGN NUMBER FOR THE DESIRED FIRE RESISTANCE RATING. TYPICAL
Building08/02/2021ApprovedSheet A400 - Architectural Stair 1 Plans: STRUCTURAL COLUMNS SHALL BE INDIVIDUALLY ENCASED WITHIN FIRE RATED ENVELOPES.
Building08/02/2021ApprovedSheet A001 - Architectural Code Summary & Egress Plans: A001 -Architectural Code Summary 30 July 2021 Prior permit activity in this building specify the construction type as being 1B or 2B construction. Please verify the actual construction characteristics.
Building08/02/2021ApprovedSheet A001 - Architectural Code Summary & Egress Plans: A001 -Architectural Code Summary 30 July 2021 The existing open stair serves as an 'exit access' stairway. VCC §1019.3
Building08/02/2021ApprovedSheet A400 - Architectural Stair 1 Plans: PROVIDE TESTING LABORATORY DESIGN NUMBER FOR THE DESIRED FIRE RESISTANCE RATING. TYPICAL
Building08/02/2021ApprovedSheet A400 - Architectural Stair 1 Plans: STRUCTURAL COLUMNS SHALL BE INDIVIDUALLY ENCASED WITHIN FIRE RATED ENVELOPES.
Building08/02/2021AdditionalSheet A001 - Architectural Code Summary & Egress Plans: A001 -Architectural Code Summary 30 July 2021 Prior permit activity in this building specify the construction type as being 1B or 2B construction. Please verify the actual construction characteristics.
Building08/02/2021AdditionalSheet A001 - Architectural Code Summary & Egress Plans: A001 -Architectural Code Summary 30 July 2021 The existing open stair serves as an 'exit access' stairway. VCC §1019.3
Building08/02/2021AdditionalSheet A400 - Architectural Stair 1 Plans: PROVIDE TESTING LABORATORY DESIGN NUMBER FOR THE DESIRED FIRE RESISTANCE RATING. TYPICAL
Building08/02/2021AdditionalSheet A400 - Architectural Stair 1 Plans: STRUCTURAL COLUMNS SHALL BE INDIVIDUALLY ENCASED WITHIN FIRE RATED ENVELOPES.
Building08/02/2021ApprovedSheet A001 - Architectural Code Summary & Egress Plans: A001 -Architectural Code Summary 30 July 2021 Prior permit activity in this building specify the construction type as being 1B or 2B construction. Please verify the actual construction characteristics.
Building08/02/2021ApprovedSheet A001 - Architectural Code Summary & Egress Plans: A001 -Architectural Code Summary 30 July 2021 The existing open stair serves as an 'exit access' stairway. VCC §1019.3
Building08/02/2021ApprovedSheet A400 - Architectural Stair 1 Plans: PROVIDE TESTING LABORATORY DESIGN NUMBER FOR THE DESIRED FIRE RESISTANCE RATING. TYPICAL
Building08/02/2021ApprovedSheet A400 - Architectural Stair 1 Plans: STRUCTURAL COLUMNS SHALL BE INDIVIDUALLY ENCASED WITHIN FIRE RATED ENVELOPES.
Building08/02/2021ApprovedSheet A001 - Architectural Code Summary & Egress Plans: A001 -Architectural Code Summary 30 July 2021 Prior permit activity in this building specify the construction type as being 1B or 2B construction. Please verify the actual construction characteristics.
Building08/02/2021ApprovedSheet A001 - Architectural Code Summary & Egress Plans: A001 -Architectural Code Summary 30 July 2021 The existing open stair serves as an 'exit access' stairway. VCC §1019.3
Building08/02/2021ApprovedSheet A400 - Architectural Stair 1 Plans: PROVIDE TESTING LABORATORY DESIGN NUMBER FOR THE DESIRED FIRE RESISTANCE RATING. TYPICAL
Building08/02/2021ApprovedSheet A400 - Architectural Stair 1 Plans: STRUCTURAL COLUMNS SHALL BE INDIVIDUALLY ENCASED WITHIN FIRE RATED ENVELOPES.
Building08/02/2021ApprovedSheet A001 - Architectural Code Summary & Egress Plans: A001 -Architectural Code Summary 30 July 2021 Prior permit activity in this building specify the construction type as being 1B or 2B construction. Please verify the actual construction characteristics.
Building08/02/2021ApprovedSheet A001 - Architectural Code Summary & Egress Plans: A001 -Architectural Code Summary 30 July 2021 The existing open stair serves as an 'exit access' stairway. VCC §1019.3
Building08/02/2021ApprovedSheet A400 - Architectural Stair 1 Plans: PROVIDE TESTING LABORATORY DESIGN NUMBER FOR THE DESIRED FIRE RESISTANCE RATING. TYPICAL
Building08/02/2021ApprovedSheet A400 - Architectural Stair 1 Plans: STRUCTURAL COLUMNS SHALL BE INDIVIDUALLY ENCASED WITHIN FIRE RATED ENVELOPES.
Building08/02/2021RejectedSheet A001 - Architectural Code Summary & Egress Plans: A001 -Architectural Code Summary 30 July 2021 Prior permit activity in this building specify the construction type as being 1B or 2B construction. Please verify the actual construction characteristics.
Building08/02/2021RejectedSheet A001 - Architectural Code Summary & Egress Plans: A001 -Architectural Code Summary 30 July 2021 The existing open stair serves as an 'exit access' stairway. VCC §1019.3
Building08/02/2021RejectedSheet A400 - Architectural Stair 1 Plans: PROVIDE TESTING LABORATORY DESIGN NUMBER FOR THE DESIRED FIRE RESISTANCE RATING. TYPICAL
Building08/02/2021RejectedSheet A400 - Architectural Stair 1 Plans: STRUCTURAL COLUMNS SHALL BE INDIVIDUALLY ENCASED WITHIN FIRE RATED ENVELOPES.
Building08/02/2021RejectedSheet A001 - Architectural Code Summary & Egress Plans: A001 -Architectural Code Summary 30 July 2021 Prior permit activity in this building specify the construction type as being 1B or 2B construction. Please verify the actual construction characteristics.
Building08/02/2021RejectedSheet A001 - Architectural Code Summary & Egress Plans: A001 -Architectural Code Summary 30 July 2021 The existing open stair serves as an 'exit access' stairway. VCC §1019.3
Building08/02/2021RejectedSheet A400 - Architectural Stair 1 Plans: PROVIDE TESTING LABORATORY DESIGN NUMBER FOR THE DESIRED FIRE RESISTANCE RATING. TYPICAL
Building08/02/2021RejectedSheet A400 - Architectural Stair 1 Plans: STRUCTURAL COLUMNS SHALL BE INDIVIDUALLY ENCASED WITHIN FIRE RATED ENVELOPES.
Building09/07/2021AdditionalSheet A000 - Architectural Cover Sheet: SUBMIT AUTOMATIC SUPPRESSION SHOP DRAWINGS FOR APPROVAL SUBMIT FIRE ALARM SYSTEM SHOP DRAWINGS FOR APPROVAL
Building09/07/2021ApprovedSheet A000 - Architectural Cover Sheet: SUBMIT AUTOMATIC SUPPRESSION SHOP DRAWINGS FOR APPROVAL SUBMIT FIRE ALARM SYSTEM SHOP DRAWINGS FOR APPROVAL
Building09/07/2021ApprovedSheet A000 - Architectural Cover Sheet: SUBMIT AUTOMATIC SUPPRESSION SHOP DRAWINGS FOR APPROVAL SUBMIT FIRE ALARM SYSTEM SHOP DRAWINGS FOR APPROVAL
Building12/18/2021RejectedSheet A000 - Architectural Cover Sheet: CTBO-34518-A 3 December 2021 SUBMIT AUTOMATIC SUPPRESSION SHOP DRAWINGS FOR APPROVAL SUBMIT FIRE ALARM SYSTEM SHOP DRAWINGS FOR APPROVAL
Building12/18/2021RejectedA000 - Architectural Cover Sheet 18 December 2021 The revision date for this drawing precedes the date of the original permit submittal. Revise.
Building12/18/2021RejectedSheet A001 - Architectural Code Summary & Egress Plans: A001 -Architectural Code Summary 30 July 2021 It is preferable to call out the changes made to this drawing, rather than applying a stamp saying the entire sheet has been revised. Clarify. TYPICAL
Building12/18/2021RejectedSheet A001 - Architectural Code Summary & Egress Plans: A001 -Architectural Code Summary 30 July 2021 Portions of the drawing are now smeary and less legible. Please restore crisp text. TYPICAL
Building12/18/2021ApprovedSheet A000 - Architectural Cover Sheet: CTBO-34518-A 3 December 2021 SUBMIT AUTOMATIC SUPPRESSION SHOP DRAWINGS FOR APPROVAL SUBMIT FIRE ALARM SYSTEM SHOP DRAWINGS FOR APPROVAL
Building12/18/2021ApprovedA000 - Architectural Cover Sheet 18 December 2021 The revision date for this drawing precedes the date of the original permit submittal. Revise.
Building12/18/2021ApprovedSheet A001 - Architectural Code Summary & Egress Plans: A001 -Architectural Code Summary 30 July 2021 It is preferable to call out the changes made to this drawing, rather than applying a stamp saying the entire sheet has been revised. Clarify. TYPICAL
Building12/18/2021ApprovedSheet A001 - Architectural Code Summary & Egress Plans: A001 -Architectural Code Summary 30 July 2021 Portions of the drawing are now smeary and less legible. Please restore crisp text. TYPICAL
Building12/18/2021ApprovedSheet A000 - Architectural Cover Sheet: CTBO-34518-A 3 December 2021 SUBMIT AUTOMATIC SUPPRESSION SHOP DRAWINGS FOR APPROVAL SUBMIT FIRE ALARM SYSTEM SHOP DRAWINGS FOR APPROVAL
Building12/18/2021ApprovedA000 - Architectural Cover Sheet 18 December 2021 The revision date for this drawing precedes the date of the original permit submittal. Revise.
Building12/18/2021ApprovedSheet A001 - Architectural Code Summary & Egress Plans: A001 -Architectural Code Summary 30 July 2021 It is preferable to call out the changes made to this drawing, rather than applying a stamp saying the entire sheet has been revised. Clarify. TYPICAL
Building12/18/2021ApprovedSheet A001 - Architectural Code Summary & Egress Plans: A001 -Architectural Code Summary 30 July 2021 Portions of the drawing are now smeary and less legible. Please restore crisp text. TYPICAL
Building12/18/2021ApprovedSheet A000 - Architectural Cover Sheet: CTBO-34518-A 3 December 2021 SUBMIT AUTOMATIC SUPPRESSION SHOP DRAWINGS FOR APPROVAL SUBMIT FIRE ALARM SYSTEM SHOP DRAWINGS FOR APPROVAL
Building12/18/2021ApprovedA000 - Architectural Cover Sheet 18 December 2021 The revision date for this drawing precedes the date of the original permit submittal. Revise.
Building12/18/2021ApprovedSheet A001 - Architectural Code Summary & Egress Plans: A001 -Architectural Code Summary 30 July 2021 It is preferable to call out the changes made to this drawing, rather than applying a stamp saying the entire sheet has been revised. Clarify. TYPICAL
Building12/18/2021ApprovedSheet A001 - Architectural Code Summary & Egress Plans: A001 -Architectural Code Summary 30 July 2021 Portions of the drawing are now smeary and less legible. Please restore crisp text. TYPICAL
DES:Water/Sewer Engineering08/01/2021ApprovedNO NEW DFU'S
Electrical07/29/2021ApprovedPlease provide the ampere rating for 'existing' panel board '2L'. Refer to sheets E2.01 and E2.02. Section 109.3 of the Virginia Construction Code.
Electrical07/29/2021ApprovedPlease clarify why the 'MDP' directory indicates 600 ampere MCB, while being fed by 500kcmil feeders (rated for 380 amperes), and protected by 400 ampere fuses in the service disconnect switch? Refer to sheet E2.02.
Electrical07/29/2021ApprovedPlease clarify on the drawings the total number of electrical services are located in this building. The electrical service equipment shown on the 'basement level' (sheet E2.02), show (2) services that are identified as existing. One rated at 200 ampere and the other rated at 400 ampere, that do not appear to be on the load side of the 800 ampere CT cabinet. How are these (2) service disconnect switches being fed from the Dominion Virginia Power? Also, refer to sheet E1.05.
Electrical07/29/2021ApprovedBased on the lack of information provided, additional comments may be forthcoming.
Electrical07/29/2021ApprovedPlease provide the ampere rating for 'existing' panel board '2L'. Refer to sheets E2.01 and E2.02. Section 109.3 of the Virginia Construction Code.
Electrical07/29/2021ApprovedPlease clarify why the 'MDP' directory indicates 600 ampere MCB, while being fed by 500kcmil feeders (rated for 380 amperes), and protected by 400 ampere fuses in the service disconnect switch? Refer to sheet E2.02.
Electrical07/29/2021ApprovedPlease clarify on the drawings the total number of electrical services are located in this building. The electrical service equipment shown on the 'basement level' (sheet E2.02), show (2) services that are identified as existing. One rated at 200 ampere and the other rated at 400 ampere, that do not appear to be on the load side of the 800 ampere CT cabinet. How are these (2) service disconnect switches being fed from the Dominion Virginia Power? Also, refer to sheet E1.05.
Electrical07/29/2021ApprovedBased on the lack of information provided, additional comments may be forthcoming.
Electrical07/29/2021ApprovedPlease provide the ampere rating for 'existing' panel board '2L'. Refer to sheets E2.01 and E2.02. Section 109.3 of the Virginia Construction Code.
Electrical07/29/2021ApprovedPlease clarify why the 'MDP' directory indicates 600 ampere MCB, while being fed by 500kcmil feeders (rated for 380 amperes), and protected by 400 ampere fuses in the service disconnect switch? Refer to sheet E2.02.
Electrical07/29/2021ApprovedPlease clarify on the drawings the total number of electrical services are located in this building. The electrical service equipment shown on the 'basement level' (sheet E2.02), show (2) services that are identified as existing. One rated at 200 ampere and the other rated at 400 ampere, that do not appear to be on the load side of the 800 ampere CT cabinet. How are these (2) service disconnect switches being fed from the Dominion Virginia Power? Also, refer to sheet E1.05.
Electrical07/29/2021ApprovedBased on the lack of information provided, additional comments may be forthcoming.
Electrical07/29/2021ApprovedPlease provide the ampere rating for 'existing' panel board '2L'. Refer to sheets E2.01 and E2.02. Section 109.3 of the Virginia Construction Code.
Electrical07/29/2021ApprovedPlease clarify why the 'MDP' directory indicates 600 ampere MCB, while being fed by 500kcmil feeders (rated for 380 amperes), and protected by 400 ampere fuses in the service disconnect switch? Refer to sheet E2.02.
Electrical07/29/2021ApprovedPlease clarify on the drawings the total number of electrical services are located in this building. The electrical service equipment shown on the 'basement level' (sheet E2.02), show (2) services that are identified as existing. One rated at 200 ampere and the other rated at 400 ampere, that do not appear to be on the load side of the 800 ampere CT cabinet. How are these (2) service disconnect switches being fed from the Dominion Virginia Power? Also, refer to sheet E1.05.
Electrical07/29/2021ApprovedBased on the lack of information provided, additional comments may be forthcoming.
Electrical07/29/2021ApprovedPlease provide the ampere rating for 'existing' panel board '2L'. Refer to sheets E2.01 and E2.02. Section 109.3 of the Virginia Construction Code.
Electrical07/29/2021ApprovedPlease clarify why the 'MDP' directory indicates 600 ampere MCB, while being fed by 500kcmil feeders (rated for 380 amperes), and protected by 400 ampere fuses in the service disconnect switch? Refer to sheet E2.02.
Electrical07/29/2021ApprovedPlease clarify on the drawings the total number of electrical services are located in this building. The electrical service equipment shown on the 'basement level' (sheet E2.02), show (2) services that are identified as existing. One rated at 200 ampere and the other rated at 400 ampere, that do not appear to be on the load side of the 800 ampere CT cabinet. How are these (2) service disconnect switches being fed from the Dominion Virginia Power? Also, refer to sheet E1.05.
Electrical07/29/2021ApprovedBased on the lack of information provided, additional comments may be forthcoming.
Electrical07/29/2021RejectedPlease provide the ampere rating for 'existing' panel board '2L'. Refer to sheets E2.01 and E2.02. Section 109.3 of the Virginia Construction Code.
Electrical07/29/2021RejectedPlease clarify why the 'MDP' directory indicates 600 ampere MCB, while being fed by 500kcmil feeders (rated for 380 amperes), and protected by 400 ampere fuses in the service disconnect switch? Refer to sheet E2.02.
Electrical07/29/2021RejectedPlease clarify on the drawings the total number of electrical services are located in this building. The electrical service equipment shown on the 'basement level' (sheet E2.02), show (2) services that are identified as existing. One rated at 200 ampere and the other rated at 400 ampere, that do not appear to be on the load side of the 800 ampere CT cabinet. How are these (2) service disconnect switches being fed from the Dominion Virginia Power? Also, refer to sheet E1.05.
Electrical07/29/2021RejectedBased on the lack of information provided, additional comments may be forthcoming.
Electrical07/29/2021AdditionalPlease provide the ampere rating for 'existing' panel board '2L'. Refer to sheets E2.01 and E2.02. Section 109.3 of the Virginia Construction Code.
Electrical07/29/2021AdditionalPlease clarify why the 'MDP' directory indicates 600 ampere MCB, while being fed by 500kcmil feeders (rated for 380 amperes), and protected by 400 ampere fuses in the service disconnect switch? Refer to sheet E2.02.
Electrical07/29/2021AdditionalPlease clarify on the drawings the total number of electrical services are located in this building. The electrical service equipment shown on the 'basement level' (sheet E2.02), show (2) services that are identified as existing. One rated at 200 ampere and the other rated at 400 ampere, that do not appear to be on the load side of the 800 ampere CT cabinet. How are these (2) service disconnect switches being fed from the Dominion Virginia Power? Also, refer to sheet E1.05.
Electrical07/29/2021AdditionalBased on the lack of information provided, additional comments may be forthcoming.
EPlan Review12/01/2021Approved 
Mechanical07/21/2021ApprovedSheet M1.02 Mechanical First Floor: Combination fire/smoke damper is required where duct penetrate a rated shaft.
Mechanical07/21/2021RejectedSheet M1.02 Mechanical First Floor: Combination fire/smoke damper is required where duct penetrate a rated shaft.
Mechanical07/21/2021RejectedSheet M1.02 Mechanical First Floor: Combination fire/smoke damper is required where duct penetrate a rated shaft.
Mechanical07/21/2021ApprovedSheet M1.02 Mechanical First Floor: Combination fire/smoke damper is required where duct penetrate a rated shaft.
Mechanical07/21/2021ApprovedSheet M1.02 Mechanical First Floor: Combination fire/smoke damper is required where duct penetrate a rated shaft.
Mechanical08/23/2021ApprovedSheet M1.01 Mechanical Basement: 1-Please provide return grills for mechanical/storage room and office. 2- Smoke damper is not required where building is equipped throughout with an automatic sprinkler system (IBC section 903.3.1.1).
Mechanical08/23/2021ApprovedSheet M1.01 Mechanical Basement: 1-Please provide return grills for mechanical/storage room and office. 2- Smoke damper is not required where building is equipped throughout with an automatic sprinkler system (IBC section 903.3.1.1).
Mechanical08/23/2021RejectedSheet M1.01 Mechanical Basement: 1-Please provide return grills for mechanical/storage room and office. 2- Smoke damper is not required where building is equipped throughout with an automatic sprinkler system (IBC section 903.3.1.1).
Mechanical08/23/2021ApprovedSheet M1.01 Mechanical Basement: 1-Please provide return grills for mechanical/storage room and office. 2- Smoke damper is not required where building is equipped throughout with an automatic sprinkler system (IBC section 903.3.1.1).
Plumbing07/26/2021Approved7-26-21 Please provide Gas riser Diagram to include lengths, size , total BTU. 2015 VFGC 402
Plumbing07/26/2021Approved7-26-21 Please provide Gas riser Diagram to include lengths, size , total BTU. 2015 VFGC 402
Plumbing07/26/2021Rejected7-26-21 Please provide Gas riser Diagram to include lengths, size , total BTU. 2015 VFGC 402
Plumbing07/26/2021Approved7-26-21 Please provide Gas riser Diagram to include lengths, size , total BTU. 2015 VFGC 402
Plumbing07/26/2021Approved7-26-21 Please provide Gas riser Diagram to include lengths, size , total BTU. 2015 VFGC 402
Plumbing07/26/2021Approved7-26-21 Please provide Gas riser Diagram to include lengths, size , total BTU. 2015 VFGC 402
Structural07/28/2021RejectedSpecial Inspections: REJECTED. The statement of special inspection is used by the structural engineer of record (SER) to identify the structural items that require special inspection. This is a legal statement that shall be filled out by the Structural Engineer of Record (SER). All applicable item lines of inspection shall be initialed by both the structural engineer of record (SER) and the special inspection engineer of record (SIER). This statement must contain signatures from the following parties. • Owner • Structural Engineer of Record (SER) • Geotechnical Engineer of Record (GER) • Precast Concrete Engineer of Record (PER) (if applicable) • Special Inspection Engineer of Record (SIER) • Testing Agency Engineer of Record (if
Structural07/28/2021ApprovedSpecial Inspections: REJECTED. The statement of special inspection is used by the structural engineer of record (SER) to identify the structural items that require special inspection. This is a legal statement that shall be filled out by the Structural Engineer of Record (SER). All applicable item lines of inspection shall be initialed by both the structural engineer of record (SER) and the special inspection engineer of record (SIER). This statement must contain signatures from the following parties. • Owner • Structural Engineer of Record (SER) • Geotechnical Engineer of Record (GER) • Precast Concrete Engineer of Record (PER) (if applicable) • Special Inspection Engineer of Record (SIER) • Testing Agency Engineer of Record (if
Structural07/28/2021ApprovedSpecial Inspections: REJECTED. The statement of special inspection is used by the structural engineer of record (SER) to identify the structural items that require special inspection. This is a legal statement that shall be filled out by the Structural Engineer of Record (SER). All applicable item lines of inspection shall be initialed by both the structural engineer of record (SER) and the special inspection engineer of record (SIER). This statement must contain signatures from the following parties. • Owner • Structural Engineer of Record (SER) • Geotechnical Engineer of Record (GER) • Precast Concrete Engineer of Record (PER) (if applicable) • Special Inspection Engineer of Record (SIER) • Testing Agency Engineer of Record (if
Structural07/28/2021RejectedSpecial Inspections: REJECTED. The statement of special inspection is used by the structural engineer of record (SER) to identify the structural items that require special inspection. This is a legal statement that shall be filled out by the Structural Engineer of Record (SER). All applicable item lines of inspection shall be initialed by both the structural engineer of record (SER) and the special inspection engineer of record (SIER). This statement must contain signatures from the following parties. • Owner • Structural Engineer of Record (SER) • Geotechnical Engineer of Record (GER) • Precast Concrete Engineer of Record (PER) (if applicable) • Special Inspection Engineer of Record (SIER) • Testing Agency Engineer of Record (if
Structural07/28/2021RejectedSpecial Inspections: REJECTED. The statement of special inspection is used by the structural engineer of record (SER) to identify the structural items that require special inspection. This is a legal statement that shall be filled out by the Structural Engineer of Record (SER). All applicable item lines of inspection shall be initialed by both the structural engineer of record (SER) and the special inspection engineer of record (SIER). This statement must contain signatures from the following parties. • Owner • Structural Engineer of Record (SER) • Geotechnical Engineer of Record (GER) • Precast Concrete Engineer of Record (PER) (if applicable) • Special Inspection Engineer of Record (SIER) • Testing Agency Engineer of Record (if
Structural09/07/2021RejectedSpecial Inspections: REJECTED missing SIER and GC information and signatures.
Structural09/07/2021RejectedSpecial Inspections: REJECTED missing SIER and GC information and signatures.
Structural09/07/2021ApprovedSpecial Inspections: REJECTED missing SIER and GC information and signatures.
Structural09/07/2021ApprovedSpecial Inspections: REJECTED missing SIER and GC information and signatures.
Structural10/26/2021ApprovedPlease fill in the SIER information. Approval pending on GC info.
Structural10/26/2021RejectedPlease fill in the SIER information. Approval pending on GC info.
Structural10/26/2021ApprovedPlease fill in the SIER information. Approval pending on GC info.
Zoning01/06/2022ApprovedRejected: Submitted plan does not match the original and admin change plans . Please revise to match or submit an admin change amendment. Reviewer: Mudoh Mbah SAM Tel: 703-228-3727 Email: mmbah@arlingtonva.us
Zoning01/06/2022ApprovedInterior alteration in blding in sp397. Proposed work includes demo of existing stair and building of two new stair cases. No admin change approval is identified. No use is proposed yet. Admin change for proposed work zadm210110 is approved APPROVAL NOTE: 1. Work must be done as shown on the plan and plat submitted for zoning review. Any alteration to the above will need zoning review and approval. 2. A copy of wall check is required upon completion of the foundation. Reviewer: Mudoh Mbah SAM Tel: 703-228-3727 Email: mmbah@arlingtonva.us
Zoning01/06/2022RejectedRejected: Submitted plan does not match the original and admin change plans . Please revise to match or submit an admin change amendment. Reviewer: Mudoh Mbah SAM Tel: 703-228-3727 Email: mmbah@arlingtonva.us
Zoning01/06/2022RejectedInterior alteration in blding in sp397. Proposed work includes demo of existing stair and building of two new stair cases. No admin change approval is identified. No use is proposed yet. Admin change for proposed work zadm210110 is approved APPROVAL NOTE: 1. Work must be done as shown on the plan and plat submitted for zoning review. Any alteration to the above will need zoning review and approval. 2. A copy of wall check is required upon completion of the foundation. Reviewer: Mudoh Mbah SAM Tel: 703-228-3727 Email: mmbah@arlingtonva.us
Zoning01/06/2022ApprovedInterior alteration in blding in sp397. Proposed work includes demo of existing stair and building of two new stair cases. No admin change approval is identified. No use is proposed yet. Admin change for proposed work zadm210110 is approved APPROVAL NOTE: 1. Work must be done as shown on the plan and plat submitted for zoning review. Any alteration to the above will need zoning review and approval. 2. A copy of wall check is required upon completion of the foundation. Reviewer: Mudoh Mbah SAM Tel: 703-228-3727 Email: mmbah@arlingtonva.us
Zoning01/06/2022ApprovedRejected: Submitted plan does not match the original and admin change plans . Please revise to match or submit an admin change amendment. Reviewer: Mudoh Mbah SAM Tel: 703-228-3727 Email: mmbah@arlingtonva.us
Zoning01/20/2022ApprovedAdmin change ACHG22-00009 is approved for the proposed revision. No zoning issues.
Zoning01/20/2022ApprovedAdmin change ACHG22-00009 is approved for the proposed revision. No zoning issues.
Zoning06/07/2022ApprovedNo zoning issues
Zoning08/02/2021RejectedInterior alteration in blding in sp397. Proposed work includes demo of existing stair and building of two new stair cases. No admin change approval. Rejected: 1. Proposed change is susbstantial. An admin change approval is required. Use the link below to download the Administrative change application or contact the zoning department at 703-228-3883 for assistance. https://arlingtonva.s3.dualstack.us-east-1.amazonaws.com/wp-content/uploads/sites/38/2016/07/Administrative-Change-Application.pdf 2. Further review shall be done after change is approve. Please attach a zoning comment response letter when submitting revisions. Reviewer: Mudoh Mbah SAM Tel: 703-228-3727 Email: mmbah@arlingtonva.us
Zoning08/06/2021RejectedInterior alteration in blding in sp397. Proposed work includes demo of existing stair and building of two new stair cases. No admin change approval. Rejected: 1. Proposed change is substantial. An admin change approval is required. Use the link below to download the Administrative change application or contact the zoning department at 703-228-3883 for assistance. https://arlingtonva.s3.dualstack.us-east-1.amazonaws.com/wp-content/uploads/sites/38/2016/07/Administrative-Change-Application.pdf 2. Further review shall be done after change is approve. Please attach a zoning comment response letter when submitting revisions. Reviewer: Mudoh Mbah SAM Tel: 703-228-3727 Email: mmbah@arlingtonva.us
Zoning08/12/2021RejectedInterior alteration in blding in sp397. Proposed work includes demo of existing stair and building of two new stair cases. No admin change approval. Rejected: 1. Proposed change is substantial. An admin change approval is required. Use the link below to download the Administrative change application or contact the zoning department at 703-228-3883 for assistance. https://arlingtonva.s3.dualstack.us-east-1.amazonaws.com/wp-content/uploads/sites/38/2016/07/Administrative-Change-Application.pdf 2. Further review shall be done after change is approve. Please attach a zoning comment response letter when submitting revisions. Reviewer: Mudoh Mbah SAM Tel: 703-228-3727 Email: mmbah@arlingtonva.us
Zoning08/13/2021RejectedInterior alteration in blding in sp397. Proposed work includes demo of existing stair and building of two new stair cases. No admin change approval is identified. No use is proposed yet. Rejected: 1. Proposed change is substantial. An admin change approval is required. Use the link below to download the Administrative change application or contact the zoning department at 703-228-3883 for assistance. https://arlingtonva.s3.dualstack.us-east-1.amazonaws.com/wp-content/uploads/sites/38/2016/07/Administrative-Change-Application.pdf 2. Further review shall be done after change is approve. Please attach a zoning comment response letter when submitting revisions. Reviewer: Mudoh Mbah SAM Tel: 703-228-3727 Email: mmbah@arlingtonva.us
Zoning09/07/2021RejectedInterior alteration in blding in sp397. Proposed work includes demo of existing stair and building of two new stair cases. No admin change approval is identified. No use is proposed yet. Rejected: 1. Proposed change is substantial. An admin change approval is required. Use the link below to download the Administrative change application or contact the zoning department at 703-228-3883 for assistance. https://arlingtonva.s3.dualstack.us-east-1.amazonaws.com/wp-content/uploads/sites/38/2016/07/Administrative-Change-Application.pdf 2. Further review shall be done after change is approve. Please attach a zoning comment response letter when submitting revisions. Reviewer: Mudoh Mbah SAM Tel: 703-228-3727 Email: mmbah@arlingtonva.us
Zoning09/07/2021RejectedAdmin change required. Please submit and get admin approval for the proposed work. This permit is rejected because it has been rejected by atleast one other reviewer.
Zoning09/07/2021ApprovedInterior alteration in blding in sp397. Proposed work includes demo of existing stair and building of two new stair cases. No admin change approval is identified. No use is proposed yet. Rejected: 1. Proposed change is substantial. An admin change approval is required. Use the link below to download the Administrative change application or contact the zoning department at 703-228-3883 for assistance. https://arlingtonva.s3.dualstack.us-east-1.amazonaws.com/wp-content/uploads/sites/38/2016/07/Administrative-Change-Application.pdf 2. Further review shall be done after change is approve. Please attach a zoning comment response letter when submitting revisions. Reviewer: Mudoh Mbah SAM Tel: 703-228-3727 Email: mmbah@arlingtonva.us
Zoning09/07/2021ApprovedAdmin change required. Please submit and get admin approval for the proposed work. This permit is rejected because it has been rejected by atleast one other reviewer.
Zoning09/07/2021RejectedInterior alteration in blding in sp397. Proposed work includes demo of existing stair and building of two new stair cases. No admin change approval is identified. No use is proposed yet. Rejected: 1. Proposed change is substantial. An admin change approval is required. Use the link below to download the Administrative change application or contact the zoning department at 703-228-3883 for assistance. https://arlingtonva.s3.dualstack.us-east-1.amazonaws.com/wp-content/uploads/sites/38/2016/07/Administrative-Change-Application.pdf 2. Further review shall be done after change is approve. Please attach a zoning comment response letter when submitting revisions. Reviewer: Mudoh Mbah SAM Tel: 703-228-3727 Email: mmbah@arlingtonva.us
Zoning09/07/2021RejectedAdmin change required. Please submit and get admin approval for the proposed work. This permit is rejected because it has been rejected by atleast one other reviewer.
Zoning09/07/2021ApprovedInterior alteration in blding in sp397. Proposed work includes demo of existing stair and building of two new stair cases. No admin change approval is identified. No use is proposed yet. Rejected: 1. Proposed change is substantial. An admin change approval is required. Use the link below to download the Administrative change application or contact the zoning department at 703-228-3883 for assistance. https://arlingtonva.s3.dualstack.us-east-1.amazonaws.com/wp-content/uploads/sites/38/2016/07/Administrative-Change-Application.pdf 2. Further review shall be done after change is approve. Please attach a zoning comment response letter when submitting revisions. Reviewer: Mudoh Mbah SAM Tel: 703-228-3727 Email: mmbah@arlingtonva.us
Zoning09/07/2021ApprovedAdmin change required. Please submit and get admin approval for the proposed work. This permit is rejected because it has been rejected by atleast one other reviewer.
Zoning09/07/2021AdditionalAdmin change required. Please submit and get admin approval for the proposed work. This permit is rejected because it has been rejected by atleast one other reviewer.
Zoning09/07/2021AdditionalInterior alteration in blding in sp397. Proposed work includes demo of existing stair and building of two new stair cases. No admin change approval is identified. No use is proposed yet. Rejected: 1. Proposed change is substantial. An admin change approval is required. Use the link below to download the Administrative change application or contact the zoning department at 703-228-3883 for assistance. https://arlingtonva.s3.dualstack.us-east-1.amazonaws.com/wp-content/uploads/sites/38/2016/07/Administrative-Change-Application.pdf 2. Further review shall be done after change is approve. Please attach a zoning comment response letter when submitting revisions. Reviewer: Mudoh Mbah SAM Tel: 703-228-3727 Email: mmbah@arlingtonva.us
Zoning09/07/2021RejectedInterior alteration in blding in sp397. Proposed work includes demo of existing stair and building of two new stair cases. No admin change approval is identified. No use is proposed yet. Rejected: 1. Proposed change is substantial. An admin change approval is required. Use the link below to download the Administrative change application or contact the zoning department at 703-228-3883 for assistance. https://arlingtonva.s3.dualstack.us-east-1.amazonaws.com/wp-content/uploads/sites/38/2016/07/Administrative-Change-Application.pdf 2. Further review shall be done after change is approve. Please attach a zoning comment response letter when submitting revisions. Reviewer: Mudoh Mbah SAM Tel: 703-228-3727 Email: mmbah@arlingtonva.us
Zoning09/07/2021RejectedAdmin change required. Please submit and get admin approval for the proposed work. This permit is rejected because it has been rejected by atleast one other reviewer.
Zoning09/07/2021ApprovedInterior alteration in blding in sp397. Proposed work includes demo of existing stair and building of two new stair cases. No admin change approval is identified. No use is proposed yet. Rejected: 1. Proposed change is substantial. An admin change approval is required. Use the link below to download the Administrative change application or contact the zoning department at 703-228-3883 for assistance. https://arlingtonva.s3.dualstack.us-east-1.amazonaws.com/wp-content/uploads/sites/38/2016/07/Administrative-Change-Application.pdf 2. Further review shall be done after change is approve. Please attach a zoning comment response letter when submitting revisions. Reviewer: Mudoh Mbah SAM Tel: 703-228-3727 Email: mmbah@arlingtonva.us
Zoning09/07/2021ApprovedAdmin change required. Please submit and get admin approval for the proposed work. This permit is rejected because it has been rejected by atleast one other reviewer.
Zoning11/23/2021RejectedInterior alteration in blding in sp397. Proposed work includes demo of existing stair and building of two new stair cases. No admin change approval is identified. No use is proposed yet. Admin change for proposed work zadm210110 is approved APPROVAL NOTE: 1. Work must be done as shown on the plan and plat submitted for zoning review. Any alteration to the above will need zoning review and approval. 2. A copy of wall check is required upon completion of the foundation. Reviewer: Mudoh Mbah SAM Tel: 703-228-3727 Email: mmbah@arlingtonva.us
Zoning11/23/2021ApprovedInterior alteration in blding in sp397. Proposed work includes demo of existing stair and building of two new stair cases. No admin change approval is identified. No use is proposed yet. Admin change for proposed work zadm210110 is approved APPROVAL NOTE: 1. Work must be done as shown on the plan and plat submitted for zoning review. Any alteration to the above will need zoning review and approval. 2. A copy of wall check is required upon completion of the foundation. Reviewer: Mudoh Mbah SAM Tel: 703-228-3727 Email: mmbah@arlingtonva.us
Zoning12/10/2021RejectedRevision to change previously approved design in admin change. Rejected: 1. Revision to the plan set does not match the plans approved in the admin change. Please submit an admin change application to match the new proposal. 2. Please attach a zoning comment response letter when submitting revisions. Reviewer: Mudoh Mbah SAM Tel: 703-228-3727 Email: mmbah@arlingtonva.us
Zoning12/10/2021ApprovedRevision to change previously approved design in admin change. Rejected: 1. Revision to the plan set does not match the plans approved in the admin change. Please submit an admin change application to match the new proposal. 2. Please attach a zoning comment response letter when submitting revisions. Reviewer: Mudoh Mbah SAM Tel: 703-228-3727 Email: mmbah@arlingtonva.us
Zoning12/10/2021RejectedRevision to change previously approved design in admin change. Rejected: 1. Revision to the plan set does not match the plans approved in the admin change. Please submit an admin change application to match the new proposal. 2. Please attach a zoning comment response letter when submitting revisions. Reviewer: Mudoh Mbah SAM Tel: 703-228-3727 Email: mmbah@arlingtonva.us
Zoning12/10/2021ApprovedRevision to change previously approved design in admin change. Rejected: 1. Revision to the plan set does not match the plans approved in the admin change. Please submit an admin change application to match the new proposal. 2. Please attach a zoning comment response letter when submitting revisions. Reviewer: Mudoh Mbah SAM Tel: 703-228-3727 Email: mmbah@arlingtonva.us