Permit Comments
 
Permit #B2200196
Address4710 LANGSTON BLVD
TypeCTBO
StatusAPPLIED
Permit HolderCONTRACTOR TBD
OwnerJAMES WILSON CONSTITUTIONAL SOCIETY LLC
Applied Date01/02/2022
Approved Date 
Date Issued 
DescriptionNEW TENANT BUILD OUT FOR COFFEE CAFE, INTERIOR DEMO, NEW MECHANICAL, PLUMBING, ELECTRICAL, COFFEE EQUIPMENT, FIXTURES, AND FURNITURE. CHANGE OF USE FROM B TO A-2.

ReviewReview DateStatusComments
Building02/09/2022ApprovedSheet A104-1 SITE AND INTERIOR PLANS: What is slope of existing ramp? If over 1:20 handrails are required on both sides. (Plan shows just one side). Edge protection required
Building02/09/2022ApprovedSheet A107 FRAMING PLAN: Elevation of front door does not match what is shown on the door/ hardware schedule. Refer to A117.1, Section 404.2.9 - 10" h bottom rail required on push side of door
Building02/09/2022ApprovedSheet A107 FRAMING PLAN: see cloud on plan. 44" clear path required to 2nd required exit. In addition, refer to A117.1, Section 404.2.3 - Maneuvering clearance is not met at doors in this reduced width corridor
Building02/09/2022ApprovedSheet A107 FRAMING PLAN: New exterior door is added to the back of establishment. Provide detail with header information to show framing for new exterior opening
Building02/09/2022ApprovedSheet A107 FRAMING PLAN: Refer to Section 2406.4.2 - Safety glazing is required at windows adjacent to new door
Building02/09/2022ApprovedSheet A014 ADA PLAN: include accessible parking and exterior existing ramp on plan to show the accessible route. Include the accessible parking dimensions and access aisle dimension. Accessible parking to comply with Section 1106.8 for identification requirements and A117.1, section 502 for sizing
Building02/09/2022ApprovedSheet A104-1 SITE AND INTERIOR PLANS: What is slope of existing ramp? If over 1:20 handrails are required on both sides. (Plan shows just one side). Edge protection required
Building02/09/2022ApprovedSheet A107 FRAMING PLAN: Elevation of front door does not match what is shown on the door/ hardware schedule. Refer to A117.1, Section 404.2.9 - 10" h bottom rail required on push side of door
Building02/09/2022ApprovedSheet A107 FRAMING PLAN: see cloud on plan. 44" clear path required to 2nd required exit. In addition, refer to A117.1, Section 404.2.3 - Maneuvering clearance is not met at doors in this reduced width corridor
Building02/09/2022ApprovedSheet A107 FRAMING PLAN: New exterior door is added to the back of establishment. Provide detail with header information to show framing for new exterior opening
Building02/09/2022ApprovedSheet A107 FRAMING PLAN: Refer to Section 2406.4.2 - Safety glazing is required at windows adjacent to new door
Building02/09/2022ApprovedSheet A014 ADA PLAN: include accessible parking and exterior existing ramp on plan to show the accessible route. Include the accessible parking dimensions and access aisle dimension. Accessible parking to comply with Section 1106.8 for identification requirements and A117.1, section 502 for sizing
Building02/09/2022RejectedSheet A106 DOOR AND WALL TYPES: Refer to Section 603 and Section 803.13. Building construction type shown as 2B construction. Non combustible or FRT required for underlayment/sheathing on partitions.
Building02/09/2022RejectedSheet A106 DOOR AND WALL TYPES: Refer to Section 1010.1.1. Min 32" clear door opening required measured door face to jamb. Both restroom doors (type 1)scheduled as 30" wide. In addition, BOH door (type 2) is a double door with 2 - 1'-6" leaves. One leaf in a pair is required to meet the 32" clearance requirement.
Building02/09/2022RejectedSheet A107 FRAMING PLAN: see cloud on plan. 44" clear path required to 2nd required exit. In addition, refer to A117.1, Section 404.2.3 - Maneuvering clearance is not met at doors in this reduced width corridor
Building02/09/2022RejectedSheet A107 FRAMING PLAN: New exterior door is added to the back of establishment. Provide detail with header information to show framing for new exterior opening
Building02/09/2022RejectedSheet A107 FRAMING PLAN: Refer to Section 2406.4.2 - Safety glazing is required at windows adjacent to new door
Building02/09/2022RejectedSheet A014 ADA PLAN: include accessible parking and exterior existing ramp on plan to show the accessible route. Include the accessible parking dimensions and access aisle dimension. Accessible parking to comply with Section 1106.8 for identification requirements and A117.1, section 502 for sizing
Building02/09/2022RejectedSheet A104-1 SITE AND INTERIOR PLANS: Stair to new door is new. Provide framing/ structural information and details to show compliance. Provide dimensions for stair and landing (landing does not appear compliant). Comply with Section 1011. Handrails and guard (if required) to Comply with Sections 1014 and 1015, including handrail extensions
Building02/09/2022RejectedSheet A104-1 SITE AND INTERIOR PLANS: What is slope of existing ramp? If over 1:20 handrails are required on both sides. (Plan shows just one side). Edge protection required
Building02/09/2022RejectedSheet A107 FRAMING PLAN: Elevation of front door does not match what is shown on the door/ hardware schedule. Refer to A117.1, Section 404.2.9 - 10" h bottom rail required on push side of door
Building02/09/2022ApprovedSheet A104-1 SITE AND INTERIOR PLANS: What is slope of existing ramp? If over 1:20 handrails are required on both sides. (Plan shows just one side). Edge protection required
Building02/09/2022ApprovedSheet A107 FRAMING PLAN: Elevation of front door does not match what is shown on the door/ hardware schedule. Refer to A117.1, Section 404.2.9 - 10" h bottom rail required on push side of door
Building02/09/2022ApprovedSheet A107 FRAMING PLAN: see cloud on plan. 44" clear path required to 2nd required exit. In addition, refer to A117.1, Section 404.2.3 - Maneuvering clearance is not met at doors in this reduced width corridor
Building02/09/2022ApprovedSheet A107 FRAMING PLAN: New exterior door is added to the back of establishment. Provide detail with header information to show framing for new exterior opening
Building02/09/2022ApprovedSheet A107 FRAMING PLAN: Refer to Section 2406.4.2 - Safety glazing is required at windows adjacent to new door
Building02/09/2022ApprovedSheet A014 ADA PLAN: include accessible parking and exterior existing ramp on plan to show the accessible route. Include the accessible parking dimensions and access aisle dimension. Accessible parking to comply with Section 1106.8 for identification requirements and A117.1, section 502 for sizing
Building02/09/2022RejectedSheet A107 FRAMING PLAN: see cloud on plan. 44" clear path required to 2nd required exit. In addition, refer to A117.1, Section 404.2.3 - Maneuvering clearance is not met at doors in this reduced width corridor
Building02/09/2022RejectedSheet A107 FRAMING PLAN: New exterior door is added to the back of establishment. Provide detail with header information to show framing for new exterior opening
Building02/09/2022RejectedSheet A107 FRAMING PLAN: Refer to Section 2406.4.2 - Safety glazing is required at windows adjacent to new door
Building02/09/2022RejectedSheet A014 ADA PLAN: include accessible parking and exterior existing ramp on plan to show the accessible route. Include the accessible parking dimensions and access aisle dimension. Accessible parking to comply with Section 1106.8 for identification requirements and A117.1, section 502 for sizing
Building02/09/2022RejectedSheet A104-1 SITE AND INTERIOR PLANS: What is slope of existing ramp? If over 1:20 handrails are required on both sides. (Plan shows just one side). Edge protection required
Building02/09/2022RejectedSheet A107 FRAMING PLAN: Elevation of front door does not match what is shown on the door/ hardware schedule. Refer to A117.1, Section 404.2.9 - 10" h bottom rail required on push side of door
Building03/11/2022RejectedSheet A400 RESTROOM PLAN: Door approach from inside ADA WC is not adequate if door has a closer. I don't see a closer specified on current door hardware., but it is typically added when a door is spec'd with push/ pull hardware. Please coordinate and confirm
Building03/11/2022RejectedSheet A106 DOOR AND WALL TYPES: Door 3 is marked as exit only on plans. No operating hardware is permitted on exterior if this door is required to be exit only
Building03/11/2022RejectedSheet A003 LIFE SAFETY: Refer to Section 1011.2 - Stair to be min. 44" wide.
Building03/11/2022RejectedSheet A106 DOOR AND WALL TYPES: Refer to Section 603 and Section 803.13. Building construction type shown as 2B construction. Non combustible or FRT required for underlayment/sheathing on partitions. ****************03/11/22 - Narrative states change was made to this sheet, but this sheet has not been updated. Comment remains
Building03/11/2022RejectedSheet A106 DOOR AND WALL TYPES: Refer to Section 1010.1.1. Min 32" clear door opening required measured door face to jamb. Both restroom doors (type 1)scheduled as 30" wide. In addition, BOH door (type 2) is a double door with 2 - 1'-6" leaves. One leaf in a pair is required to meet the 32" clearance requirement. ***************03/11/22 - Narrative states revision change, but no change has been made to this sheet. Comment remains
Building03/11/2022RejectedSheet A104-1 SITE AND INTERIOR PLANS: Stair to new door is new. Provide framing/ structural information and details to show compliance. Provide dimensions for stair and landing (landing does not appear compliant). Comply with Section 1011. Handrails and guard (if required) to Comply with Sections 1014 and 1015, including handrail extensions *******************03/11/22 - New structural and architectural information does not give stair geometry including rise and run. This needs to be represented on drawings. While not indicated on plans, the landing appears to be over 30" requiring a guard per Section 1015 is required
Building03/11/2022ApprovedSheet A104-1 SITE AND INTERIOR PLANS: Stair to new door is new. Provide framing/ structural information and details to show compliance. Provide dimensions for stair and landing (landing does not appear compliant). Comply with Section 1011. Handrails and guard (if required) to Comply with Sections 1014 and 1015, including handrail extensions *******************03/11/22 - New structural and architectural information does not give stair geometry including rise and run. This needs to be represented on drawings. While not indicated on plans, the landing appears to be over 30" requiring a guard per Section 1015 is required
Building03/11/2022ApprovedSheet A106 DOOR AND WALL TYPES: Refer to Section 603 and Section 803.13. Building construction type shown as 2B construction. Non combustible or FRT required for underlayment/sheathing on partitions. ****************03/11/22 - Narrative states change was made to this sheet, but this sheet has not been updated. Comment remains
Building03/11/2022ApprovedSheet A106 DOOR AND WALL TYPES: Refer to Section 1010.1.1. Min 32" clear door opening required measured door face to jamb. Both restroom doors (type 1)scheduled as 30" wide. In addition, BOH door (type 2) is a double door with 2 - 1'-6" leaves. One leaf in a pair is required to meet the 32" clearance requirement. ***************03/11/22 - Narrative states revision change, but no change has been made to this sheet. Comment remains
Building03/11/2022ApprovedSheet A400 RESTROOM PLAN: Door approach from inside ADA WC is not adequate if door has a closer. I don't see a closer specified on current door hardware., but it is typically added when a door is spec'd with push/ pull hardware. Please coordinate and confirm
Building03/11/2022ApprovedSheet A106 DOOR AND WALL TYPES: Door 3 is marked as exit only on plans. No operating hardware is permitted on exterior if this door is required to be exit only
Building03/11/2022ApprovedSheet A003 LIFE SAFETY: Refer to Section 1011.2 - Stair to be min. 44" wide.
Building03/11/2022ApprovedSheet A104-1 SITE AND INTERIOR PLANS: Stair to new door is new. Provide framing/ structural information and details to show compliance. Provide dimensions for stair and landing (landing does not appear compliant). Comply with Section 1011. Handrails and guard (if required) to Comply with Sections 1014 and 1015, including handrail extensions *******************03/11/22 - New structural and architectural information does not give stair geometry including rise and run. This needs to be represented on drawings. While not indicated on plans, the landing appears to be over 30" requiring a guard per Section 1015 is required
Building03/11/2022ApprovedSheet A106 DOOR AND WALL TYPES: Refer to Section 603 and Section 803.13. Building construction type shown as 2B construction. Non combustible or FRT required for underlayment/sheathing on partitions. ****************03/11/22 - Narrative states change was made to this sheet, but this sheet has not been updated. Comment remains
Building03/11/2022ApprovedSheet A106 DOOR AND WALL TYPES: Refer to Section 1010.1.1. Min 32" clear door opening required measured door face to jamb. Both restroom doors (type 1)scheduled as 30" wide. In addition, BOH door (type 2) is a double door with 2 - 1'-6" leaves. One leaf in a pair is required to meet the 32" clearance requirement. ***************03/11/22 - Narrative states revision change, but no change has been made to this sheet. Comment remains
Building03/11/2022ApprovedSheet A400 RESTROOM PLAN: Door approach from inside ADA WC is not adequate if door has a closer. I don't see a closer specified on current door hardware., but it is typically added when a door is spec'd with push/ pull hardware. Please coordinate and confirm
Building03/11/2022ApprovedSheet A106 DOOR AND WALL TYPES: Door 3 is marked as exit only on plans. No operating hardware is permitted on exterior if this door is required to be exit only
Building03/11/2022ApprovedSheet A003 LIFE SAFETY: Refer to Section 1011.2 - Stair to be min. 44" wide.
Building03/11/2022ApprovedSheet A104-1 SITE AND INTERIOR PLANS: Stair to new door is new. Provide framing/ structural information and details to show compliance. Provide dimensions for stair and landing (landing does not appear compliant). Comply with Section 1011. Handrails and guard (if required) to Comply with Sections 1014 and 1015, including handrail extensions *******************03/11/22 - New structural and architectural information does not give stair geometry including rise and run. This needs to be represented on drawings. While not indicated on plans, the landing appears to be over 30" requiring a guard per Section 1015 is required
Building03/11/2022ApprovedSheet A400 RESTROOM PLAN: Door approach from inside ADA WC is not adequate if door has a closer. I don't see a closer specified on current door hardware., but it is typically added when a door is spec'd with push/ pull hardware. Please coordinate and confirm
Building03/11/2022ApprovedSheet A106 DOOR AND WALL TYPES: Door 3 is marked as exit only on plans. No operating hardware is permitted on exterior if this door is required to be exit only
Building03/11/2022ApprovedSheet A003 LIFE SAFETY: Refer to Section 1011.2 - Stair to be min. 44" wide.
Building03/11/2022ApprovedSheet A106 DOOR AND WALL TYPES: Refer to Section 603 and Section 803.13. Building construction type shown as 2B construction. Non combustible or FRT required for underlayment/sheathing on partitions. ****************03/11/22 - Narrative states change was made to this sheet, but this sheet has not been updated. Comment remains
Building03/11/2022ApprovedSheet A106 DOOR AND WALL TYPES: Refer to Section 1010.1.1. Min 32" clear door opening required measured door face to jamb. Both restroom doors (type 1)scheduled as 30" wide. In addition, BOH door (type 2) is a double door with 2 - 1'-6" leaves. One leaf in a pair is required to meet the 32" clearance requirement. ***************03/11/22 - Narrative states revision change, but no change has been made to this sheet. Comment remains
Building04/14/2022ApprovedSheet A106 DOOR AND WALL TYPES: DEADBOLTS AT RESTROOM DOORS TO HAVE ELONGATED (ACCESSIBLE) THUMBTURNS
Building04/14/2022ApprovedSheet A106 DOOR AND WALL TYPES: REFER TO A117.1, SECTION 404.2.10. VISION PANELS ON DOORS TO BE 43" AFF MAX TO BOTTOM OF PANEL
Building04/14/2022ApprovedSheet 00 CERTIFICATE OF OCCUPANCY APPLICATION: CERTIFICATE FOR OCCUPANCY APPLICATION IS NOT APPLIED THROUGH THE BUILDING PERMIT. A SEPARATE SUBMISSION IS REQUIRED
Building04/14/2022ApprovedSheet A000 COVER SHEET: SUBMIT FIRE ALARM SHOP DRAWINGS FOR APPROVAL
Building04/14/2022ApprovedSheet A106 DOOR AND WALL TYPES: DEADBOLTS AT RESTROOM DOORS TO HAVE ELONGATED (ACCESSIBLE) THUMBTURNS
Building04/14/2022ApprovedSheet A106 DOOR AND WALL TYPES: REFER TO A117.1, SECTION 404.2.10. VISION PANELS ON DOORS TO BE 43" AFF MAX TO BOTTOM OF PANEL
Building04/14/2022ApprovedSheet 00 CERTIFICATE OF OCCUPANCY APPLICATION: CERTIFICATE FOR OCCUPANCY APPLICATION IS NOT APPLIED THROUGH THE BUILDING PERMIT. A SEPARATE SUBMISSION IS REQUIRED
Building04/14/2022ApprovedSheet A000 COVER SHEET: SUBMIT FIRE ALARM SHOP DRAWINGS FOR APPROVAL
Building04/14/2022ApprovedSheet A106 DOOR AND WALL TYPES: DEADBOLTS AT RESTROOM DOORS TO HAVE ELONGATED (ACCESSIBLE) THUMBTURNS
Building04/14/2022ApprovedSheet A106 DOOR AND WALL TYPES: REFER TO A117.1, SECTION 404.2.10. VISION PANELS ON DOORS TO BE 43" AFF MAX TO BOTTOM OF PANEL
Building04/14/2022ApprovedSheet 00 CERTIFICATE OF OCCUPANCY APPLICATION: CERTIFICATE FOR OCCUPANCY APPLICATION IS NOT APPLIED THROUGH THE BUILDING PERMIT. A SEPARATE SUBMISSION IS REQUIRED
Building04/14/2022ApprovedSheet A000 COVER SHEET: SUBMIT FIRE ALARM SHOP DRAWINGS FOR APPROVAL
Building05/25/2022ApprovedPlan review cycle ended and plans returned at submitter's request to add new revision..
Building05/25/2022ApprovedPlan review cycle ended and plans returned at submitter's request to add new revision..
DES:Water/Sewer Engineering05/19/2022ApprovedCOMMERCIAL INT ALT. 9.50 NEW DFU'S. APPROVED
Energy02/16/2022RejectedSheet A001 ZONING AND BUILDING INFO: EN-1) 02/16/22: NOT USED.
Energy02/16/2022RejectedSheet A104 FLOOR PLAN: EN-2) 02/16/22 - Label the new door with an identification tag, for purposes of addressing the energy criteria associated with new fenestration.
Energy02/16/2022RejectedSheet A106 DOOR AND WALL TYPES: EN-03) 02/16/22 : New doors and new windows/storefront/curtainwall glazing in the building thermal envelope shall meet the energy code requirements for all three of these metrics: A) the Air Infiltration Rate (whether glazed or opaque), B) the U-factor (whether glazed or opaque) and C) SHGC value (if glazed). Reference Tables C402.1.4, C402.4, C402.5.2. Per Existing Building Code 601.4. State ON THE DRAWINGS the numeric values for your specific fenestration types on the drawings. Citing only the code section numbers will not be sufficient to comply with the code.
Energy02/16/2022RejectedSheet E101 RCP: EN-4) 02/16/22 COMCHECK – The incorrect space type has been entered into comcheck to determine the allowed wattage. You have opted to use the space by space method from Table C405.3.2(2). Each space’s function must be assigned the most closely matched category available. Café seating and dining would be Dining Area, and would be either lounge/bar or fast food, but NOT retail. The Bathroom would fall under Restroom NOT retail, the BOH needs to be separated in to Storage (former vault) and Food Prep Area, but NOT retail. Revise and resubmit.
Energy02/16/2022RejectedSheet E101 RCP: EN-5) 02/16/22 Lighting Controls – Provide the required occupancy sensors per C405.2.1, in the storage room. Revise and resubmit.
Energy02/16/2022RejectedSheet E101 RCP: EN-6) 02/16/22 Lighting Controls – Provide the required manual controls light reduction for the areas that are NOT in a daylighting zone and that are NOT controlled by an occupancy sensor, per C405.2.2.1 and C405.2.2.2. Revise and resubmit.
Energy02/16/2022RejectedSheet M104 MECHANICAL SCHEDULES: EN-07) 02/16/22 - On the rooftop unit schedule, in addition to the EER listed for the new unit, list the IEER, to comply with Table C403.3.2(1).
Energy02/16/2022RejectedSheet P600 PLUMBING DETAILS: EN-08) 02/16/22 - Provide ON THE DRAWINGS a schedule of the gas tankless water heater. Include its size, andits minimum required efficiency from Tab;e C404.2.
Energy02/16/2022RejectedEN-09) 02/16/22: Resubmission may result in additional comments. Please number your narrative responses with the identical EN-X number indicated in my comments. This significantly reduces the time required for review of your responses. Per VECC 109.4. If you have questions regarding this energy code review, you can contact me via email at lbaskerville@arlingtonva.us, or call on my mobile number 703-244-0479. The Virginia Energy Conservation Code can be found free online at https://codes.iccsafe.org/content/VECC2018P1
Energy03/22/2022ApprovedSheet P600 PLUMBING DETAILS: EN-08) 02/16/22 - Provide ON THE DRAWINGS a schedule of the gas tankless water heater. Include its size, and its minimum required efficiency from Tab;e C404.2.
Energy03/22/2022ApprovedSheet A001 ZONING AND BUILDING INFO: EN-1) EN-1) 03/22/22 – Current code year cycle is 2018, with the option to use 2015 until June 30, 2022. Your code summary indicates 2012. For Energy Code compliance purposes, you need to state in your code summary section whether you are following VECC or ASHRAE 90.1, and which year. Revise and resubmit. Per VCC section 101.2.*******************************02/16/22: NOT USED.
Energy03/22/2022ApprovedSheet A104 FLOOR PLAN: EN-2) 03/22/22: The previous comment had not been addressed. Please address the energy code rejection comment. ************************************************************************************02/16/22 - Label the new door with an identification tag, for purposes of addressing the energy criteria associated with new fenestration.
Energy03/22/2022ApprovedSheet A106 DOOR AND WALL TYPES: EN-03) 03/22/22: The previous comment had not been addressed. Please address the energy code rejection comment. ************************************************************************************02/16/22 : New doors and new windows/storefront/curtainwall glazing in the building thermal envelope shall meet the energy code requirements for all three of these metrics: A) the Air Infiltration Rate (whether glazed or opaque), B) the U-factor (whether glazed or opaque) and C) SHGC value (if glazed). Reference Tables C402.1.4, C402.4, C402.5.2. Per Existing Building Code 601.4. State ON THE DRAWINGS the numeric values for your specific fenestration types on the drawings. Citing only the code section numbe
Energy03/22/2022ApprovedSheet E101 RCP: EN-4) 03/22/22: The previous comment had not been addressed. Please address the energy code rejection comment. ************************************************************************************02/16/22 COMCHECK – The incorrect space type has been entered into comcheck to determine the allowed wattage. You have opted to use the space by space method from Table C405.3.2(2). Each space’s function must be assigned the most closely matched category available. Café seating and dining would be Dining Area, and would be either lounge/bar or fast food, but NOT retail. The Bathroom would fall under Restroom NOT retail, the BOH needs to be separated in to Storage (former vault) and Food Prep Area, but NOT retail. Revise and
Energy03/22/2022ApprovedSheet E101 RCP: EN-5) 03/22/22: The previous comment had not been addressed. Please address the energy code rejection comment. ************************************************************************************02/16/22 Lighting Controls – Provide the required occupancy sensors per C405.2.1, in the storage room. Revise and resubmit.
Energy03/22/2022ApprovedSheet E101 RCP: EN-6) 03/22/22: The previous comment had not been addressed. Please address the energy code rejection comment. ************************************************************************************02/16/22 Lighting Controls – Provide the required manual controls light reduction for the areas that are NOT in a daylighting zone and that are NOT controlled by an occupancy sensor, per C405.2.2.1 and C405.2.2.2. Revise and resubmit.
Energy03/22/2022ApprovedSheet A001 ZONING AND BUILDING INFO: EN-1) EN-1) 03/22/22 – Current code year cycle is 2018, with the option to use 2015 until June 30, 2022. Your code summary indicates 2012. For Energy Code compliance purposes, you need to state in your code summary section whether you are following VECC or ASHRAE 90.1, and which year. Revise and resubmit. Per VCC section 101.2.*******************************02/16/22: NOT USED.
Energy03/22/2022ApprovedSheet A104 FLOOR PLAN: EN-2) 03/22/22: The previous comment had not been addressed. Please address the energy code rejection comment. ************************************************************************************02/16/22 - Label the new door with an identification tag, for purposes of addressing the energy criteria associated with new fenestration.
Energy03/22/2022ApprovedSheet A106 DOOR AND WALL TYPES: EN-03) 03/22/22: The previous comment had not been addressed. Please address the energy code rejection comment. ************************************************************************************02/16/22 : New doors and new windows/storefront/curtainwall glazing in the building thermal envelope shall meet the energy code requirements for all three of these metrics: A) the Air Infiltration Rate (whether glazed or opaque), B) the U-factor (whether glazed or opaque) and C) SHGC value (if glazed). Reference Tables C402.1.4, C402.4, C402.5.2. Per Existing Building Code 601.4. State ON THE DRAWINGS the numeric values for your specific fenestration types on the drawings. Citing only the code section numbe
Energy03/22/2022ApprovedSheet E101 RCP: EN-4) 03/22/22: The previous comment had not been addressed. Please address the energy code rejection comment. ************************************************************************************02/16/22 COMCHECK – The incorrect space type has been entered into comcheck to determine the allowed wattage. You have opted to use the space by space method from Table C405.3.2(2). Each space’s function must be assigned the most closely matched category available. Café seating and dining would be Dining Area, and would be either lounge/bar or fast food, but NOT retail. The Bathroom would fall under Restroom NOT retail, the BOH needs to be separated in to Storage (former vault) and Food Prep Area, but NOT retail. Revise and
Energy03/22/2022ApprovedSheet E101 RCP: EN-5) 03/22/22: The previous comment had not been addressed. Please address the energy code rejection comment. ************************************************************************************02/16/22 Lighting Controls – Provide the required occupancy sensors per C405.2.1, in the storage room. Revise and resubmit.
Energy03/22/2022ApprovedSheet E101 RCP: EN-6) 03/22/22: The previous comment had not been addressed. Please address the energy code rejection comment. ************************************************************************************02/16/22 Lighting Controls – Provide the required manual controls light reduction for the areas that are NOT in a daylighting zone and that are NOT controlled by an occupancy sensor, per C405.2.2.1 and C405.2.2.2. Revise and resubmit.
Energy03/22/2022RejectedSheet A001 ZONING AND BUILDING INFO: EN-1) EN-1) 03/22/22 – Current code year cycle is 2018, with the option to use 2015 until June 30, 2022. Your code summary indicates 2012. For Energy Code compliance purposes, you need to state in your code summary section whether you are following VECC or ASHRAE 90.1, and which year. Revise and resubmit. Per VCC section 101.2.*******************************02/16/22: NOT USED.
Energy03/22/2022RejectedSheet A104 FLOOR PLAN: EN-2) 03/22/22: The previous comment had not been addressed. Please address the energy code rejection comment. ************************************************************************************02/16/22 - Label the new door with an identification tag, for purposes of addressing the energy criteria associated with new fenestration.
Energy03/22/2022RejectedSheet A106 DOOR AND WALL TYPES: EN-03) 03/22/22: The previous comment had not been addressed. Please address the energy code rejection comment. ************************************************************************************02/16/22 : New doors and new windows/storefront/curtainwall glazing in the building thermal envelope shall meet the energy code requirements for all three of these metrics: A) the Air Infiltration Rate (whether glazed or opaque), B) the U-factor (whether glazed or opaque) and C) SHGC value (if glazed). Reference Tables C402.1.4, C402.4, C402.5.2. Per Existing Building Code 601.4. State ON THE DRAWINGS the numeric values for your specific fenestration types on the drawings. Citing only the code section numbe
Energy03/22/2022RejectedSheet E101 RCP: EN-4) 03/22/22: The previous comment had not been addressed. Please address the energy code rejection comment. ************************************************************************************02/16/22 COMCHECK – The incorrect space type has been entered into comcheck to determine the allowed wattage. You have opted to use the space by space method from Table C405.3.2(2). Each space’s function must be assigned the most closely matched category available. Café seating and dining would be Dining Area, and would be either lounge/bar or fast food, but NOT retail. The Bathroom would fall under Restroom NOT retail, the BOH needs to be separated in to Storage (former vault) and Food Prep Area, but NOT retail. Revise and
Energy03/22/2022RejectedSheet E101 RCP: EN-5) 03/22/22: The previous comment had not been addressed. Please address the energy code rejection comment. ************************************************************************************02/16/22 Lighting Controls – Provide the required occupancy sensors per C405.2.1, in the storage room. Revise and resubmit.
Energy03/22/2022RejectedSheet E101 RCP: EN-6) 03/22/22: The previous comment had not been addressed. Please address the energy code rejection comment. ************************************************************************************02/16/22 Lighting Controls – Provide the required manual controls light reduction for the areas that are NOT in a daylighting zone and that are NOT controlled by an occupancy sensor, per C405.2.2.1 and C405.2.2.2. Revise and resubmit.
Energy03/22/2022RejectedSheet M104 MECHANICAL SCHEDULES: EN-07) 03/22/22: The previous comment had not been adequately addressed. The TRANE rooftop unit, which appears to be a new one, has not been updated on the schedule to include the IEER. ************************************************************************************02/16/22 - On the rooftop unit schedule, in addition to the EER listed for the new unit, list the IEER, to comply with Table C403.3.2(1).
Energy03/22/2022RejectedSheet P600 PLUMBING DETAILS: EN-08) 02/16/22 - Provide ON THE DRAWINGS a schedule of the gas tankless water heater. Include its size, and its minimum required efficiency from Tab;e C404.2.
Energy03/22/2022RejectedEN-09) 03/22/22: Resubmission may result in additional comments. Please number your narrative responses with the identical EN-X number indicated in my comments. This significantly reduces the time required for review of your responses. Per VECC 109.4. If you have questions regarding this energy code review, you can contact me via email at lbaskerville@arlingtonva.us, or call on my mobile number 703-244-0479. The Virginia Energy Conservation Code can be found free online at https://codes.iccsafe.org/content/VECC2018P1
Energy03/22/2022ApprovedSheet P600 PLUMBING DETAILS: EN-08) 02/16/22 - Provide ON THE DRAWINGS a schedule of the gas tankless water heater. Include its size, and its minimum required efficiency from Tab;e C404.2.
Energy03/22/2022RejectedSheet A001 ZONING AND BUILDING INFO: EN-1) EN-1) 03/22/22 – Current code year cycle is 2018, with the option to use 2015 until June 30, 2022. Your code summary indicates 2012. For Energy Code compliance purposes, you need to state in your code summary section whether you are following VECC or ASHRAE 90.1, and which year. Revise and resubmit. Per VCC section 101.2.*******************************02/16/22: NOT USED.
Energy03/22/2022RejectedSheet A104 FLOOR PLAN: EN-2) 03/22/22: The previous comment had not been addressed. Please address the energy code rejection comment. ************************************************************************************02/16/22 - Label the new door with an identification tag, for purposes of addressing the energy criteria associated with new fenestration.
Energy03/22/2022RejectedSheet A106 DOOR AND WALL TYPES: EN-03) 03/22/22: The previous comment had not been addressed. Please address the energy code rejection comment. ************************************************************************************02/16/22 : New doors and new windows/storefront/curtainwall glazing in the building thermal envelope shall meet the energy code requirements for all three of these metrics: A) the Air Infiltration Rate (whether glazed or opaque), B) the U-factor (whether glazed or opaque) and C) SHGC value (if glazed). Reference Tables C402.1.4, C402.4, C402.5.2. Per Existing Building Code 601.4. State ON THE DRAWINGS the numeric values for your specific fenestration types on the drawings. Citing only the code section numbe
Energy03/22/2022RejectedSheet E101 RCP: EN-4) 03/22/22: The previous comment had not been addressed. Please address the energy code rejection comment. ************************************************************************************02/16/22 COMCHECK – The incorrect space type has been entered into comcheck to determine the allowed wattage. You have opted to use the space by space method from Table C405.3.2(2). Each space’s function must be assigned the most closely matched category available. Café seating and dining would be Dining Area, and would be either lounge/bar or fast food, but NOT retail. The Bathroom would fall under Restroom NOT retail, the BOH needs to be separated in to Storage (former vault) and Food Prep Area, but NOT retail. Revise and
Energy03/22/2022RejectedSheet E101 RCP: EN-5) 03/22/22: The previous comment had not been addressed. Please address the energy code rejection comment. ************************************************************************************02/16/22 Lighting Controls – Provide the required occupancy sensors per C405.2.1, in the storage room. Revise and resubmit.
Energy03/22/2022RejectedSheet E101 RCP: EN-6) 03/22/22: The previous comment had not been addressed. Please address the energy code rejection comment. ************************************************************************************02/16/22 Lighting Controls – Provide the required manual controls light reduction for the areas that are NOT in a daylighting zone and that are NOT controlled by an occupancy sensor, per C405.2.2.1 and C405.2.2.2. Revise and resubmit.
Energy03/22/2022RejectedSheet M104 MECHANICAL SCHEDULES: EN-07) 03/22/22: The previous comment had not been adequately addressed. The TRANE rooftop unit, which appears to be a new one, has not been updated on the schedule to include the IEER. ************************************************************************************02/16/22 - On the rooftop unit schedule, in addition to the EER listed for the new unit, list the IEER, to comply with Table C403.3.2(1).
Energy03/22/2022RejectedSheet P600 PLUMBING DETAILS: EN-08) 02/16/22 - Provide ON THE DRAWINGS a schedule of the gas tankless water heater. Include its size, and its minimum required efficiency from Tab;e C404.2.
Energy04/25/2022RejectedEN-09) 04/25/22: Resubmission may result in additional comments. Please number your narrative responses with the identical EN-X number indicated in my comments. This significantly reduces the time required for review of your responses. Per VECC 109.4. If you have questions regarding this energy code review, you can contact me via email at lbaskerville@arlingtonva.us, or call on my mobile number 703-244-0479. The Virginia Energy Conservation Code can be found free online at https://codes.iccsafe.org/content/VECC2018P1
Energy04/25/2022RejectedSheet A106 DOOR AND WALL TYPES: EN-10) 4/25/22 - Change the word 'minimum' to 'maximum' U-factor. Per section C402.4.3.
Energy04/25/2022ApprovedEN-09) 04/25/22: Resubmission may result in additional comments. Please number your narrative responses with the identical EN-X number indicated in my comments. This significantly reduces the time required for review of your responses. Per VECC 109.4. If you have questions regarding this energy code review, you can contact me via email at lbaskerville@arlingtonva.us, or call on my mobile number 703-244-0479. The Virginia Energy Conservation Code can be found free online at https://codes.iccsafe.org/content/VECC2018P1
Energy04/25/2022ApprovedSheet A106 DOOR AND WALL TYPES: EN-10) 4/25/22 - Change the word 'minimum' to 'maximum' U-factor. Per section C402.4.3.
Energy04/25/2022ApprovedEN-09) 04/25/22: Resubmission may result in additional comments. Please number your narrative responses with the identical EN-X number indicated in my comments. This significantly reduces the time required for review of your responses. Per VECC 109.4. If you have questions regarding this energy code review, you can contact me via email at lbaskerville@arlingtonva.us, or call on my mobile number 703-244-0479. The Virginia Energy Conservation Code can be found free online at https://codes.iccsafe.org/content/VECC2018P1
Energy04/25/2022ApprovedSheet A106 DOOR AND WALL TYPES: EN-10) 4/25/22 - Change the word 'minimum' to 'maximum' U-factor. Per section C402.4.3.
Energy04/26/2022ApprovedSheet M104 MECHANICAL SCHEDULES: EN-07) 04/25/22 The provided IEER (12.7) does not meet the minimum code required IEER which is 12.8. Revise and resubmit a roof top unit which meets the minimum code efficiency requirements. ************************************************************************************03/22/22: The previous comment had not been adequately addressed. The TRANE rooftop unit, which appears to be a new one, has not been updated on the schedule to include the IEER. ************************************************************************************02/16/22 - On the rooftop unit schedule, in addition to the EER listed for the new unit, list the IEER, to comply with Table C403.3.2(1).
Energy04/26/2022RejectedSheet M104 MECHANICAL SCHEDULES: EN-07) 04/25/22 The provided IEER (12.7) does not meet the minimum code required IEER which is 12.8. Revise and resubmit a roof top unit which meets the minimum code efficiency requirements. ************************************************************************************03/22/22: The previous comment had not been adequately addressed. The TRANE rooftop unit, which appears to be a new one, has not been updated on the schedule to include the IEER. ************************************************************************************02/16/22 - On the rooftop unit schedule, in addition to the EER listed for the new unit, list the IEER, to comply with Table C403.3.2(1).
Energy04/26/2022ApprovedSheet M104 MECHANICAL SCHEDULES: EN-07) 04/25/22 The provided IEER (12.7) does not meet the minimum code required IEER which is 12.8. Revise and resubmit a roof top unit which meets the minimum code efficiency requirements. ************************************************************************************03/22/22: The previous comment had not been adequately addressed. The TRANE rooftop unit, which appears to be a new one, has not been updated on the schedule to include the IEER. ************************************************************************************02/16/22 - On the rooftop unit schedule, in addition to the EER listed for the new unit, list the IEER, to comply with Table C403.3.2(1).
Mechanical02/09/2022ApprovedSheet M100 MECHANICAL PLAN: Is these registers are supply or return registers?
Mechanical02/09/2022ApprovedSheet M101 MECHANICAL ROOF PLAN: Please indicate and add note this RTU is existing to remain, and show smoke detector on return duct.
Mechanical02/09/2022ApprovedSheet M101 MECHANICAL ROOF PLAN: Show number 3 note next to return duct.
Mechanical02/09/2022ApprovedSheet M101 MECHANICAL ROOF PLAN: Please show existing or new exhaust fan on the roof and indicate that is for toilet exhaust.
Mechanical02/09/2022ApprovedSheet M103 MECHANICAL DESIGN 3D: Show location of toilet exhaust fan on the roof.
Mechanical02/09/2022ApprovedSheet M100 MECHANICAL PLAN: Please coordinate every sheet note with floor plan.
Mechanical02/09/2022ApprovedSheet M100 MECHANICAL PLAN: Show location of dryer on floor plan including vent connection. At discharge location show louver with out bird screen.
Mechanical02/09/2022ApprovedSheet M104 MECHANICAL SCHEDULES: The occupant density #/1000 SF and breathing zone must be 100 and 0.18 for café and bar area (VMC 2018 table 403.3.1.1).
Mechanical02/09/2022ApprovedSheet M104 MECHANICAL SCHEDULES: Please indicate which RTU is new or existing and show outside air CFM in roof top unit schedule.
Mechanical02/09/2022ApprovedSheet M100 MECHANICAL PLAN: Please coordinate location of each toile with architectural plan, and keep each toilet under negative pressure.
Mechanical02/09/2022ApprovedSheet M100 MECHANICAL PLAN: Is these registers are supply or return registers?
Mechanical02/09/2022ApprovedSheet M101 MECHANICAL ROOF PLAN: Please indicate and add note this RTU is existing to remain, and show smoke detector on return duct.
Mechanical02/09/2022ApprovedSheet M101 MECHANICAL ROOF PLAN: Show number 3 note next to return duct.
Mechanical02/09/2022ApprovedSheet M101 MECHANICAL ROOF PLAN: Please show existing or new exhaust fan on the roof and indicate that is for toilet exhaust.
Mechanical02/09/2022ApprovedSheet M103 MECHANICAL DESIGN 3D: Show location of toilet exhaust fan on the roof.
Mechanical02/09/2022ApprovedSheet M100 MECHANICAL PLAN: Please coordinate every sheet note with floor plan.
Mechanical02/09/2022ApprovedSheet M100 MECHANICAL PLAN: Show location of dryer on floor plan including vent connection. At discharge location show louver with out bird screen.
Mechanical02/09/2022ApprovedSheet M104 MECHANICAL SCHEDULES: The occupant density #/1000 SF and breathing zone must be 100 and 0.18 for café and bar area (VMC 2018 table 403.3.1.1).
Mechanical02/09/2022ApprovedSheet M104 MECHANICAL SCHEDULES: Please indicate which RTU is new or existing and show outside air CFM in roof top unit schedule.
Mechanical02/09/2022ApprovedSheet M100 MECHANICAL PLAN: Please coordinate location of each toile with architectural plan, and keep each toilet under negative pressure.
Mechanical02/09/2022ApprovedSheet M100 MECHANICAL PLAN: Please coordinate every sheet note with floor plan.
Mechanical02/09/2022ApprovedSheet M100 MECHANICAL PLAN: Is these registers are supply or return registers?
Mechanical02/09/2022ApprovedSheet M103 MECHANICAL DESIGN 3D: Show location of toilet exhaust fan on the roof.
Mechanical02/09/2022ApprovedSheet M100 MECHANICAL PLAN: Show location of dryer on floor plan including vent connection. At discharge location show louver with out bird screen.
Mechanical02/09/2022ApprovedSheet M104 MECHANICAL SCHEDULES: Please indicate which RTU is new or existing and show outside air CFM in roof top unit schedule.
Mechanical02/09/2022ApprovedSheet M101 MECHANICAL ROOF PLAN: Show number 3 note next to return duct.
Mechanical02/09/2022ApprovedSheet M101 MECHANICAL ROOF PLAN: Please indicate and add note this RTU is existing to remain, and show smoke detector on return duct.
Mechanical02/09/2022ApprovedSheet M101 MECHANICAL ROOF PLAN: Please show existing or new exhaust fan on the roof and indicate that is for toilet exhaust.
Mechanical02/09/2022ApprovedSheet M104 MECHANICAL SCHEDULES: The occupant density #/1000 SF and breathing zone must be 100 and 0.18 for café and bar area (VMC 2018 table 403.3.1.1).
Mechanical02/09/2022ApprovedSheet M100 MECHANICAL PLAN: Please coordinate location of each toile with architectural plan, and keep each toilet under negative pressure.
Mechanical02/09/2022RejectedSheet M100 MECHANICAL PLAN: Is these registers are supply or return registers?
Mechanical02/09/2022RejectedSheet M101 MECHANICAL ROOF PLAN: Please indicate and add note this RTU is existing to remain, and show smoke detector on return duct.
Mechanical02/09/2022RejectedSheet M101 MECHANICAL ROOF PLAN: Show number 3 note next to return duct.
Mechanical02/09/2022RejectedSheet M101 MECHANICAL ROOF PLAN: Please show existing or new exhaust fan on the roof and indicate that is for toilet exhaust.
Mechanical02/09/2022RejectedSheet M103 MECHANICAL DESIGN 3D: Show location of toilet exhaust fan on the roof.
Mechanical02/09/2022RejectedSheet M100 MECHANICAL PLAN: Please coordinate every sheet note with floor plan.
Mechanical02/09/2022RejectedSheet M100 MECHANICAL PLAN: Show location of dryer on floor plan including vent connection. At discharge location show louver with out bird screen.
Mechanical02/09/2022RejectedSheet M100 MECHANICAL PLAN: Is these registers are supply or return registers?
Mechanical02/09/2022RejectedSheet M101 MECHANICAL ROOF PLAN: Please indicate and add note this RTU is existing to remain, and show smoke detector on return duct.
Mechanical02/09/2022RejectedSheet M101 MECHANICAL ROOF PLAN: Show number 3 note next to return duct.
Mechanical02/09/2022RejectedSheet M101 MECHANICAL ROOF PLAN: Please show existing or new exhaust fan on the roof and indicate that is for toilet exhaust.
Mechanical02/09/2022RejectedSheet M103 MECHANICAL DESIGN 3D: Show location of toilet exhaust fan on the roof.
Mechanical02/09/2022RejectedSheet M100 MECHANICAL PLAN: Please coordinate every sheet note with floor plan.
Mechanical02/09/2022RejectedSheet M100 MECHANICAL PLAN: Show location of dryer on floor plan including vent connection. At discharge location show louver with out bird screen.
Mechanical02/09/2022RejectedSheet M104 MECHANICAL SCHEDULES: The occupant density #/1000 SF and breathing zone must be 100 and 0.18 for café and bar area (VMC 2018 table 403.3.1.1).
Mechanical02/09/2022RejectedSheet M104 MECHANICAL SCHEDULES: Please indicate which RTU is new or existing and show outside air CFM in roof top unit schedule.
Mechanical02/09/2022RejectedSheet M100 MECHANICAL PLAN: Please coordinate location of each toile with architectural plan, and keep each toilet under negative pressure.
Mechanical02/09/2022RejectedSheet M104 MECHANICAL SCHEDULES: The occupant density #/1000 SF and breathing zone must be 100 and 0.18 for café and bar area (VMC 2018 table 403.3.1.1).
Mechanical02/09/2022RejectedSheet M104 MECHANICAL SCHEDULES: Please indicate which RTU is new or existing and show outside air CFM in roof top unit schedule.
Mechanical02/09/2022RejectedSheet M100 MECHANICAL PLAN: Please coordinate location of each toile with architectural plan, and keep each toilet under negative pressure.
Mechanical03/16/2022RejectedSheet M104 MECHANICAL SCHEDULES: Please provide uncorrected outdoor air intake (Vou) and system ventilation efficiency (Ev) for outside air calculations, and coordinate outside air CFM between rooftop unit schedule and outside air calculations (VMC 2015 or 2018 chapter 4)..
Mechanical03/16/2022ApprovedSheet M104 MECHANICAL SCHEDULES: Please provide uncorrected outdoor air intake (Vou) and system ventilation efficiency (Ev) for outside air calculations, and coordinate outside air CFM between rooftop unit schedule and outside air calculations (VMC 2015 or 2018 chapter 4)..
Mechanical03/16/2022ApprovedSheet M104 MECHANICAL SCHEDULES: Please provide uncorrected outdoor air intake (Vou) and system ventilation efficiency (Ev) for outside air calculations, and coordinate outside air CFM between rooftop unit schedule and outside air calculations (VMC 2015 or 2018 chapter 4)..
Mechanical03/16/2022ApprovedSheet M104 MECHANICAL SCHEDULES: Please provide uncorrected outdoor air intake (Vou) and system ventilation efficiency (Ev) for outside air calculations, and coordinate outside air CFM between rooftop unit schedule and outside air calculations (VMC 2015 or 2018 chapter 4)..
Plumbing02/14/2022Rejected2-14-22 Pg P600 Tee fitting required at Trap arm connection. 2018 VPC 706.3
Plumbing02/14/2022Rejected2/14/22 Pg P300 Plans seem to indicate Waste disposer connection. Waste Disposer prohibited to connect/drain to GI . 2018 VPC 1003.3.2
Plumbing02/14/2022Approved2-14-22 Pg P600 Tee fitting required at Trap arm connection. 2018 VPC 706.3
Plumbing02/14/2022Approved2/14/22 Pg P300 Plans seem to indicate Waste disposer connection. Waste Disposer prohibited to connect/drain to GI . 2018 VPC 1003.3.2
Plumbing02/14/2022Rejected2-14-22 Pg P600 Tee fitting required at Trap arm connection. 2018 VPC 706.3
Plumbing02/14/2022Rejected2/14/22 Pg P300 Plans seem to indicate Waste disposer connection. Waste Disposer prohibited to connect/drain to GI . 2018 VPC 1003.3.2
Plumbing02/14/2022Rejected2-14-22 Please provide location and additional information on Grease Interceptor. Size , calculation, location and details
Plumbing02/14/2022Approved2-14-22 Pg P600 Tee fitting required at Trap arm connection. 2018 VPC 706.3
Plumbing02/14/2022Approved2/14/22 Pg P300 Plans seem to indicate Waste disposer connection. Waste Disposer prohibited to connect/drain to GI . 2018 VPC 1003.3.2
Plumbing02/14/2022Rejected2-14-22 Pg P600 Tee fitting required at Trap arm connection. 2018 VPC 706.3
Plumbing02/14/2022Rejected2/14/22 Pg P300 Plans seem to indicate Waste disposer connection. Waste Disposer prohibited to connect/drain to GI . 2018 VPC 1003.3.2
Plumbing03/21/2022Rejected2-14-22 Please provide location and additional information on Grease Interceptor. Size , calculation, location and details 3-21-22 Please be advised requirements for Grease Interceptors is required under the 2018 VPC 1003.3.1 . A Code Modification will be required to be submitted and reviewed thru the Building Official. If u may have any further questions please contact me 703 228-3873
Plumbing03/21/2022Rejected3-21-22 Pg A000 states 2012 code year please update. Application states 2018 code year
Plumbing03/21/2022Rejected3-21-22 Pg A000 states 2012 code year please update. Application states 2018 code year
Plumbing03/21/2022Approved3-21-22 Pg A000 states 2012 code year please update. Application states 2018 code year
Plumbing03/21/2022Approved3-21-22 Pg A000 states 2012 code year please update. Application states 2018 code year
Plumbing04/22/2022Approved2-14-22 Please provide location and additional information on Grease Interceptor. Size , calculation, location and details 3-21-22 Please be advised requirements for Grease Interceptors is required under the 2018 VPC 1003.3.1 . A Code Modification will be required to be submitted and reviewed thru the Building Official. If u may have any further questions please contact me 703 228-3873 4-22-22 Respectfully please be advised Per Mr Dodge . The FOG policy has been updated to include Coffee Shops. Respectfully please contact Mr Dodge if you require further clarification. At this time a Grease interceptor is required. Please provide information as stated from my 2-14-22 comment.
Plumbing04/22/2022Rejected2-14-22 Please provide location and additional information on Grease Interceptor. Size , calculation, location and details 3-21-22 Please be advised requirements for Grease Interceptors is required under the 2018 VPC 1003.3.1 . A Code Modification will be required to be submitted and reviewed thru the Building Official. If u may have any further questions please contact me 703 228-3873 4-22-22 Respectfully please be advised Per Mr Dodge . The FOG policy has been updated to include Coffee Shops. Respectfully please contact Mr Dodge if you require further clarification. At this time a Grease interceptor is required. Please provide information as stated from my 2-14-22 comment.
Plumbing04/22/2022Approved2-14-22 Please provide location and additional information on Grease Interceptor. Size , calculation, location and details 3-21-22 Please be advised requirements for Grease Interceptors is required under the 2018 VPC 1003.3.1 . A Code Modification will be required to be submitted and reviewed thru the Building Official. If u may have any further questions please contact me 703 228-3873 4-22-22 Respectfully please be advised Per Mr Dodge . The FOG policy has been updated to include Coffee Shops. Respectfully please contact Mr Dodge if you require further clarification. At this time a Grease interceptor is required. Please provide information as stated from my 2-14-22 comment.
Public Health Division02/15/2022RejectedConfirm there will be a certified food protection manager provided at the pre-opening inspection and at all hours of operation. See the list of approved providers; https://health.arlingtonva.us/wp-content/uploads/sites/25/2021/08/Certified-Food-Manager-Guidelines_2021.08.02.pdf
Public Health Division02/15/2022RejectedProvide the proposed menu. The menu should include a consumer advisory disclosure and reminder for animal-derived foods offered raw or undercooked.
Public Health Division02/15/2022RejectedComplete and upload the Application for Foodservice Plan Review found on the Arlington County webpage. https://health.arlingtonva.us/wp-content/uploads/sites/25/2021/09/PHD-Food-Service-Plan-Review-Application_Fillable_2021.09.01.pdf
Public Health Division02/15/2022RejectedConfirm there will be a certified food protection manager provided at the pre-opening inspection and at all hours of operation. See the list of approved providers; https://health.arlingtonva.us/wp-content/uploads/sites/25/2021/08/Certified-Food-Manager-Guidelines_2021.08.02.pdf
Public Health Division02/15/2022RejectedProvide the proposed menu. The menu should include a consumer advisory disclosure and reminder for animal-derived foods offered raw or undercooked.
Public Health Division02/15/2022RejectedComplete and upload the Application for Foodservice Plan Review found on the Arlington County webpage. https://health.arlingtonva.us/wp-content/uploads/sites/25/2021/09/PHD-Food-Service-Plan-Review-Application_Fillable_2021.09.01.pdf
Public Health Division02/15/2022ApprovedConfirm there will be a certified food protection manager provided at the pre-opening inspection and at all hours of operation. See the list of approved providers; https://health.arlingtonva.us/wp-content/uploads/sites/25/2021/08/Certified-Food-Manager-Guidelines_2021.08.02.pdf
Public Health Division02/15/2022ApprovedProvide the proposed menu. The menu should include a consumer advisory disclosure and reminder for animal-derived foods offered raw or undercooked.
Public Health Division02/15/2022ApprovedComplete and upload the Application for Foodservice Plan Review found on the Arlington County webpage. https://health.arlingtonva.us/wp-content/uploads/sites/25/2021/09/PHD-Food-Service-Plan-Review-Application_Fillable_2021.09.01.pdf
Public Health Division02/15/2022ApprovedConfirm there will be a certified food protection manager provided at the pre-opening inspection and at all hours of operation. See the list of approved providers; https://health.arlingtonva.us/wp-content/uploads/sites/25/2021/08/Certified-Food-Manager-Guidelines_2021.08.02.pdf
Public Health Division02/15/2022ApprovedProvide the proposed menu. The menu should include a consumer advisory disclosure and reminder for animal-derived foods offered raw or undercooked.
Public Health Division02/15/2022ApprovedComplete and upload the Application for Foodservice Plan Review found on the Arlington County webpage. https://health.arlingtonva.us/wp-content/uploads/sites/25/2021/09/PHD-Food-Service-Plan-Review-Application_Fillable_2021.09.01.pdf
Public Health Division02/15/2022ApprovedConfirm there will be a certified food protection manager provided at the pre-opening inspection and at all hours of operation. See the list of approved providers; https://health.arlingtonva.us/wp-content/uploads/sites/25/2021/08/Certified-Food-Manager-Guidelines_2021.08.02.pdf
Public Health Division02/15/2022ApprovedProvide the proposed menu. The menu should include a consumer advisory disclosure and reminder for animal-derived foods offered raw or undercooked.
Public Health Division02/15/2022ApprovedComplete and upload the Application for Foodservice Plan Review found on the Arlington County webpage. https://health.arlingtonva.us/wp-content/uploads/sites/25/2021/09/PHD-Food-Service-Plan-Review-Application_Fillable_2021.09.01.pdf
Public Health Division03/16/2022RejectedConfirm all foods supplies are from an approved source.
Public Health Division04/21/2022ApprovedConfirm all foods supplies are from an approved source.
Public Health Division04/21/2022ApprovedConfirm all foods supplies are from an approved source.
Public Health Division04/21/2022ApprovedConfirm all foods supplies are from an approved source.
Structural03/23/2022ApprovedOnly one structural sheet was submitted for review. Are there more sheets?
Structural03/23/2022ApprovedPlease submit structural sheet with building code year, live loads, etc
Structural03/23/2022ApprovedOn sheet S231, how tall is the retaining wall?
Structural03/23/2022ApprovedPlease provide the safety factor for sliding and overturning of the retaining wall
Structural03/23/2022ApprovedOnly one structural sheet was submitted for review. Are there more sheets?
Structural03/23/2022ApprovedPlease submit structural sheet with building code year, live loads, etc
Structural03/23/2022ApprovedOn sheet S231, how tall is the retaining wall?
Structural03/23/2022ApprovedPlease provide the safety factor for sliding and overturning of the retaining wall
Structural03/23/2022ApprovedOnly one structural sheet was submitted for review. Are there more sheets?
Structural03/23/2022ApprovedPlease submit structural sheet with building code year, live loads, etc
Structural03/23/2022ApprovedOn sheet S231, how tall is the retaining wall?
Structural03/23/2022ApprovedPlease provide the safety factor for sliding and overturning of the retaining wall
Structural03/23/2022RejectedOnly one structural sheet was submitted for review. Are there more sheets?
Structural03/23/2022RejectedPlease submit structural sheet with building code year, live loads, etc
Structural03/23/2022RejectedOn sheet S231, how tall is the retaining wall?
Structural03/23/2022RejectedPlease provide the safety factor for sliding and overturning of the retaining wall
Zoning02/15/2022RejectedInterior and exterior alteration including parking of an existing building in C-2 district. Proposed use is restaurant (coffee cafe). Proposed seating capacity is 50. Proposed use is allowed. Rejected: 1. please provide existing and proposed parking plan and count for the site. 2. On the parking plan, please show the various dimensions of the parking spaces and driveway 3. For parking requirements, please refer to section 14.3.7A and 14.3.3C for parking dimensions 4. Please provide a zoning comment response letter when resubmitting revisions. Reviewer: Mudoh Mbah SAM Tel: 703-228-3727 Email: mmbah@arlingtonva.us
Zoning03/22/2022RejectedInterior and exterior alteration including parking of an existing building in C-2 district. Proposed use is restaurant (coffee cafe). Proposed seating capacity is 50. Proposed use is allowed. Rejected: 1. please provide existing and proposed parking plan and count for the site. 2. On the parking plan, please show the various dimensions of the parking spaces and driveway 3. For parking requirements, please refer to section 14.3.7A and 14.3.3C for parking dimensions 4. Please provide a zoning comment response letter when resubmitting revisions. Reviewer: Mudoh Mbah SAM Tel: 703-228-3727 Email: mmbah@arlingtonva.us
Zoning03/22/2022RejectedInterior and exterior alteration including parking of an existing building in C-2 district. Proposed use is restaurant (coffee cafe). Proposed seating capacity is 50. Proposed use is allowed. Rejected: 1. please provide existing and proposed parking plan and count for the site. 2. On the parking plan, please show the various dimensions of the parking spaces and driveway 3. For parking requirements, please refer to section 14.3.7A and 14.3.3C for parking dimensions 4. Please provide a zoning comment response letter when resubmitting revisions. Reviewer: Mudoh Mbah SAM Tel: 703-228-3727 Email: mmbah@arlingtonva.us
Zoning03/22/2022RejectedInterior and exterior alteration including parking of an existing building in C-2 district. Proposed use is restaurant (coffee cafe). Proposed seating capacity is 50. Proposed use is allowed. Total parkin provided = 15 Rejected: 1. It appears the restaurant proposes a drive-through window. This is not clear in your use description. Per $$7.1.3 use table, a use permit is required for a drive-through-window for this zoning district. Staff did not find any use permit approval for the drive through window. Please clarify or visit the county website for a use permit application. 2. The 215in (17.9ft) depth dimension provided for parking does not comply. A minimum of 18ft depth is required. Please reck your measurement. 3. Show the dimension
Zoning03/22/2022ApprovedInterior and exterior alteration including parking of an existing building in C-2 district. Proposed use is restaurant (coffee cafe). Proposed seating capacity is 50. Proposed use is allowed. Rejected: 1. please provide existing and proposed parking plan and count for the site. 2. On the parking plan, please show the various dimensions of the parking spaces and driveway 3. For parking requirements, please refer to section 14.3.7A and 14.3.3C for parking dimensions 4. Please provide a zoning comment response letter when resubmitting revisions. Reviewer: Mudoh Mbah SAM Tel: 703-228-3727 Email: mmbah@arlingtonva.us
Zoning03/22/2022ApprovedInterior and exterior alteration including parking of an existing building in C-2 district. Proposed use is restaurant (coffee cafe). Proposed seating capacity is 50. Proposed use is allowed. Rejected: 1. please provide existing and proposed parking plan and count for the site. 2. On the parking plan, please show the various dimensions of the parking spaces and driveway 3. For parking requirements, please refer to section 14.3.7A and 14.3.3C for parking dimensions 4. Please provide a zoning comment response letter when resubmitting revisions. Reviewer: Mudoh Mbah SAM Tel: 703-228-3727 Email: mmbah@arlingtonva.us
Zoning04/19/2022ApprovedInterior and exterior alteration including parking of an existing building in C-2 district. Proposed use is restaurant (coffee cafe). Proposed seating capacity is 50. Proposed use is allowed. Total parkin provided = 15 (conforming) Rejected: 1. It appears the restaurant proposes a drive-through window. This is not clear in your use description. Per $$7.1.3 use table, a use permit is required for a drive-through-window for this zoning district. Staff did not find any use permit approval for the drive through window. Please clarify or visit the county website for a use permit application. 2. The 215in (17.9ft) depth dimension provided for parking does not comply. A minimum of 18ft depth is required. Please reck your measurement. 3. Show
Zoning04/19/2022ApprovedInterior and exterior alteration including parking of an existing building in C-2 district. Proposed use is restaurant (coffee cafe). Proposed seating capacity is 50. Proposed use is allowed. Total parkin provided = 15 (conforming) Rejected: 1. It appears the restaurant proposes a drive-through window. This is not clear in your use description. Per $$7.1.3 use table, a use permit is required for a drive-through-window for this zoning district. Staff did not find any use permit approval for the drive through window. Please clarify or visit the county website for a use permit application. 2. The 215in (17.9ft) depth dimension provided for parking does not comply. A minimum of 18ft depth is required. Please reck your measurement. 3. Show
Zoning04/19/2022RejectedInterior and exterior alteration including parking of an existing building in C-2 district. Proposed use is restaurant (coffee cafe). Proposed seating capacity is 50. Proposed use is allowed. Total parkin provided = 15 (conforming) Rejected: 1. It appears the restaurant proposes a drive-through window. This is not clear in your use description. Per $$7.1.3 use table, a use permit is required for a drive-through-window for this zoning district. Staff did not find any use permit approval for the drive through window. Please clarify or visit the county website for a use permit application. 2. The 215in (17.9ft) depth dimension provided for parking does not comply. A minimum of 18ft depth is required. Please reck your measurement. 3. Show
Zoning05/02/2022RejectedRejected: 1. As discussed, Please revise the enclosure around the trash bin to be maximum 4ft in height as required. $$3.2.6A.3e: ) The front, side and rear yard requirements of this zoning ordinance shall not be deemed to prohibit any otherwise lawful fence or wall which is not more than four feet high; provided, however, that a fence or wall along the rear lot line or along a side lot line to the rear of the required setback line may be erected to a height not exceeding seven feet; provided, further, that in side and rear yards of corner lots, fences up to six feet in height may be erected in the required setback in order to permit the enclosure of the side and rear yards for privacy so long as the requirements of §3.2.6.A.4, rel
Zoning05/02/2022ApprovedRejected: 1. As discussed, Please revise the enclosure around the trash bin to be maximum 4ft in height as required. $$3.2.6A.3e: ) The front, side and rear yard requirements of this zoning ordinance shall not be deemed to prohibit any otherwise lawful fence or wall which is not more than four feet high; provided, however, that a fence or wall along the rear lot line or along a side lot line to the rear of the required setback line may be erected to a height not exceeding seven feet; provided, further, that in side and rear yards of corner lots, fences up to six feet in height may be erected in the required setback in order to permit the enclosure of the side and rear yards for privacy so long as the requirements of §3.2.6.A.4, rel
Zoning05/02/2022ApprovedRejected: 1. As discussed, Please revise the enclosure around the trash bin to be maximum 4ft in height as required. $$3.2.6A.3e: ) The front, side and rear yard requirements of this zoning ordinance shall not be deemed to prohibit any otherwise lawful fence or wall which is not more than four feet high; provided, however, that a fence or wall along the rear lot line or along a side lot line to the rear of the required setback line may be erected to a height not exceeding seven feet; provided, further, that in side and rear yards of corner lots, fences up to six feet in height may be erected in the required setback in order to permit the enclosure of the side and rear yards for privacy so long as the requirements of §3.2.6.A.4, rel
Zoning05/16/2022ApprovedInterior and exterior alteration including parking of an existing building in C-2 district. Proposed use is restaurant (coffee cafe). Proposed seating capacity is 50. Proposed use is allowed. Total parking provided = 15 (conforming). Enclosure around dumpster is max. 4ft height as required. APPROVAL NOTE: 1. Work must be done as shown on the plan and plat submitted for zoning review on 9/22/2017. Any alteration to the above will need zoning review and approval. Reviewer: Mudoh Mbah Tel: 703-228-3727 Email: mmbah@arlingtonva.us
Zoning05/16/2022ApprovedInterior and exterior alteration including parking of an existing building in C-2 district. Proposed use is restaurant (coffee cafe). Proposed seating capacity is 50. Proposed use is allowed. Total parking provided = 15 (conforming). Enclosure around dumpster is max. 4ft height as required. APPROVAL NOTE: 1. Work must be done as shown on the plan and plat submitted for zoning review on 9/22/2017. Any alteration to the above will need zoning review and approval. Reviewer: Mudoh Mbah Tel: 703-228-3727 Email: mmbah@arlingtonva.us