Permit Comments
 
Permit #B2200650
Address2910 COLUMBIA PIKE
TypeCTBO
StatusAPPLIED
Permit HolderCONTRACTOR TBD
OwnerARLINGTON FREE CLINIC INC
Applied Date30/03/2022
Approved Date 
Date Issued 
DescriptionNEW OWNER, PAINTING, FLOORING AND NEW VENTILATION ONLY NO GAS AND PLUMBING CHANGE, EXISTING LAYOUT TO REMAIN TENANT : Nightbird Restaurant & Lounge

ReviewReview DateStatusComments
Building06/08/2022RejectedPlans returned to submitter to rename the files with descriptive names. Please give the files names that will help the reviewers find what they are looking for. A descriptive file name might be "A3 - PROPOSED FIRST FLOOR PLAN" for example. Name the files as shown in your Drawing Index on CS - COVER SHEET. ************* 6/8/22 ************ Comment not addressed.
Building06/22/2022RejectedSheet A004_ProposedMezzanine: Please provide an area analysis for the mezzanine demonstrating the additional floor area still qualifies as a mezzanine per VCC 505
Building06/22/2022RejectedSheet A004_ProposedMezzanine: Stated 36" high handrail should be a 42" high guardrail complying with 1015 VCC. Please include construction details for the rail.
Building06/22/2022RejectedSheet CS000_Coversheet: Please include area occupant load for both levels with seating and standing area calculations.
Building06/22/2022RejectedPlease update all MEP plan sheets showing the new layout of the mezzanine which includes the added floor area.
Building06/22/2022RejectedPlease provide exit lighting plan for mezzanine.
Building06/22/2022RejectedSheet A004_ProposedMezzanine: This is a type II A building. The new mezzanine floor must be non combustible protected per VCC table 601
Building06/22/2022RejectedSheet A004_ProposedMezzanine: Show 5% accessible seating at bar,tables and banquette per VCC 1108.2.9.1
Building06/22/2022RejectedSheet A004_ProposedMezzanine: Provide door and hardware schedule for door at new smoking room.
Building07/01/2022RejectedSheet A005_EquipmentSchedule: The area of the mezzanine containing the divider walls and lounge furniture is a dead end exceeding 20' for an A use. The condition is existing, however adding the walls and lounge furniture makes the condition worse as there is no line of sight and area to return in the direction from which you have come. Please show a condition compliant with VCC 1020.4
DES:Water/Sewer Engineering06/07/2022ApprovedCTBO INT ALT USING EXISTING FIXTURES
Mechanical06/30/2022RejectedSheet M002_NewExhaustedFanplan: Please confirm area of smoke room which is 189 SF.
Mechanical06/30/2022RejectedSheet M002_NewExhaustedFanplan: Smoking room ventilation must be in accordance with VMC 2015 table 403.3.1.1 and must under negative pressure.
Mechanical06/30/2022RejectedSheet M002_NewExhaustedFanplan: Recirculation or air from smoking room is prohibited.
Mechanical06/30/2022RejectedSheet M002_NewExhaustedFanplan: Provide outside air calculations for above referenced project for each area (VMC 2015 or 2018 table 403.3.1.1).
Mechanical06/30/2022RejectedSheet M002_NewExhaustedFanplan: Provide mechanical first floor plan, demolition and new work.
Mechanical06/30/2022RejectedSheet M002_NewExhaustedFanplan: Show location of convection oven on floor plan and it's ventilation system including cut sheet.
Mechanical06/30/2022RejectedSheet M002_NewExhaustedFanplan: Show mechanical lay-out for mezzanine floor plan
Public Health Division04/06/2022ApprovedSheet AccessibilityComplianceForm2012: It is not permitted for the customer to be required to pass through a smoking area to get to the non-smoking area, or to get to the restroom. In order to have the plan accepted by the Health Department, the plan must be revised to meet the Code of Virginia 15.2-2825 and show the following; The smoking area and the non-smoking area must be provided with separate ventilation systems (show separate ventilation units and duct work). If Hookah is to be provided by the establishment, a separate cleaning area must be shown.
Public Health Division04/06/2022ApprovedSheet AccessibilityComplianceForm2012: Provide a copy of the menu. The menu must include the Health disclaimer statement, and the necessary asterisks on the pertinent menu items that may be ordered raw or undercooked.
Public Health Division04/06/2022ApprovedSheet AccessibilityComplianceForm2012: Confirm a Certified Food Protection Manager will be on duty during all hours of operation.
Public Health Division04/06/2022ApprovedSheet AccessibilityComplianceForm2012: Show a hand wash sink on the diagram for the second floor bar.
Public Health Division04/06/2022ApprovedComplete and upload the Application for Foodservice Plan Review found on the Arlington County webpage. https://health.arlingtonva.us/wp-content/uploads/sites/25/2021/09/PHD-Food-Service-Plan-Review-Application_Fillable_2021.09.01.pdf
Public Health Division04/06/2022ApprovedShow a dump sink in the bar area.
Public Health Division04/06/2022ApprovedWill windows or garage style doors open to the outside? If yes, submit the specifications for air curtains or screens installed at windows or doors that open to the outside for ventilation.
Public Health Division04/06/2022RejectedSheet AccessibilityComplianceForm2012: It is not permitted for the customer to be required to pass through a smoking area to get to the non-smoking area, or to get to the restroom. In order to have the plan accepted by the Health Department, the plan must be revised to meet the Code of Virginia 15.2-2825 and show the following; The smoking area and the non-smoking area must be provided with separate ventilation systems (show separate ventilation units and duct work). If Hookah is to be provided by the establishment, a separate cleaning area must be shown.
Public Health Division04/06/2022RejectedSheet AccessibilityComplianceForm2012: Provide a copy of the menu. The menu must include the Health disclaimer statement, and the necessary asterisks on the pertinent menu items that may be ordered raw or undercooked.
Public Health Division04/06/2022RejectedSheet AccessibilityComplianceForm2012: Confirm a Certified Food Protection Manager will be on duty during all hours of operation.
Public Health Division04/06/2022RejectedSheet AccessibilityComplianceForm2012: Show a hand wash sink on the diagram for the second floor bar.
Public Health Division04/06/2022RejectedComplete and upload the Application for Foodservice Plan Review found on the Arlington County webpage. https://health.arlingtonva.us/wp-content/uploads/sites/25/2021/09/PHD-Food-Service-Plan-Review-Application_Fillable_2021.09.01.pdf
Public Health Division04/06/2022RejectedShow a dump sink in the bar area.
Public Health Division04/06/2022RejectedWill windows or garage style doors open to the outside? If yes, submit the specifications for air curtains or screens installed at windows or doors that open to the outside for ventilation.
Public Health Division06/06/2022RejectedSheet A4: Confirm that smoking will not be permitted to occur outside of the smoking room.
Public Health Division06/06/2022RejectedSheet A4: Show a space with a dedicated sink within the establishment for cleaning any equipment associated with smoking.
Public Health Division06/06/2022RejectedSheet A4: Provide a menu with necessary consumer advisory information as necessary.
Public Health Division06/06/2022ApprovedSheet A4: Confirm that smoking will not be permitted to occur outside of the smoking room.
Public Health Division06/06/2022ApprovedSheet A4: Show a space with a dedicated sink within the establishment for cleaning any equipment associated with smoking.
Public Health Division06/06/2022ApprovedSheet A4: Provide a menu with necessary consumer advisory information as necessary.
Structural07/08/2022RejectedProvide on structural sheet the building code year being used
Structural07/08/2022RejectedProvide in structural sheet the live loads
Structural07/08/2022RejectedPer structural sheet S001 regarding steel beam, a special inspections packet needs to be submitted for review. See comment below
Structural07/11/2022RejectedSpecial Inspections; REJECTED Due to the project’s scope of work, Special Inspections will be required. Please submit the Statement of Special Inspections (SSI) packet. This statement is to be prepared by the Structural Engineer of Record (SER), and is used for identifying the structural items that require special inspection. (1) The SSI shall cover the special inspection requirements for the completion of the project. (2) All fields on the SSI must be completed. For irrelevant items, please mark N/A. All relevant items must be marked with the SIER/SER initials. For items not specified in the Statement, please write in the inspection in the field marked “other inspection” on page 59. (3) The SSI shall be signed by the Structural E
Zoning07/07/2022ApprovedInterior renovation of an existing restaurant in C-2 zoning district. No zoning issues is identified.