Review | Review Date | Status | Comments |
Building | 08/26/2021 | Additional | Sheet LS1-0 - LIFE SAFETY _ ACCESSIBILITY: Please note the correction: Grab bar mounting height dimension is to the top of the grab bar and not to the centerline of the grab bar.
Code Reference: 2009 ICC A117.1 Sec 604.5.2;
|
Building | 08/26/2021 | Additional | Sheet A2-1 - FLOOR PLAN: Door maneuvering clearance at pull side requires 18 inches for compliance. Column appears to be an obstruction. Please show compliance.
Code Reference: 2009 ICC A117.1 Sec. 404.2.3 |
Building | 08/26/2021 | Additional | Sheet A2-1 - FLOOR PLAN: Please indicate that the casework, service counters meet the accessibility requirements for forward and/or side wheelchair approaches per 2009 ICC A117.1 section 904
Code Reference: 2009 ICC A117.1 Section 904 / 904.3 |
Building | 08/26/2021 | Approved | Sheet LS1-0 - LIFE SAFETY _ ACCESSIBILITY: Please note the correction: Grab bar mounting height dimension is to the top of the grab bar and not to the centerline of the grab bar.
Code Reference: 2009 ICC A117.1 Sec 604.5.2; |
Building | 08/26/2021 | Approved | Sheet A2-1 - FLOOR PLAN: Door maneuvering clearance at pull side requires 18 inches for compliance. Column appears to be an obstruction. Please show compliance.
Code Reference: 2009 ICC A117.1 Sec. 404.2.3 |
Building | 08/26/2021 | Approved | Sheet A2-1 - FLOOR PLAN: Please indicate that the casework, service counters meet the accessibility requirements for forward and/or side wheelchair approaches per 2009 ICC A117.1 section 904
Code Reference: 2009 ICC A117.1 Section 904 / 904.3 |
Building | 08/26/2021 | Rejected | Sheet LS1-0 - LIFE SAFETY _ ACCESSIBILITY: Please note the correction: Grab bar mounting height dimension is to the top of the grab bar and not to the centerline of the grab bar.
Code Reference: 2009 ICC A117.1 Sec 604.5.2;
|
Building | 08/26/2021 | Rejected | Sheet A2-1 - FLOOR PLAN: Door maneuvering clearance at pull side requires 18 inches for compliance. Column appears to be an obstruction. Please show compliance.
Code Reference: 2009 ICC A117.1 Sec. 404.2.3 |
Building | 08/26/2021 | Rejected | Sheet A2-1 - FLOOR PLAN: Please indicate that the casework, service counters meet the accessibility requirements for forward and/or side wheelchair approaches per 2009 ICC A117.1 section 904
Code Reference: 2009 ICC A117.1 Section 904 / 904.3 |
Building | 08/26/2021 | Approved | Sheet LS1-0 - LIFE SAFETY _ ACCESSIBILITY: Please note the correction: Grab bar mounting height dimension is to the top of the grab bar and not to the centerline of the grab bar.
Code Reference: 2009 ICC A117.1 Sec 604.5.2; |
Building | 08/26/2021 | Approved | Sheet A2-1 - FLOOR PLAN: Door maneuvering clearance at pull side requires 18 inches for compliance. Column appears to be an obstruction. Please show compliance.
Code Reference: 2009 ICC A117.1 Sec. 404.2.3 |
Building | 08/26/2021 | Approved | Sheet A2-1 - FLOOR PLAN: Please indicate that the casework, service counters meet the accessibility requirements for forward and/or side wheelchair approaches per 2009 ICC A117.1 section 904
Code Reference: 2009 ICC A117.1 Section 904 / 904.3 |
Building | 09/02/2021 | Approved | Reviewed under the 2018 Virginia Construction Code and the Virginia Uniform Statewide Building Code (VUSBC). Please correct any references to VUSRC. The 2018 Virginia Construction Code can be found for free online at https://codes.iccsafe.org/category/Virginia
If you have questions regarding this building plan review, please contact me via email at aawofisayo@arlingtonva.us or by telephone at 703-228-0542. |
Building | 09/02/2021 | Approved | Sheet A4-1 - DOOR SCHEDULE- DOOR DETAILS: Please specify accessible hardware to meet the accessible provision of the VCC and the ICC A117.1. Please note this requirement on the drawings.
Code Reference: VCC Section 1010.1.9.1; 2009 ICC A117.1 Section 404.2.6, |
Building | 09/02/2021 | Approved | Sheet A4-1 - DOOR SCHEDULE- DOOR DETAILS: Please populate hardware set column on the door schedule to facilitate plan review. |
Building | 09/02/2021 | Approved | Sheet T1-1 - COVER SHEET: Please note the correct construction type on the drawing. Construction type is Type II-B and not Type III-B. |
Building | 09/02/2021 | Approved | Sheet T1-1 - COVER SHEET: Minimum required corridor width shall be not less than 44” as required by Table 1020.2 of the Virginia Construction Code.
Code Reference: VCC Section 1020.2 |
Building | 09/02/2021 | Approved | Sheet A2-1 - FLOOR PLAN: The plans show an occupant load of 55 for the tenant space. The space requires a minimum of 2 means of egress with egress doors opening in the direction of travel. Please show egress doors swing open in the direction of travel.
Code Reference: VCC Section 1010.1.2
|
Building | 09/02/2021 | Rejected | Sheet A4-1 - DOOR SCHEDULE- DOOR DETAILS: Please specify accessible hardware to meet the accessible provision of the VCC and the ICC A117.1. Please note this requirement on the drawings.
Code Reference: VCC Section 1010.1.9.1; 2009 ICC A117.1 Section 404.2.6,
|
Building | 09/02/2021 | Rejected | Sheet A4-1 - DOOR SCHEDULE- DOOR DETAILS: Please populate hardware set column on the door schedule to facilitate plan review. |
Building | 09/02/2021 | Rejected | Sheet T1-1 - COVER SHEET: Please note the correct construction type on the drawing. Construction type is Type II-B and not Type III-B. |
Building | 09/02/2021 | Rejected | Sheet T1-1 - COVER SHEET: Minimum required corridor width shall be not less than 44” as required by Table 1020.2 of the Virginia Construction Code.
Code Reference: VCC Section 1020.2
|
Building | 09/02/2021 | Rejected | Sheet A2-1 - FLOOR PLAN: The plans show an occupant load of 55 for the tenant space. The space requires a minimum of 2 means of egress with egress doors opening in the direction of travel. Please show egress doors swing open in the direction of travel.
Code Reference: VCC Section 1010.1.2
|
Building | 09/02/2021 | Rejected | Sheet A2-1 - FLOOR PLAN: It appears that the existing restroom may not be in full compliance of the accessibility requirements of the VCC. Please verify fixture clearances, grab bars and other provision for accessible toilets per 2009 ICC A117.1 Section 604. Modify Accessible Compliance Form as needed to reflect the condition of the tenant space.
Code Reference: VCC Section 1102.1; 2009 ICC A117.1 Section 604
|
Building | 09/02/2021 | Rejected | Reviewed under the 2018 Virginia Construction Code and the Virginia Uniform Statewide Building Code (VUSBC). Please correct any references to VUSRC. The 2018 Virginia Construction Code can be found for free online at https://codes.iccsafe.org/category/Virginia
If you have questions regarding this building plan review, please contact me via email at aawofisayo@arlingtonva.us or by telephone at 703-228-0542.
|
Building | 09/02/2021 | Approved | Sheet A4-1 - DOOR SCHEDULE- DOOR DETAILS: Please specify accessible hardware to meet the accessible provision of the VCC and the ICC A117.1. Please note this requirement on the drawings.
Code Reference: VCC Section 1010.1.9.1; 2009 ICC A117.1 Section 404.2.6, |
Building | 09/02/2021 | Approved | Sheet A4-1 - DOOR SCHEDULE- DOOR DETAILS: Please populate hardware set column on the door schedule to facilitate plan review. |
Building | 09/02/2021 | Approved | Sheet T1-1 - COVER SHEET: Please note the correct construction type on the drawing. Construction type is Type II-B and not Type III-B. |
Building | 09/02/2021 | Approved | Sheet T1-1 - COVER SHEET: Minimum required corridor width shall be not less than 44” as required by Table 1020.2 of the Virginia Construction Code.
Code Reference: VCC Section 1020.2 |
Building | 09/02/2021 | Approved | Sheet A2-1 - FLOOR PLAN: The plans show an occupant load of 55 for the tenant space. The space requires a minimum of 2 means of egress with egress doors opening in the direction of travel. Please show egress doors swing open in the direction of travel.
Code Reference: VCC Section 1010.1.2
|
Building | 09/02/2021 | Additional | Sheet A4-1 - DOOR SCHEDULE- DOOR DETAILS: Please specify accessible hardware to meet the accessible provision of the VCC and the ICC A117.1. Please note this requirement on the drawings.
Code Reference: VCC Section 1010.1.9.1; 2009 ICC A117.1 Section 404.2.6,
|
Building | 09/02/2021 | Additional | Sheet A4-1 - DOOR SCHEDULE- DOOR DETAILS: Please populate hardware set column on the door schedule to facilitate plan review. |
Building | 09/02/2021 | Additional | Sheet T1-1 - COVER SHEET: Please note the correct construction type on the drawing. Construction type is Type II-B and not Type III-B. |
Building | 09/02/2021 | Additional | Sheet T1-1 - COVER SHEET: Minimum required corridor width shall be not less than 44” as required by Table 1020.2 of the Virginia Construction Code.
Code Reference: VCC Section 1020.2
|
Building | 09/02/2021 | Additional | Sheet A2-1 - FLOOR PLAN: The plans show an occupant load of 55 for the tenant space. The space requires a minimum of 2 means of egress with egress doors opening in the direction of travel. Please show egress doors swing open in the direction of travel.
Code Reference: VCC Section 1010.1.2
|
Building | 09/02/2021 | Additional | Sheet A2-1 - FLOOR PLAN: It appears that the existing restroom may not be in full compliance of the accessibility requirements of the VCC. Please verify fixture clearances, grab bars and other provision for accessible toilets per 2009 ICC A117.1 Section 604. Modify Accessible Compliance Form as needed to reflect the condition of the tenant space.
Code Reference: VCC Section 1102.1; 2009 ICC A117.1 Section 604
|
Building | 09/02/2021 | Additional | Reviewed under the 2018 Virginia Construction Code and the Virginia Uniform Statewide Building Code (VUSBC). Please correct any references to VUSRC. The 2018 Virginia Construction Code can be found for free online at https://codes.iccsafe.org/category/Virginia
If you have questions regarding this building plan review, please contact me via email at aawofisayo@arlingtonva.us or by telephone at 703-228-0542.
|
Building | 09/02/2021 | Approved | Reviewed under the 2018 Virginia Construction Code and the Virginia Uniform Statewide Building Code (VUSBC). Please correct any references to VUSRC. The 2018 Virginia Construction Code can be found for free online at https://codes.iccsafe.org/category/Virginia
If you have questions regarding this building plan review, please contact me via email at aawofisayo@arlingtonva.us or by telephone at 703-228-0542. |
Building | 10/11/2021 | Approved | Review Date: 10/11/21
The revised documents shall be named exactly as the original documents submitted. A duplicate document that has been renamed creates an issue when the approved plan set is created. Both the original and the revised documents will receive an approval stamp and create confusion on which is the correct document. |
Building | 10/11/2021 | Additional | Review Date: 10/11/21
The revised documents shall be named exactly as the original documents submitted. A duplicate document that has been renamed creates an issue when the approved plan set is created. Both the original and the revised documents will receive an approval stamp and create confusion on which is the correct document. |
Building | 10/11/2021 | Approved | Review Date: 10/11/21
The revised documents shall be named exactly as the original documents submitted. A duplicate document that has been renamed creates an issue when the approved plan set is created. Both the original and the revised documents will receive an approval stamp and create confusion on which is the correct document. |
Building | 10/25/2021 | Approved | Sheet A2-1 - FLOOR PLAN: It appears that the existing restroom may not be in full compliance of the accessibility requirements of the VCC. Please verify fixture clearances, grab bars and other provision for accessible toilets per 2009 ICC A117.1 Section 604. Modify Accessible Compliance Form as needed to reflect the condition of the tenant space.
Code Reference: VCC Section 1102.1; 2009 ICC A117.1 Section 604 |
Building | 10/25/2021 | Approved | Sheet A2-1 - FLOOR PLAN: It appears that the existing restroom may not be in full compliance of the accessibility requirements of the VCC. Please verify fixture clearances, grab bars and other provision for accessible toilets per 2009 ICC A117.1 Section 604. Modify Accessible Compliance Form as needed to reflect the condition of the tenant space.
Code Reference: VCC Section 1102.1; 2009 ICC A117.1 Section 604 |
DES:Water/Sewer Engineering | 12/07/2021 | Approved | INT ALT. 14 NEW DFU'S. COMMERCIAL INT ALT. APPROVED |
Electrical | 09/13/2021 | Rejected | Indicate on the drawings the 'type' of grounding electrode(s) to be used to properly ground the re-located 45kva transformer. NEC Article 250.30 (A) (4). Refer to Note 3, under the 'Key Notes' shown on sheet E3.01. Also, Section 109.3 of the Virginia Construction Code. |
Electrical | 09/13/2021 | Rejected | On sheet E3.01, 'Key Note' #6 references an existing 60 ampere disconnect to be removed. However, Key Note #6 appears to be an electrical transformer. Please clarify. |
Electrical | 09/13/2021 | Rejected | Based on the lack of information provided, additional design information is required for the county to review for code compliance. Additional comments may be forthcoming. Section 109.3 of the Virginia Construction Code. |
Electrical | 09/13/2021 | Rejected | Indicate on the drawings the 'type' of grounding electrode(s) to be used to properly ground the re-located 45kva transformer. NEC Article 250.30 (A) (4). Refer to Note 3, under the 'Key Notes' shown on sheet E3.01. Also, Section 109.3 of the Virginia Construction Code. |
Electrical | 09/13/2021 | Rejected | On sheet E3.01, 'Key Note' #6 references an existing 60 ampere disconnect to be removed. However, Key Note #6 appears to be an electrical transformer. Please clarify. |
Electrical | 09/13/2021 | Rejected | Based on the lack of information provided, additional design information is required for the county to review for code compliance. Additional comments may be forthcoming. Section 109.3 of the Virginia Construction Code. |
Electrical | 09/13/2021 | Approved | Indicate on the drawings the 'type' of grounding electrode(s) to be used to properly ground the re-located 45kva transformer. NEC Article 250.30 (A) (4). Refer to Note 3, under the 'Key Notes' shown on sheet E3.01. Also, Section 109.3 of the Virginia Construction Code. |
Electrical | 09/13/2021 | Approved | On sheet E3.01, 'Key Note' #6 references an existing 60 ampere disconnect to be removed. However, Key Note #6 appears to be an electrical transformer. Please clarify. |
Electrical | 09/13/2021 | Approved | Based on the lack of information provided, additional design information is required for the county to review for code compliance. Additional comments may be forthcoming. Section 109.3 of the Virginia Construction Code. |
Electrical | 09/13/2021 | Additional | Indicate on the drawings the 'type' of grounding electrode(s) to be used to properly ground the re-located 45kva transformer. NEC Article 250.30 (A) (4). Refer to Note 3, under the 'Key Notes' shown on sheet E3.01. Also, Section 109.3 of the Virginia Construction Code. |
Electrical | 09/13/2021 | Additional | On sheet E3.01, 'Key Note' #6 references an existing 60 ampere disconnect to be removed. However, Key Note #6 appears to be an electrical transformer. Please clarify. |
Electrical | 09/13/2021 | Additional | Based on the lack of information provided, additional design information is required for the county to review for code compliance. Additional comments may be forthcoming. Section 109.3 of the Virginia Construction Code. |
Electrical | 10/29/2021 | Approved | In this latest review cycle dated (10-15-2021), there appears to be a 'new' 75kva transformer, provided by the landlord, shown to be suspended from the structure. Therefore, the designer will need to provide a 'Transformer Mounting Detail' on the drawings. Refer to 'Key Note' number 5, shown on revised sheet E3.01. Section 109.3 of the Virginia Construction Code. |
Electrical | 10/29/2021 | Approved | The #8 copper conductor shown to ground the 'new' 75kva transformer is too small. Transformer grounding electrode conductors 'must' be properly sized per NEC Article 250.30 (A) (5), and NEC Table 250.66. Refer to 'Key Note' number 5, shown on the revised electrical riser diagram. See sheet E3.01. Clarify. |
Electrical | 10/29/2021 | Approved | Indicate on the drawings the type(s) of grounding electrode(s) to be used to properly ground the 'new' 75kva transformer shown on revised sheet E3.01. NEC Article 250.30 (A) (4). Section 109.3 of the Virginia Construction Code. |
Electrical | 10/29/2021 | Approved | Please indicate on the drawings whether the 'new' 75kva (T-LA) transformer, suspended from the structure, will be located 'above or below' the ceiling in 'Corridor 14'. Refer to revised sheet E2.02. NEC Article 450.13 (B). Section 109.3 of the Virginia Construction Code. |
Electrical | 10/29/2021 | Approved | There appears to be mechanical duct work located above electrical panel board 'LB' located in 'IT Room 11'. Relocate either. Refer to revised sheets E2.02 and M2.01. NEC Article 110.26 (E) (1) (a). Section 109.3 of the Virginia Construction Code. |
Electrical | 10/29/2021 | Approved | On newly revised sheet E3.01, 'Note 8' under 'Key Notes', indicates the use of 125 ampere fuses in this disconnect. However, panel board 'HA', which is located on the load side of this fused disconnect has a demand ampere load of 160. Please clarify. Refer to the 'HA' directory and electrical riser diagram shown on this sheet. NEC Article 110.3 (B). Section 109.3 of the Virginia Construction Code. |
Electrical | 10/29/2021 | Approved | Based on the lack of information provide, the above comments may not constitute a complete list of requested information. Additional design information is required for the county to review for code compliance. Section 109.3 of the Virginia Construction Code. |
Electrical | 10/29/2021 | Rejected | In this latest review cycle dated (10-15-2021), there appears to be a 'new' 75kva transformer, provided by the landlord, shown to be suspended from the structure. Therefore, the designer will need to provide a 'Transformer Mounting Detail' on the drawings. Refer to 'Key Note' number 5, shown on revised sheet E3.01. Section 109.3 of the Virginia Construction Code. |
Electrical | 10/29/2021 | Rejected | The #8 copper conductor shown to ground the 'new' 75kva transformer is too small. Transformer grounding electrode conductors 'must' be properly sized per NEC Article 250.30 (A) (5), and NEC Table 250.66. Refer to 'Key Note' number 5, shown on the revised electrical riser diagram. See sheet E3.01. Clarify. |
Electrical | 10/29/2021 | Rejected | Indicate on the drawings the type(s) of grounding electrode(s) to be used to properly ground the 'new' 75kva transformer shown on revised sheet E3.01. NEC Article 250.30 (A) (4). Section 109.3 of the Virginia Construction Code. |
Electrical | 10/29/2021 | Rejected | Please indicate on the drawings whether the 'new' 75kva (T-LA) transformer, suspended from the structure, will be located 'above or below' the ceiling in 'Corridor 14'. Refer to revised sheet E2.02. NEC Article 450.13 (B). Section 109.3 of the Virginia Construction Code. |
Electrical | 10/29/2021 | Rejected | There appears to be mechanical duct work located above electrical panel board 'LB' located in 'IT Room 11'. Relocate either. Refer to revised sheets E2.02 and M2.01. NEC Article 110.26 (E) (1) (a). Section 109.3 of the Virginia Construction Code. |
Electrical | 10/29/2021 | Rejected | On newly revised sheet E3.01, 'Note 8' under 'Key Notes', indicates the use of 125 ampere fuses in this disconnect. However, panel board 'HA', which is located on the load side of this fused disconnect has a demand ampere load of 160. Please clarify. Refer to the 'HA' directory and electrical riser diagram shown on this sheet. NEC Article 110.3 (B). Section 109.3 of the Virginia Construction Code. |
Electrical | 10/29/2021 | Rejected | Based on the lack of information provide, the above comments may not constitute a complete list of requested information. Additional design information is required for the county to review for code compliance. Section 109.3 of the Virginia Construction Code. |
EPlan Review | 12/17/2021 | Approved | |
Mechanical | 10/11/2021 | Approved | Sheet M2-01 - MECHANICAL -FLOOR PLAN: Drawings M2.01 and M3.01 dated 8/26/2021 must be deleted (duplicate drawings) and M2.01 and M3.01 dated 10/8/2021 will stay. |
Mechanical | 10/11/2021 | Rejected | Sheet M2-01 - MECHANICAL -FLOOR PLAN: Drawings M2.01 and M3.01 dated 8/26/2021 must be deleted (duplicate drawings) and M2.01 and M3.01 dated 10/8/2021 will stay. |
Plumbing | 08/30/2021 | Rejected | Review Date: 8/27/21
VPC 410.3 Provide high and low drinking fountains.
Where drinking fountains are required, not fewer than two drinking fountains shall be provided. One drinking fountain shall comply with the requirements for people who use a wheelchair and one drinking fountain shall comply with the requirements for standing persons. |
Plumbing | 08/30/2021 | Approved | Review Date: 8/27/21
VPC 410.3 Provide high and low drinking fountains.
Where drinking fountains are required, not fewer than two drinking fountains shall be provided. One drinking fountain shall comply with the requirements for people who use a wheelchair and one drinking fountain shall comply with the requirements for standing persons. |
Plumbing | 08/30/2021 | Additional | Review Date: 8/27/21
VPC 410.3 Provide high and low drinking fountains.
Where drinking fountains are required, not fewer than two drinking fountains shall be provided. One drinking fountain shall comply with the requirements for people who use a wheelchair and one drinking fountain shall comply with the requirements for standing persons. |
Plumbing | 08/30/2021 | Approved | Review Date: 8/27/21
VPC 410.3 Provide high and low drinking fountains.
Where drinking fountains are required, not fewer than two drinking fountains shall be provided. One drinking fountain shall comply with the requirements for people who use a wheelchair and one drinking fountain shall comply with the requirements for standing persons. |
Zoning | 09/15/2021 | Rejected | it looks like this space's storefront faces the muse, therefore any storefront modification must first be approved through an administrative change request.
Application and process can be found on Building Arlington ; link attached here:
https://building.arlingtonva.us/permits/admin-change/
Contact Rosa Achour at 228-7579 or rachour@arlingtonva.us. for questions if any.
|
Zoning | 09/15/2021 | Rejected | please provide a key plan showing the location of the space within the mall. |
Zoning | 09/15/2021 | Rejected | it looks like this space's storefront faces the muse, therefore any storefront modification must first be approved through an administrative change request.
Application and process can be found on Building Arlington ; link attached here:
https://building.arlingtonva.us/permits/admin-change/
Contact Rosa Achour at 228-7579 or rachour@arlingtonva.us. for questions if any.
|
Zoning | 09/15/2021 | Rejected | please provide a key plan showing the location of the space within the mall. |
Zoning | 09/15/2021 | Additional | it looks like this space's storefront faces the muse, therefore any storefront modification must first be approved through an administrative change request.
Application and process can be found on Building Arlington ; link attached here:
https://building.arlingtonva.us/permits/admin-change/
Contact Rosa Achour at 228-7579 or rachour@arlingtonva.us. for questions if any.
|
Zoning | 09/15/2021 | Additional | please provide a key plan showing the location of the space within the mall. |
Zoning | 09/15/2021 | Approved | it looks like this space's storefront faces the muse, therefore any storefront modification must first be approved through an administrative change request.
Application and process can be found on Building Arlington ; link attached here:
https://building.arlingtonva.us/permits/admin-change/
Contact Rosa Achour at 228-7579 or rachour@arlingtonva.us. for questions if any. |
Zoning | 09/15/2021 | Approved | please provide a key plan showing the location of the space within the mall. |
Zoning | 09/16/2021 | Approved | Per article 7.1.2 (principal uses allowed in C districts) a game Arcade requires a Board Approved use permit on sites that are controlled by a site plan. |
Zoning | 09/16/2021 | Additional | Per article 7.1.2 (principal uses allowed in C districts) a game Arcade requires a Board Approved use permit on sites that are controlled by a site plan. |
Zoning | 09/16/2021 | Rejected | Per article 7.1.2 (principal uses allowed in C districts) a game Arcade requires a Board Approved use permit on sites that are controlled by a site plan. |
Zoning | 09/16/2021 | Rejected | Per article 7.1.2 (principal uses allowed in C districts) a game Arcade requires a Board Approved use permit on sites that are controlled by a site plan. |