Review | Review Date | Status | Comments |
Bike Review | 04/20/2022 | Additional | Sheet A2-02 - FLOOR PLAN -LEVEL G1: Provide dimensioned detail call-out drawing for each interior Class 1 bike parking area. Detail drawing will show the proposed room or cage walls, wall material, door and door material, cage wall and/or door security plates or strike guard (as appropriate), door lock type, the dimensions between the racks, dimension from racks to the walls and other obstructions, vertical clearance, aisle widths, and how many bike parking spaces are provided in each bike room. |
Bike Review | 04/20/2022 | Additional | Sheet A2-02 - FLOOR PLAN -LEVEL G1: Provide construction drawing/spec/cut sheets for all proposed bike rack products to be used, consistent with the County's Bike Parking Standards. Arlington County’s bike parking standards guide is available online, but email smcgraw@arlingtonva.us for a link to the guidance if you need it. |
Bike Review | 04/20/2022 | Additional | Sheet A2-02 - FLOOR PLAN -LEVEL G1: Please indicate which room the employee bike parking space(s) required for use by retail employees will be located in. Please indicate if the required locker(s) will also be part of that room. |
Bike Review | 04/20/2022 | Additional | Sheet A2-01 - FLOOR PLAN -LEVEL G2: Provide dimensioned detail call-out drawing for each interior Class 1 bike parking area. Detail drawing will show the proposed room or cage walls, wall material, door and door material, cage wall and/or door security plates or strike guard (as appropriate), door lock type, the dimensions between the racks, dimension from racks to the walls and other obstructions, vertical clearance, aisle widths, and how many bike parking spaces are provided in each bike room. |
Bike Review | 04/20/2022 | Additional | Sheet A2-01 - FLOOR PLAN -LEVEL G2: Provide construction drawing/spec/cut sheets for all proposed bike rack products to be used, consistent with the County's Bike Parking Standards. Arlington County’s bike parking standards guide is available online, but email smcgraw@arlingtonva.us for a link to the guidance if you need it. |
Bike Review | 04/20/2022 | Rejected | Sheet A2-01 - FLOOR PLAN -LEVEL G2: Provide dimensioned detail call-out drawing for each interior Class 1 bike parking area. Detail drawing will show the proposed room or cage walls, wall material, door and door material, cage wall and/or door security plates or strike guard (as appropriate), door lock type, the dimensions between the racks, dimension from racks to the walls and other obstructions, vertical clearance, aisle widths, and how many bike parking spaces are provided in each bike room. |
Bike Review | 04/20/2022 | Rejected | Sheet A2-01 - FLOOR PLAN -LEVEL G2: Provide construction drawing/spec/cut sheets for all proposed bike rack products to be used, consistent with the County's Bike Parking Standards. Arlington County’s bike parking standards guide is available online, but email smcgraw@arlingtonva.us for a link to the guidance if you need it. |
Bike Review | 04/20/2022 | Rejected | Sheet A2-02 - FLOOR PLAN -LEVEL G1: Provide dimensioned detail call-out drawing for each interior Class 1 bike parking area. Detail drawing will show the proposed room or cage walls, wall material, door and door material, cage wall and/or door security plates or strike guard (as appropriate), door lock type, the dimensions between the racks, dimension from racks to the walls and other obstructions, vertical clearance, aisle widths, and how many bike parking spaces are provided in each bike room. |
Bike Review | 04/20/2022 | Rejected | Sheet A2-02 - FLOOR PLAN -LEVEL G1: Provide construction drawing/spec/cut sheets for all proposed bike rack products to be used, consistent with the County's Bike Parking Standards. Arlington County’s bike parking standards guide is available online, but email smcgraw@arlingtonva.us for a link to the guidance if you need it. |
Bike Review | 04/20/2022 | Rejected | Sheet A2-02 - FLOOR PLAN -LEVEL G1: Please indicate which room the employee bike parking space(s) required for use by retail employees will be located in. Please indicate if the required locker(s) will also be part of that room. |
Bike Review | 04/20/2022 | Rejected | Sheet A2-01 - FLOOR PLAN -LEVEL G2: Provide dimensioned detail call-out drawing for each interior Class 1 bike parking area. Detail drawing will show the proposed room or cage walls, wall material, door and door material, cage wall and/or door security plates or strike guard (as appropriate), door lock type, the dimensions between the racks, dimension from racks to the walls and other obstructions, vertical clearance, aisle widths, and how many bike parking spaces are provided in each bike room. |
Bike Review | 04/20/2022 | Rejected | Sheet A2-01 - FLOOR PLAN -LEVEL G2: Provide construction drawing/spec/cut sheets for all proposed bike rack products to be used, consistent with the County's Bike Parking Standards. Arlington County’s bike parking standards guide is available online, but email smcgraw@arlingtonva.us for a link to the guidance if you need it. |
Bike Review | 04/20/2022 | Rejected | Sheet A2-02 - FLOOR PLAN -LEVEL G1: Provide dimensioned detail call-out drawing for each interior Class 1 bike parking area. Detail drawing will show the proposed room or cage walls, wall material, door and door material, cage wall and/or door security plates or strike guard (as appropriate), door lock type, the dimensions between the racks, dimension from racks to the walls and other obstructions, vertical clearance, aisle widths, and how many bike parking spaces are provided in each bike room. |
Bike Review | 04/20/2022 | Rejected | Sheet A2-02 - FLOOR PLAN -LEVEL G1: Provide construction drawing/spec/cut sheets for all proposed bike rack products to be used, consistent with the County's Bike Parking Standards. Arlington County’s bike parking standards guide is available online, but email smcgraw@arlingtonva.us for a link to the guidance if you need it. |
Bike Review | 04/20/2022 | Rejected | Sheet A2-02 - FLOOR PLAN -LEVEL G1: Please indicate which room the employee bike parking space(s) required for use by retail employees will be located in. Please indicate if the required locker(s) will also be part of that room. |
Bike Review | 06/27/2022 | Rejected | Sheet A3-51 - ENLARGED PLAN -LOADING DOCK & PARKING RAMP: Comment response says the locker and shower for retail employees are provided on the first floor in proximity to the bike storage room. Indicate locker and shower locations and locker dimensions on this sheet. 2 lockers are required per County requirements. |
Bike Review | 06/27/2022 | Rejected | Sheet A3-51 - ENLARGED PLAN -LOADING DOCK & PARKING RAMP: Label rack type and dimensions and show vertical clearance if using vertical or double-decker racks. |
Bike Review | 06/27/2022 | Rejected | Sheet A3-54 - ENLARGED PLANS -BIKE STORAGE: For G2 SE bike storage room, it indicates space for 134 bikes but only shows a total of 132 spaces: 13 Saris stretch racks for 10 bikes each (130 total) and 2 one-sided racks. Sheet A2-01 FLOOR PLAN LEVEL G2 says there should be a total of 133, so the number indicated on this sheet seems incorrect. |
Bike Review | 06/27/2022 | Rejected | Sheet A3-54 - ENLARGED PLANS -BIKE STORAGE: Bike parking matrix on other sheets says there are 6 accessible bike racks on G2, but only 5 indicated (3 in NE bike storage and 2 in SE bike storage). Show location of 6th accessible rack. |
Building | 04/28/2022 | Rejected | Sheet A2.11 - Room 214: Please check Door #ID214 front approach, pull side door clearance per ICC A117.1-2009, 404.2.3.2. Please also see figure 4040.2.3.2(a). |
Building | 04/28/2022 | Rejected | Sheets A10.10, A10.11, A10.12 – Blocking for Type A and B units: It appears that a general note is provided for grab bar blocking requirements stating it shall meet ANSI A117.1-2009. This note appears to be too general in nature. Where are you calling out blocking required locations? Your restroom plans nor elevations show grab bar and blocking locations compliant with ICC A117.1-2009, Type-A 1003.11.1 and Type-B 1004.11.1. Please clarify. |
Building | 04/28/2022 | Rejected | Sheet A10.10, A10.11, A10.12: In Type A units, how does the Lavatory unit comply with ICC A117.1-2009, 1003.11.2.2? |
Building | 04/28/2022 | Rejected | Sheet A10.10, A10.11, A10.12: In Type B units, how does the Lavatory unit comply with ICC A117.1-2009, 1004.11.3.1.1? |
Building | 04/28/2022 | Rejected | Sheet A2.10: Is reception desk accessible per ICC A117.1-2009, 904? |
Building | 04/28/2022 | Rejected | Sheet A2-10: Your Retail space appears to not have restroom access. How are you complying with VCC 2902 Plumbing Fixture requirements for Retail use? |
Building | 04/28/2022 | Rejected | Sheet A2-10: Mail room appears to have a large table or some form of mail storage unit? How are you complying with ADA accessibility requirements based on ICC A117.1-2009, 308 and 904? |
Building | 04/28/2022 | Rejected | Is Leasing office front desk ADA accessible based on ICC A117.1-2009, 904? |
Building | 04/28/2022 | Rejected | Sheet A2.26: See markup. There appears to be 3 chairs located in shallow pool area and pool extent is unclear. What’s the extent of the shallow pool? |
Building | 04/28/2022 | Rejected | Sheet A2.26: Handrail extensions at top and bottom of stair? (VCC 1014.6) |
Building | 04/28/2022 | Rejected | General comment – Sheet G0.01: See markups. Please update sheet index to match submitted permit sheets. |
Building | 04/28/2022 | Rejected | General comment – Sheet G0.01: See markup. Enlarged A-series sheets not provided for review. Please provide. Current plan review is incomplete. Additional review comments may be forthcoming upon resubmission. |
Building | 04/28/2022 | Rejected | General Comment: Please provide a breakdown of the Gross Floor Area by Floor for each Level. The Building Permit Area includes spaces not included in Zoning FAR. Building Permit Area typically includes ALL MEP Utility Areas, Vault Spaces, Roof Decks, Terrace, Balconies and Garage (and Occupiable Roof Areas). |
Building | 04/28/2022 | Rejected | General Comment – Exterior wall section details Sheets A6-11 to A6-14: It appears that your Exterior Wall Sections call for “Exterior Sheathing”. What’s the sheating thickness? For a Construction Type IB building, your Exterior Wall system is required to be built out of Noncombustible material(s) per VCC, 602.2. Accordingly, you cannot use regular exterior grade plywood/sheathing. This means that the exterior surface is required to be a Noncombustible Sheathing Material or FRT Plywood. |
Building | 04/28/2022 | Rejected | Sheet A2.01: Stair & Elevator numbering sequence shall be determined based on Arlington County Fire Department requirements. As you enter the Lobby the first stair may be Stair-A followed by clockwise numbering. Since these are tied to the Fire Alarm, please reach out to Cpt. Gregg Karl via email gkarl@arlingtonva.us and confirm Arlington County FD preferred Stair and Elevator naming and numbering. |
Building | 04/28/2022 | Rejected | General comment – Sheet G0.01: See markups. Please update sheet index to match submitted permit sheets. |
Building | 04/28/2022 | Rejected | General comment – Sheet G0.01: See markup. Enlarged A-series sheets not provided for review. Please provide. Current plan review is incomplete. Additional review comments may be forthcoming upon resubmission. |
Building | 04/28/2022 | Rejected | General Comment: Please provide a breakdown of the Gross Floor Area by Floor for each Level. The Building Permit Area includes spaces not included in Zoning FAR. Building Permit Area typically includes ALL MEP Utility Areas, Vault Spaces, Roof Decks, Terrace, Balconies and Garage (and Occupiable Roof Areas). |
Building | 04/28/2022 | Rejected | General Comment – Exterior wall section details Sheets A6-11 to A6-14: It appears that your Exterior Wall Sections call for “Exterior Sheathing”. What’s the sheating thickness? For a Construction Type IB building, your Exterior Wall system is required to be built out of Noncombustible material(s) per VCC, 602.2. Accordingly, you cannot use regular exterior grade plywood/sheathing. This means that the exterior surface is required to be a Noncombustible Sheathing Material or FRT Plywood. |
Building | 04/28/2022 | Rejected | General Comment: Air-bone Sound - Wall, partitions and floor/ceiling assemblies separating dwelling units and sleeping units from each other or from the public or service areas shall have a Sound Transmission Class of not less than 50 STC, for air-borne noise when tested in accordance with ASTM E90. Please show me how are you addressing this code requirement? (2015 VCC, 1207.2) |
Building | 04/28/2022 | Rejected | General Comment: Structure-borne Sound – How are you addressing the 50 STC minimum impact isolation class requirement between dwelling units and/or sleeping units per ASTM E492? (2015 VCC, 1207.03) |
Building | 04/28/2022 | Rejected | General Comment: Please provide Civil drawings for plan review reference. Please upload each sheet individually. |
Building | 04/28/2022 | Rejected | Sheet G0.07 - Is East side “Alley” a public or private alley? View 1/A4.22 appears to show majority of alley within property boundary. You may calculate fire separation distance to alley centerline only if it’s a public alley. A private alley does not count. See markups on “Exterior Partition Openings” table. Markups show allowable FSD percentage based on property line to east façade at ground floor. You may want to double check. |
Building | 04/28/2022 | Rejected | Sheet G0.07 - Architectural Site Plan shows an aerial view of the proposed building and also shows the roof lines too. FSD is floor by floor and so it varies as plan moves in and out. And so this Site Plan is not helpful to determine FSD. Overall floor plans aren’t helpful to determine FSD since road and alley aren’t shown on them. You may want to filter line work and clearly show and tag building façades, Roads and Alley extent and dimension FSD. |
Building | 04/28/2022 | Rejected | Sheet G0.07: See markups on referenced code sections. Please be consistent in referencing VCC code sections as this has amendments to the IBC and at times the referenced sections may not match. |
Building | 04/28/2022 | Rejected | Sheet G0.06 - Parking Tabulation: It appears that a Zoning compliant parking count is provided for Residential, Residential visitor and Retail uses. Please note that while Zoning has their own parking requirements that are required to be complied with, that the VCC building code has its own parking requirements listed in “chapter 11 Accessibility” that’s also required to be complied with. Accordingly, accessible parking space requirement are derived using VCC, Table 1106.1(1). Please show how you’re proposing to comply with building code required accessible parking for the 3 functions listed above. Note that you’re first required to provide Van accessible space(s) for compliance with VCC 1106.5 (check and show required headroom clearance re |
Building | 04/28/2022 | Rejected | Sheet G0.06 - Parking Tabulation: Please see markup. Help me understand what you mean by “included in residential total”? - Are residential total parking 65 spaces? Using VCC Table 1106.1(1) and VCC 1106.5, please provide me a parking space breakdown for regular, compact, ADA car and ADA Van as applicable to the Residential, Visitor and Retail uses. |
Building | 04/28/2022 | Rejected | Sheet G0.06 - Parking Tabulation: A total of 4 accessible parking spaces are shown on plan (2 van and 2 car spaces). It appears that 2 accessible car spaces have access to “EV charging stations”. We encourage and support this route for providing EV accessible charging for equitable use. However, we do not want to limit the number of accessible parking spaces available for regular ADA use too. For example, an accessible needs person may not be driving an electric vehicle and may not require an EV space, but their parking needs have to be met too based on code required minimum number of spaces. As such we require that you first provide the minimum number of accessible parking required per building code per VCC Table 1106.1(1) and 1106.5, and |
Building | 04/28/2022 | Rejected | Sheet G0.06 – Unit Matrix Tabulation: VCC 1107.6.2.2.1 requires 2% Type-A units based on overall unit count and disbursed among the various unit classes. Building code appear to require 5 Type-A units (231 units x 0.02 = 5 Type-A min). Your matrix appears to show 12 Type-A units, which is acceptable. However, Type-A, 2 & 3-bedroom units appear to occur at the lower levels only and none are located beyond level 7 at higher levels. I’m concerned that these units don’t appear to be equitable disbursement since they may not receive comparable outside views or balcony access? |
Building | 04/28/2022 | Rejected | Sheet A2.01: There are 8 exterior doors shown on plan. Please help me understand how many of these are building entrance doors and how they comply with VCC section 1105.1 which requires at least 60% of all public entrances to be accessible? |
Building | 04/28/2022 | Rejected | Sheet A2.01: Stair & Elevator numbering sequence shall be determined based on Arlington County Fire Department requirements. As you enter the Lobby the first stair may be Stair-A followed by clockwise numbering. Since these are tied to the Fire Alarm, please reach out to Cpt. Gregg Karl via email gkarl@arlingtonva.us and confirm Arlington County FD preferred Stair and Elevator naming and numbering. |
Building | 04/28/2022 | Rejected | Sheet A7.01 - Stair A: Please coordinate slab elevations shown on stair detail plans with Stair section view 10/A7.01. |
Building | 04/28/2022 | Rejected | Sheet A7.02 - Stair B: Similar to Stair A, please show me your stair landing elevations on stair detail plans and coordinate with section details 9, 10 and 11. |
Building | 04/28/2022 | Rejected | Sheet A7.02 – Stair B: See markup. Please check of concrete beam is obstructing stair pressurization duct path. SP-2 riser appears to be changing path between level 16 and PH. |
Building | 04/28/2022 | Rejected | Sheet A2.10: Is reception desk accessible per ICC A117.1-2009, 904? |
Building | 04/28/2022 | Rejected | Sheet A2-10: Your Retail space appears to not have restroom access. How are you complying with VCC 2902 Plumbing Fixture requirements for Retail use? |
Building | 04/28/2022 | Rejected | Sheet A2-10: Mail room appears to have a large table or some form of mail storage unit? How are you complying with ADA accessibility requirements based on ICC A117.1-2009, 308 and 904? |
Building | 04/28/2022 | Rejected | Is Leasing office front desk ADA accessible based on ICC A117.1-2009, 904? |
Building | 04/28/2022 | Rejected | Sheet A2.26: See markup. There appears to be 3 chairs located in shallow pool area and pool extent is unclear. What’s the extent of the shallow pool? |
Building | 04/28/2022 | Rejected | Sheet A2.26: Handrail extensions at top and bottom of stair? (VCC 1014.6) |
Building | 04/28/2022 | Rejected | What is the large object shown inside the “West Meeting Room” (VCC 109.3). Enlarged plan A3.57 not provided for review. |
Building | 04/28/2022 | Rejected | How does the Roof Terrace function for ADA access? Please provide enlarged sheet A3.58, balcony threshold detail per VCC 1010.1.7 and guardrail detail per VCC 1015. |
Building | 04/28/2022 | Rejected | Sheet A2.11 - Room 214: Please check Door #ID214 front approach, pull side door clearance per ICC A117.1-2009, 404.2.3.2. Please also see figure 4040.2.3.2(a). |
Building | 04/28/2022 | Rejected | General Comment: ALL Efficiency Dwelling Units shall have a Living Room not less than 220 SF of floor area (VCC 1208.4). The corridor/passageway from the entrance door that leads into this space cannot be considered towards the minimum required floor area. Please check ALL the Efficiency Unit Floor Plans and ensure that they comply with the minimum required floor area code requirement.
Example: Micro A, Micro D, Micro D (Type A), JR 1 Bed A (Type A).
|
Building | 04/28/2022 | Rejected | Sheets A10.10, A10.11, A10.12 – Blocking for Type A and B units: It appears that a general note is provided for grab bar blocking requirements stating it shall meet ANSI A117.1-2009. This note appears to be too general in nature. Where are you calling out blocking required locations? Your restroom plans nor elevations show grab bar and blocking locations compliant with ICC A117.1-2009, Type-A 1003.11.1 and Type-B 1004.11.1. Please clarify. |
Building | 04/28/2022 | Rejected | Sheet A10.10, A10.11, A10.12: In Type A units, how does the Lavatory unit comply with ICC A117.1-2009, 1003.11.2.2? |
Building | 04/28/2022 | Rejected | Sheet A10.10, A10.11, A10.12: In Type B units, how does the Lavatory unit comply with ICC A117.1-2009, 1004.11.3.1.1? |
Building | 04/29/2022 | Rejected | Sheet G0.06 - Parking Tabulation: Are Visitor and Retail uses allowed to access level G1 and G2 and park in without any parking restrictions in visitor and retail assigned spaces? If there are parking restrictions now or in the future, then each group requires its own accessible parking spaces compliant with VCC Table 1106.1(1) and section 1106.5. |
Building | 04/29/2022 | Rejected | Sheet A2.01 & A2.02 - See markups G2 & G1 levels. How are you complying with VCC 1003.5? Changes in elevation less the 6” requires either handrails on both side or floor finish material contrast with adjacent floor finish materials. |
Building | 04/29/2022 | Rejected | Sheet A2.01 & A2.02 – Door B201 & B101 occur in a 2-hr fire rated Fire Barrier wall. Door rating 90 min required per VCC Table 716.5. Any glazed openings shall be fire-rated too in compliance with this table (VCC 109.3). |
Building | 04/29/2022 | Rejected | Sheet A9.31 – Please key (interior) window types to floor plans for cross reference (VCC 109.3). |
Building | 04/29/2022 | Rejected | Doors B205 & B106 occur in 2-hr rated walls accordingly 90 min door required VCC Table 716.5. |
Building | 04/29/2022 | Rejected | Sheet A2.01 & A9.10– See markups. Exhaust room appears to be 2hr rated and 90 min door listed on A9.10. Door number missing from plan. Check door number on A9.10 (VCC 109.3). |
Building | 04/29/2022 | Rejected | Sheet A2.02 – Door B104 occurs in a 2-hr fire rated Fire Barrier wall. Door rating 90 min required per VCC Table 716.5. |
Building | 04/29/2022 | Rejected | Sheet A2.10 – Room 113 is Mail room. Where does door #113 occur? |
Building | 04/29/2022 | Rejected | Sheet A9.10 – General Comment: See markups on door schedule. Please list Door names based on their Room Name without calling them Back of House or Parking etc. This helps expedite plan review time. |
Building | 04/29/2022 | Rejected | Sheet A2.10 & A9.11: Stair-C Doors XSTA-01 and XSTC-1 information not available on exterior door schedule. Please provide (VCC 109.3). |
Building | 04/29/2022 | Rejected | Sheet A2.10: See markup. Retail single swing door, door number appears to be missing (VCC 109.3). |
Building | 04/29/2022 | Rejected | Sheet A2.20, A2.23, A2.25: See markups. Please coordinate 3-bedroom exterior terrace door numbers with door schedule (VCC 109.3). |
Building | 04/29/2022 | Rejected | Sheet A2.26: What type of Maglock for Door X1726? Provide VCC Code section. Note that there are 6 conditions to comply with for a VCC 1010.1.9.8 door. How are you complying? |
Building | 04/29/2022 | Rejected | Sheet A9.11 and Door Hardware specifications: Please see markups. Exterior door schedule appears to be incomplete. Similar to other door numbers, you may want to coordinate important code related information between these documents and update comments column (VCC 109.3). |
Building | 04/29/2022 | Rejected | Sheet A9.11: ID door numbers missing hardware type information. Please provide (VCC 109.3). |
Building | 04/29/2022 | Rejected | Sheet A2.26: Please confirm Stair pressurization extent for Stair A. Is Stair Access Corridor pressurized too? (VCC 109.3). |
Building | 04/29/2022 | Rejected | Sheet A9.11: Unit door numbers missing hardware type information. Please provide (VCC 109.3). |
Building | 04/29/2022 | Rejected | Sheet A2.12: See markups. Balcony Door numbers missing (VCC 109.3). |
Building | 04/29/2022 | Rejected | As a general reminder, please cloud all revisions and provide delta number. Please provide a review comments response letter briefly addressing resolution for each open comment. Do not delete or change file names or numbers. Please note that this review cycle is complete. Additional comments may be forthcoming based on resubmission. |
Building | 04/29/2022 | Rejected | Sheet A2.01 & A2.02 - See markups G2 & G1 levels. How are you complying with VCC 1003.5? Changes in elevation less the 6” requires either handrails on both side or floor finish material contrast with adjacent floor finish materials. |
Building | 04/29/2022 | Rejected | Sheet A2.01 & A2.02 – Door B201 & B101 occur in a 2-hr fire rated Fire Barrier wall. Door rating 90 min required per VCC Table 716.5. Any glazed openings shall be fire-rated too in compliance with this table (VCC 109.3). |
Building | 04/29/2022 | Rejected | Sheet A9.31 – Please key (interior) window types to floor plans for cross reference (VCC 109.3). |
Building | 04/29/2022 | Rejected | Doors B205 & B106 occur in 2-hr rated walls accordingly 90 min door required VCC Table 716.5. |
Building | 04/29/2022 | Rejected | Sheet A2.01 & A9.10– See markups. Exhaust room appears to be 2hr rated and 90 min door listed on A9.10. Door number missing from plan. Check door number on A9.10 (VCC 109.3). |
Building | 04/29/2022 | Rejected | Sheet A2.02 – Door B104 occurs in a 2-hr fire rated Fire Barrier wall. Door rating 90 min required per VCC Table 716.5. |
Building | 04/29/2022 | Rejected | Sheet A2.10 – Room 113 is Mail room. Where does door #113 occur? |
Building | 04/29/2022 | Rejected | Sheet A9.10 – General Comment: See markups on door schedule. Please list Door names based on their Room Name without calling them Back of House or Parking etc. This helps expedite plan review time. |
Building | 04/29/2022 | Rejected | Sheet A2.10 & A9.11: Stair-C Doors XSTA-01 and XSTC-1 information not available on exterior door schedule. Please provide (VCC 109.3). |
Building | 04/29/2022 | Rejected | Sheet A2.10: See markup. Retail single swing door, door number appears to be missing (VCC 109.3). |
Building | 04/29/2022 | Rejected | Sheet A2.20, A2.23, A2.25: See markups. Please coordinate 3-bedroom exterior terrace door numbers with door schedule (VCC 109.3). |
Building | 04/29/2022 | Rejected | Sheet A2.26: What type of Maglock for Door X1726? Provide VCC Code section. Note that there are 6 conditions to comply with for a VCC 1010.1.9.8 door. How are you complying? |
Building | 04/29/2022 | Rejected | Sheet A9.11 and Door Hardware specifications: Please see markups. Exterior door schedule appears to be incomplete. Similar to other door numbers, you may want to coordinate important code related information between these documents and update comments column (VCC 109.3). |
Building | 04/29/2022 | Rejected | Sheet A9.11: ID door numbers missing hardware type information. Please provide (VCC 109.3). |
Building | 04/29/2022 | Rejected | Sheet A9.11: Unit door numbers missing hardware type information. Please provide (VCC 109.3). |
Building | 04/29/2022 | Rejected | Sheet A2.12: See markups. Balcony Door numbers missing (VCC 109.3). |
Building | 04/29/2022 | Rejected | As a general reminder, please cloud all revisions and provide delta number. Please provide a review comments response letter briefly addressing resolution for each open comment. Do not delete or change file names or numbers. Please note that this review cycle is complete. Additional comments may be forthcoming based on resubmission. |
Building | 06/28/2022 | Rejected | Sheet G0.06 - Parking Tabulation: Are Visitor and Retail uses allowed to access level G1 and G2 and park in without any parking restrictions in visitor and retail assigned spaces? If there are parking restrictions now or in the future, then each group requires its own accessible parking spaces compliant with VCC Table 1106.1(1) and section 1106.5. |
Building | 06/28/2022 | Rejected | Sheet A7.01: Please check if the Stair-A mechanical duct clears the minimum required headroom clearance (VCC 1011.3) and include a dimension on stair section 10/A7.01. |
Building | 06/28/2022 | Rejected | How does the Roof Terrace function for ADA access? Please provide enlarged sheet A3.58, balcony threshold detail per VCC 1010.1.7 and guardrail detail per VCC 1015. |
Building | 06/28/2022 | Rejected | Sheet A7.01 - Stair A: Please coordinate slab elevations shown on stair detail plans with Stair section view 10/A7.01. |
Building | 06/28/2022 | Rejected | Sheet A7.02 - Stair B: Similar to Stair A, please show me your stair landing elevations on stair detail plans and coordinate with section details 9, 10 and 11. |
Building | 06/28/2022 | Rejected | Sheet A7.02 – Stair B: See markup. Please check if concrete beam is obstructing stair pressurization duct path. SP-2 riser appears to be changing path between level 16 and PH. |
Building | 06/28/2022 | Rejected | Sheet G0.07: See markups on referenced code sections. Please be consistent in referencing VCC code sections as this has amendments to the IBC and at times the referenced sections may not match. |
Building | 06/28/2022 | Rejected | Sheet G0.06 - Parking Tabulation: It appears that a Zoning compliant parking count is provided for Residential, Residential visitor and Retail uses. Please note that while Zoning has their own parking requirements that are required to be complied with, that the VCC building code has its own parking requirements listed in “chapter 11 Accessibility” that’s also required to be complied with. Accordingly, accessible parking space requirement are derived using VCC, Table 1106.1(1). Please show how you’re proposing to comply with building code required accessible parking for the 3 functions listed above. Note that you’re first required to provide Van accessible space(s) for compliance with VCC 1106.5 (check and show required headroom clearance re |
Building | 06/28/2022 | Rejected | Sheet G0.06 - Parking Tabulation: Please see markup. Help me understand what you mean by “included in residential total”? - Are residential total parking 65 spaces? Using VCC Table 1106.1(1) and VCC 1106.5, please provide me a parking space breakdown for regular, compact, ADA car and ADA Van as applicable to the Residential, Visitor and Retail uses. |
Building | 06/28/2022 | Rejected | Sheet G0.06 - Parking Tabulation: A total of 4 accessible parking spaces are shown on plan (2 van and 2 car spaces). It appears that 2 accessible car spaces have access to “EV charging stations”. We encourage and support this route for providing EV accessible charging for equitable use. However, we do not want to limit the number of accessible parking spaces available for regular ADA use too. For example, an accessible needs person may not be driving an electric vehicle and may not require an EV space, but their parking needs have to be met too based on code required minimum number of spaces. As such we require that you first provide the minimum number of accessible parking required per building code per VCC Table 1106.1(1) and 1106.5, and |
Building | 06/28/2022 | Rejected | Sheet G0.06 – Unit Matrix Tabulation: VCC 1107.6.2.2.1 requires 2% Type-A units based on overall unit count and disbursed among the various unit classes. Building code appear to require 5 Type-A units (231 units x 0.02 = 5 Type-A min). Your matrix appears to show 12 Type-A units, which is acceptable. However, Type-A, 2 & 3-bedroom units appear to occur at the lower levels only and none are located beyond level 7 at higher levels. I’m concerned that these units don’t appear to be equitable disbursement since they may not receive comparable outside views or balcony access? |
Building | 06/28/2022 | Rejected | General Comment: Air-bone Sound - Wall, partitions and floor/ceiling assemblies separating dwelling units and sleeping units from each other or from the public or service areas shall have a Sound Transmission Class of not less than 50 STC, for air-borne noise when tested in accordance with ASTM E90. Please show me how are you addressing this code requirement? (2015 VCC, 1207.2) |
Building | 06/30/2022 | Rejected | Sheet A2.01: There are 8 exterior doors shown on plan. Please help me understand how many of these are building entrance doors and how they comply with VCC section 1105.1 which requires at least 60% of all public entrances to be accessible? ****************************************************************************************************************
06/30/3022: Common not fully addressed. Please coordinate slab elevations Civil drawings and list floor elevation at each exterior entrance door to building and show me how you are complying with VCC 1010.1.5. |
Building | 06/30/2022 | Rejected | Sheet G0.07 - Architectural Site Plan shows an aerial view of the proposed building and also shows the roof lines too. FSD is floor by floor and so it varies as plan moves in and out. And so this Site Plan is not helpful to determine FSD. Overall floor plans aren’t helpful to determine FSD since road and alley aren’t shown on them. You may want to filter line work and clearly show and tag building façades, Roads and Alley extent and dimension FSD.
*************************************************************************************************
06/30/2022: This comment shall remain open and resolved based on Civil Plan Set provided as part of this permit. |
Building | 06/30/2022 | Rejected | What is the large object shown inside the “West Meeting Room” (VCC 109.3). Enlarged plan A3.57 not provided for review. *********************************************************************************************************************
06/30/2022: Is the build in couch planned to have electrical power outlets/receptacles and USB outlets? None currently shown on the electrical drawings. Please confirm that it is your intent to have this built-in furniture piece built without power outlets. If power outlets are provided, then please note that we review such powered furniture like a wall. All framing for this built-in furniture piece shall be none-combustible metal or if framed with wood, it shall be FRT wood framing including any blocking |
Building | 06/30/2022 | Rejected | 06/30/2022: New Comment - See markups on Sheets A2.01 & A2.02. Please stripe ADA access aisle from accessible parking to elevator vestibule entrance. |
Building | 06/30/2022 | Rejected | Sheet A7-01 - STAIR A PLANS AND SECTIONS: 06/30/2022: New Comment - Please provide code complaint 2-hr rated duct enclosure detail (VCC 109.3). |
Building | 06/30/2022 | Rejected | Sheet A2-10 - FLOOR PLAN -LEVEL 01 (STREET LEVEL): 06/30/2022: New Comment - Stair-A. Please check Civil drawing elevation and coordinate threshold, and stair interior landing slab elevations (VCC 1010.1.5). |
Building | 06/30/2022 | Rejected | Sheet A2-10 - FLOOR PLAN -LEVEL 01 (STREET LEVEL): 06/30/2022: New Comment - See markup at exterior air intake louver. Louver is wider than intake shaft width and extends beyond the 2-hr rated shaft walls and is backed by a none-rated interior partition. Please coordinate fire ratings for walls and shaft louver size (VCC 109.3). |
Building | 06/30/2022 | Rejected | Sheet A6-11 - SECTION DETAILS -TOWER: 06/30/2022: New Comment - Details 8 & 10/A6.11, Glass Guardrail. Please specify on plan how you intend to comply with VCC 2407 including material and structural loads. Provide all relevant details on the plans including VCC 2407.1.1, 2407.1.2, 2407.1.4.1, 2407.1.4.2. |
Building | 06/30/2022 | Rejected | Sheet A3-11 - ENLARGED UNIT PLANS & RCPS -MICRO UNITS: 06/30/2022: New Comment - Micro Unit A, appears to not comply with VCC 1208.4 minimum required 220 sf floor area. We do not count the 30 inch equipment clearance in the kitchen. Corridor width is included in the minimum required area only if the face-of-wall to face-of-wall width is 7'-0" minimum similar to VCC 1208.1. You may want to take another look at updating the layout of this unit to comply with these minimum Code requirements. Please note that the area in front of the washer/dryer closet cannot be counted towards the minimum required 220 sf. |
Building | 07/01/2022 | Rejected | Sheets A2.01 & A2.02: Shows a garage exhaust shaft between gridlines CC-EE. The duct work for this appears to change direction and extends to another shaft at gridline AA. An exterior louver is shown on the East façade on sheet A4.02. Mechanical sheets M1.01 for G1 level shows fan access into exhaust shaft wall. Sheet M1.02 for G2 level shows duct with fire dampers leaving rated shaft and extending to plan North and connecting into a second exhaust shaft with fire dampers. Sheet M1.10 for level 1 shows shaft and exhausting out of the building north and east facades. With these conditions, it appears there will be a garage shaft poke down from level 01 floor and extending down through the slab to G1 so that the exhaust duct can tie back into |
Building | 07/01/2022 | Rejected | Sheet A2.10: Exterior exit doors (#101, X101) are not readily visible & identifiable from Stair B point of enclosure termination at door # STB-1. This condition appears to be non-compliant with VCC 1028.1, Exception 1, 1.1. To be code compliant all 4 conditions are required to be met. Please review and comply with code requirement. ********************************************************************************************************
06/30/2022: Comment not adequately addressed. Stair-B door STB-1 does not comply with VCC 1028.1, Exception #1, 1.1. Exterior exit doors are required to be "readily visible" from Stair-B "termination". Please resolve. |
Building | 07/01/2022 | Rejected | Sheet A2.10: Your Mail Room appears to exceed 100’ max., common path of travel. It also appears that Stair-C door # STC-1A cannot swing out into the Mail Room as this creates an occupant discharge back again into the building (which is not code compliant in an emergency). You may consider swinging this door into the stair and increasing the landing depth and creating a legal required exit from Mail room into Stair-C, which may help resolve the Mail Room dead-end issue also (VCC Table 1006.2.1, 1020.4).
******************************************************************************************************
06/30/2022: Comment not adequately addressed. Mailroom is considered a Business occupancy and exceeds 100'-0" common path of egress per |
Building | 07/01/2022 | Rejected | Sheet A3-12 - ENLARGED UNIT PLANS & RCPS -MICRO & JR 1 BED UNITS: 06/30/2022: New Comment - Micro Unit D, appears to not comply with VCC 1208.4 minimum required 220 sf floor area. We do not count the 30 inch equipment clearance in the kitchen. Corridor width is included in the minimum required area only if the face-of-wall to face-of-wall width is 7'-0" minimum similar to VCC 1208.1. You may want to take another look at updating the layout of this unit to comply with these minimum Code requirements. Please note that similar to Micro Unit A, the area in front of the washer/dryer closet and kitchen equipment clearance cannot to counted towards the minimum required 220 sf area. The remaining kitchen area cannot be considered contiguous to the |
Building | 07/01/2022 | Rejected | General Comment: ALL Efficiency Dwelling Units shall have a Living Room not less than 220 SF of floor area (VCC 1208.4). The corridor/passageway from the entrance door that leads into this space cannot be considered towards the minimum required floor area. Please check ALL the Efficiency Unit Floor Plans and ensure that they comply with the minimum required floor area code requirement.
Example: Micro A, Micro D, Micro D (Type A), JR 1 Bed A (Type A). ****************************************************************************************************
06/28/2022: Regardless of the terminology used for space naming, we review "Micro Units" as an "Efficiency Unit" aka "Studio Unit". All area(s) counted towards an Efficiency Unit’s minimum req |
Building | 07/01/2022 | Rejected | Sheet A2.26: Please confirm Stair pressurization extent for Stair A. Is Stair Access Corridor pressurized too? (VCC 109.3). *******************************************************************************************************************
06/30/2022: Stair access corridor 1712 appears to be an extension of Stair-A and is required to be pressurized based on VCC 1023.11. This is the only way that door 1712A is permitted provided into the exit passageway provided that it is pressurized the same way as the Stair, and 90 min., rating is provided for this door. Additionally exit remoteness between doors ID1714 and 1712B appears to be maintained by extending this exit passageway. Code compliance required as stated. |
Building | 07/01/2022 | Rejected | General Comment: Structure-borne Sound – How are you addressing the 50 STC minimum impact isolation class requirement between dwelling units and/or sleeping units per ASTM E492? (2015 VCC, 1207.03) |
Building | 07/01/2022 | Rejected | General Comment: Please provide Civil drawings for plan review reference. Please upload each sheet individually. *********************************************************************************************************************
06/30/2022: Comment not addressed adequately. Civil Plan Set required as part of this Permit. Please comply. |
Building | 07/01/2022 | Rejected | Sheet G0.07 - Is East side “Alley” a public or private alley? View 1/A4.22 appears to show majority of alley within property boundary. You may calculate fire separation distance to alley centerline only if it’s a public alley. A private alley does not count. See markups on “Exterior Partition Openings” table. Markups show allowable FSD percentage based on property line to east façade at ground floor. You may want to double check. ******************************************************************************************************
06/30/2022: Please provide Site "Plat" for this project. This comment shall remain open. |
DES/RE Vacation - Encroachment | 04/20/2022 | Rejected | Vacation and encroachment conditions haven't been met. |
DES:Engineering | 06/17/2022 | Approved | NEW 16 STORY BUILDING WITH POOL DFUS COUNTED AND APPROVED 2793.5 NEW DFUS CONFIRMED WITH APPLICANT CAN'T TELL IF CREDITS SHOULD BE APPLIED YET. NO LDA APPLIED FOR CAN'T TELL WHAT PROPOSED METER SIZE IS |
Electrical | 04/15/2022 | Rejected | Provide original seal and signature of the registered design professional (RDP), licensed to practice electrical engineering in the Commonwealth of Virginia. Section 111.1 of the Virginia Construction Code, and Section 54.1-410 of the Code of Virginia. When certifying a set of drawings, each page must be sealed, signed and dated. |
Electrical | 04/15/2022 | Rejected | Provide original seal and signature of the registered design professional (RDP), licensed to practice electrical engineering in the Commonwealth of Virginia. Section 111.1 of the Virginia Construction Code, and Section 54.1-410 of the Code of Virginia. When certifying a set of drawings, each page must be sealed, signed and dated. |
Electrical | 04/18/2022 | Rejected | Provide the ampere rating of the 'Integral Circuit Breaker' located in the Fire Pump Controller. Refer to the House Riser Diagram shown on sheet E5.01. Section 109.3 of the Virginia Construction Code. |
Electrical | 04/18/2022 | Rejected | Please provide clarity for transformers shown on the 'Transformer Schedule'. For example, there are 45kva transformers identified as 'XMFR Tag' -T45-A and T45-B' with different size secondary conductors. Transformer 'T-ELPH' rated for 45kva (located in the Penthouse), does not show an 'XMFR TAG' A or B. Please clarify for 'all' transformers shown on the 'Transformer Schedule' that have multiple 'XMFR TAGS' for various sizes of transformers. Refer to sheet E5.00. Section 109.3 of the Virginia Construction Code. |
Electrical | 04/18/2022 | Rejected | Panelboard 'SLG1', (PH) level located on the secondary side of a 30kva transformer requires a 'MCB'. The 'SLG1' directory shown on sheet E6-04 indicates 'MLO'. Please clarify. NEC Article 408.36 (B). Section 109.3 of the Virginia Construction Code. Also, see riser diagram shown on sheet E5.02. |
Electrical | 04/18/2022 | Rejected | The 'Panel Schedule Legend' shown on sheet E6-02, references a panelboard identified as 'H9M'. However, there is no such panelboard shown on the electrical riser diagram. Please clarify. Refer to sheet E5-01. |
Electrical | 04/18/2022 | Rejected | Provide the ampere rating of the 'Integral Circuit Breaker' located in the Fire Pump Controller. Refer to the House Riser Diagram shown on sheet E5.01. Section 109.3 of the Virginia Construction Code. |
Electrical | 04/18/2022 | Rejected | Please provide clarity for transformers shown on the 'Transformer Schedule'. For example, there are 45kva transformers identified as 'XMFR Tag' -T45-A and T45-B' with different size secondary conductors. Transformer 'T-ELPH' rated for 45kva (located in the Penthouse), does not show an 'XMFR TAG' A or B. Please clarify for 'all' transformers shown on the 'Transformer Schedule' that have multiple 'XMFR TAGS' for various sizes of transformers. Refer to sheet E5.00. Section 109.3 of the Virginia Construction Code. |
Electrical | 04/18/2022 | Rejected | Panelboard 'SLG1', (PH) level located on the secondary side of a 30kva transformer requires a 'MCB'. The 'SLG1' directory shown on sheet E6-04 indicates 'MLO'. Please clarify. NEC Article 408.36 (B). Section 109.3 of the Virginia Construction Code. Also, see riser diagram shown on sheet E5.02. |
Electrical | 04/18/2022 | Rejected | The 'Panel Schedule Legend' shown on sheet E6-02, references a panelboard identified as 'H9M'. However, there is no such panelboard shown on the electrical riser diagram. Please clarify. Refer to sheet E5-01. |
Electrical | 04/29/2022 | Rejected | Additional comments 'will' be forthcoming. |
Electrical | 04/29/2022 | Rejected | Additional comments 'will' be forthcoming. |
Electrical | 06/28/2022 | Rejected | Please clarify why the 'DOAS-1' in the Penthouse, is shown to be fed with 4/0 AL conductors and protected by a 350 ampere over current protection device. Refer to sheets E2.26P and E6-02. |
Electrical | 06/28/2022 | Rejected | Indicate on the drawings how the new electrical equipment for the 'EV' car chargers will be protected from physical damage as required. NEC Article 110.27(B) and 90.4. Refer to sheets E2.02P and E2.01P. Section 109.3 of the Virginia Construction Code. |
Electrical | 06/28/2022 | Rejected | The 'main' Grounding Electrode System Detail shown on sheet E5.00, shows the type(s) of grounding electrodes to be used. However, there is 'no' wire size provided on this detail for the 'Fire Pump' electrical service. Also, refer to the electrical riser diagram shown on sheet E5.01. Section 109.3 of the Virginia Construction Code. Please clarify. |
Electrical | 06/28/2022 | Rejected | On sheet E5.00, the 'Main Grounding Electrode System' detail references NEC Article 250.52 (A)(1) for the proper grounding of the metal underground water pipe. However, there is 'no' wire size provided. Provide the size of the grounding electrode conductor to be used for the metal underground water pipe. NEC Table 250.66 and Section 109.3 of the Virginia Construction Code. |
Electrical | 06/28/2022 | Rejected | Based on the lack of information provided in this 3rd review cycle (dated 6-3-2022), the above comments may not constitute a complete list of requested information. Additional design information is required for the county to review for code compliance. |
Energy | 05/02/2022 | Rejected | Sheet E0-04 - COMCHECK: EN-1) 05/02/22 For your information: The inspection checklist page portion of COMCHECK are not required to be provided. You may delete them or leave them. |
Energy | 05/02/2022 | Rejected | Sheet E0-04 - COMCHECK: EN-2) not used. |
Energy | 05/02/2022 | Rejected | Sheet E0-04 - COMCHECK: EN-3) 05/02/22 Please provide the COMCHECK lighting analysis for the garage lighting. Per section 109.4. You may run it separately, or as a different space type category (parking garage, not multifamily) of the rest of the interior lighting COMCEHCK analysis provided. Your choice. |
Energy | 05/02/2022 | Rejected | Sheet M-401 - SCHEDULES - MECHANICAL: EN-4) 05/02/22 Label “at AHRI TEST CONDITIONS” on the schedule the EER/IEER/COP. You may also list them at design conditions but you must identify which is which. Table 6.8.1-10. |
Energy | 05/02/2022 | Rejected | Sheet A4-11 - BUILDING SECTION -EAST_WEST (LOADING): EN-6) 05/02/22 – Clarify the intent of this “Min 6” batt insulation” cited on sheet A235, by indicating whether it is insulating the slab from above or below. The small portion of the slab appears to function as a “roof” over the 2 story retail space (restaurant). Despite not being exposed to precipitation, it would appear to be exposed to cold and hot temperatures of the outside air, as the only separation from the open air of the plaza appears to be the decorative wood ceiling above the decorative lights of the prow. Per Table 11.5.1, section 5. |
Energy | 05/02/2022 | Rejected | Sheet A2-35 - RCP -LEVEL 03: EN-7) 05/02/22 – See comment EN-6. |
Energy | 05/02/2022 | Rejected | Sheet A2-12 - FLOOR PLAN -LEVEL 03: EN-8) 05/02/22 – Clarify on the drawings what is going on with this space. I’m trying to ascertain the exposure to outside air temperatures, the need for required air barriers, and any thermal treatment of the slab at the floor of the 4th floor unit and at the ceiling of the 2 story retail space. Is this a wall? If so provide a wall type tag. Are these openings through the wall? If so, then label. The drawing seems to indicate a wall with openings, but that conflicts with the section cut. Per Table 11.5.1, section 5. |
Energy | 05/02/2022 | Rejected | Sheet A2-12 - FLOOR PLAN -LEVEL 03: EN-9) 05/02/22 – Clarify on the drawings the air barrier boundary of this “enclosed space”. Per section 5.4.3.1. |
Energy | 05/02/2022 | Rejected | Sheet A4-12 - BUILDING SECTION -EAST_WEST (RAMP): EN-10) 05/02/22 – Clarify on the drawings the thermal treatment of the garage ramp ceiling/2nd floor unit floor slab. Is this floor really not thermally treated with anything other than dead air space, according to the Level 1 RCP plan on A233? Per Table 11.5.1, section 5. |
Energy | 05/02/2022 | Rejected | Sheet A6-01 - SECTION DETAILS -BASE: EN-12) 05/02/22 Call out ALL air barrier on the building to be “continuous” for example, but not limited to, this detail. Per section 5.4.3.1. |
Energy | 05/02/2022 | Rejected | Sheet A6-02 - SECTION DETAILS -BASE: EN-13) 05/02/22 Here, and elsewhere throughout the details, call out the R-value of all insulations (exterior continuous and interior cavity of the building thermal envelope as well as soffit areas) as I do not find any typical wall /roof, floor details listing the R-value, or associated ID tags. Per Table 11.5.1., section 5. |
Energy | 05/02/2022 | Rejected | Sheet A6-03 - SECTION DETAILS -BASE: EN-14) 05/02/22 Call out the R-value of the insulation. Per Table 11.5.1., section 5. |
Energy | 05/02/2022 | Rejected | Sheet A2-34 - RCP -LEVEL 02: EN-15) 05/02/22 Provide a call out to the detail so I can confirm the insulation value intended here. Per Table 11.5.1., section 5, and section 109.4. |
Energy | 05/02/2022 | Rejected | Sheet E2-26L - LEVEL PH - LIGHTING: EN-16) 05/02/22 - These 3 lights appear to exceed the 150 watt limitation exclusion from daylighting zone definition and control requirements . Clarify with notes, and with a daylighting legend, the required PRIMARY and SECONDARY daylighting zone and associated daylighting controls. Per Table 9.6.1. Put on the drawing a depth dimension for each of the primary and secondary daylighting zones. |
Energy | 05/02/2022 | Rejected | Sheet E2-26L - LEVEL PH - LIGHTING: EN-17) 05/02/22 – Automatic full off is required. Per Table 9.6.1. |
Energy | 05/02/2022 | Rejected | Sheet E2-26L - LEVEL PH - LIGHTING: EN-18) 05/02/22 – Show the daylight photocell sensor on the plan. Per Table 9.6.1. |
Energy | 05/02/2022 | Rejected | Sheet E4-06 - ENLARGED AMENTIY AREA: EN-19) 05/02/22 – Make the distinction on the plans between the PRIMARY versus the SECONDARY daylighting control zones (include a depth dimension). The daylight (general lighting) controls in the secondary zone shall be independent of the daylight (general lighting) controls in the primary zone. Per section 9.4.1.1.e. |
Energy | 05/02/2022 | Rejected | EN-19) 05/02/22: Resubmission may result in additional comments. Please number your narrative responses with the identical EN-X number indicated in my comments. This significantly reduces the time required for review of your responses. Per VECC 109.4. If you have questions regarding this energy code review, you can contact me via email at lbaskerville@arlingtonva.us, or call on my mobile number 703-244-0479. |
Energy | 05/02/2022 | Rejected | Sheet A4-11 - BUILDING SECTION -EAST_WEST (LOADING): EN-5) 05/02/22 – Provide an RCP plan detail with notes, showing the underside of the 4th floor slab, specifically addressing the thermal treatment of this slab area which is directly above the open air plaza, even if no thermal treatment is intended. This area has not been addressed in the drawings, that I can find. There appears to be nothing separating the 4th floor unit’s floor slab from the outside air temperatures except a decorative wood ceiling , as indicated in 1/A251. Nor is it addressed on A235. Per section 109.4 and Table 11.5.1 section 5. |
Energy | 05/02/2022 | Rejected | Sheet E0-04 - COMCHECK: EN-1) 05/02/22 For your information: The inspection checklist page portion of COMCHECK are not required to be provided. You may delete them or leave them. |
Energy | 05/02/2022 | Rejected | Sheet E0-04 - COMCHECK: EN-2) not used. |
Energy | 05/02/2022 | Rejected | Sheet A4-11 - BUILDING SECTION -EAST_WEST (LOADING): EN-5) 05/02/22 – Provide an RCP plan detail with notes, showing the underside of the 4th floor slab, specifically addressing the thermal treatment of this slab area which is directly above the open air plaza, even if no thermal treatment is intended. This area has not been addressed in the drawings, that I can find. There appears to be nothing separating the 4th floor unit’s floor slab from the outside air temperatures except a decorative wood ceiling , as indicated in 1/A251. Nor is it addressed on A235. Per section 109.4 and Table 11.5.1 section 5. |
Energy | 05/02/2022 | Rejected | Sheet A4-11 - BUILDING SECTION -EAST_WEST (LOADING): EN-6) 05/02/22 – Clarify the intent of this “Min 6” batt insulation” cited on sheet A235, by indicating whether it is insulating the slab from above or below. The small portion of the slab appears to function as a “roof” over the 2 story retail space (restaurant). Despite not being exposed to precipitation, it would appear to be exposed to cold and hot temperatures of the outside air, as the only separation from the open air of the plaza appears to be the decorative wood ceiling above the decorative lights of the prow. Per Table 11.5.1, section 5. |
Energy | 05/02/2022 | Rejected | Sheet A2-35 - RCP -LEVEL 03: EN-7) 05/02/22 – See comment EN-6. |
Energy | 05/02/2022 | Rejected | Sheet A2-12 - FLOOR PLAN -LEVEL 03: EN-8) 05/02/22 – Clarify on the drawings what is going on with this space. I’m trying to ascertain the exposure to outside air temperatures, the need for required air barriers, and any thermal treatment of the slab at the floor of the 4th floor unit and at the ceiling of the 2 story retail space. Is this a wall? If so provide a wall type tag. Are these openings through the wall? If so, then label. The drawing seems to indicate a wall with openings, but that conflicts with the section cut. Per Table 11.5.1, section 5. |
Energy | 05/02/2022 | Rejected | Sheet A2-12 - FLOOR PLAN -LEVEL 03: EN-9) 05/02/22 – Clarify on the drawings the air barrier boundary of this “enclosed space”. Per section 5.4.3.1. |
Energy | 05/02/2022 | Rejected | Sheet A4-12 - BUILDING SECTION -EAST_WEST (RAMP): EN-10) 05/02/22 – Clarify on the drawings the thermal treatment of the garage ramp ceiling/2nd floor unit floor slab. Is this floor really not thermally treated with anything other than dead air space, according to the Level 1 RCP plan on A233? Per Table 11.5.1, section 5. |
Energy | 05/02/2022 | Rejected | Sheet A6-01 - SECTION DETAILS -BASE: EN-12) 05/02/22 Call out ALL air barrier on the building to be “continuous” for example, but not limited to, this detail. Per section 5.4.3.1. |
Energy | 05/02/2022 | Rejected | Sheet A6-02 - SECTION DETAILS -BASE: EN-13) 05/02/22 Here, and elsewhere throughout the details, call out the R-value of all insulations (exterior continuous and interior cavity of the building thermal envelope as well as soffit areas) as I do not find any typical wall /roof, floor details listing the R-value, or associated ID tags. Per Table 11.5.1., section 5. |
Energy | 05/02/2022 | Rejected | Sheet A6-03 - SECTION DETAILS -BASE: EN-14) 05/02/22 Call out the R-value of the insulation. Per Table 11.5.1., section 5. |
Energy | 05/02/2022 | Rejected | Sheet A2-34 - RCP -LEVEL 02: EN-15) 05/02/22 Provide a call out to the detail so I can confirm the insulation value intended here. Per Table 11.5.1., section 5, and section 109.4. |
Energy | 05/02/2022 | Rejected | Sheet E2-26L - LEVEL PH - LIGHTING: EN-16) 05/02/22 - These 3 lights appear to exceed the 150 watt limitation exclusion from daylighting zone definition and control requirements . Clarify with notes, and with a daylighting legend, the required PRIMARY and SECONDARY daylighting zone and associated daylighting controls. Per Table 9.6.1. Put on the drawing a depth dimension for each of the primary and secondary daylighting zones. |
Energy | 06/27/2022 | Rejected | Sheet E2-26L - LEVEL PH - LIGHTING: EN-17) 06/27/22 This comment has not been addressed. Where is the clarification on the drawings of the lighting controls, spelling out that automatic off is required? ****************************************************05/02/22 – Automatic full off is required. Per Table 9.6.1. |
Energy | 06/27/2022 | Rejected | Sheet E2-26L - LEVEL PH - LIGHTING: EN-18) 06/27/22 This comment has not been addressed. Clarify where the photosensors are on the plans, for the daylighting primary and secondary daylighting controls. *************************************************05/02/22 – Show the daylight photocell sensor on the plan. Per Table 9.6.1. |
Energy | 06/27/2022 | Rejected | Sheet E4-06 - ENLARGED AMENTIY AREA: EN-19) 06/27/22 This comment has not been addressed. *************************************05/02/22 – Make the distinction on the plans between the PRIMARY versus the SECONDARY daylighting control zones (include a depth dimension). The daylight (general lighting) controls in the secondary zone shall be independent of the daylight (general lighting) controls in the primary zone. Per section 9.4.1.1.e. |
Energy | 06/27/2022 | Rejected | EN-19) 06/27/22: Resubmission may result in additional comments. Please number your narrative responses with the identical EN-X number indicated in my comments. This significantly reduces the time required for review of your responses. Per VECC 109.4. If you have questions regarding this energy code review, you can contact me via email at lbaskerville@arlingtonva.us, or call on my mobile number 703-244-0479. |
Energy | 06/27/2022 | Rejected | Sheet E0-04 - COMCHECK: EN-3) 06/27/22 The requested information has not been provided. *************************************************05/02/22 Please provide the COMCHECK lighting analysis for the garage lighting. Per section 109.4. You may run it separately, or as a different space type category (parking garage, not multifamily) of the rest of the interior lighting COMCEHCK analysis provided. Your choice. |
Energy | 06/27/2022 | Rejected | Sheet M-401 - SCHEDULES - MECHANICAL: EN-4) 06/27/22 The requested EER/IEER/COP have NOT been provided at TEST conditions. I can only evaluate code compliance of the equipment at test conditions, so that I am comparing apples to apples. Provide the requested information. You have only identified that the values are at design conditions. *********************************************05/02/22 Label “at AHRI TEST CONDITIONS” on the schedule the EER/IEER/COP. You may also list them at design conditions but you must identify which is which. Table 6.8.1-10. |
Energy | 06/27/2022 | Rejected | Sheet .G0-00 - COVER SHEET: EN-20) 06/27/22: Include this note on the cover sheet of all your construction sets and on the permit set: “Energy Inspections are required for this project. Your first energy inspection will be for the air barrier. To set up your energy inspections, contact Linda Baskerville at 703-244-0479, or LBaskerville@arlingtonva.us, at least a month before the construction commences.” |
Energy | 06/27/2022 | Rejected | Sheet E4-06 - ENLARGED AMENTIY AREA: EN-22) Clarify, on the drawings, this symbol. It does not appear on the symbol legend on E001. Per 9.4.1.1.e. |
Environmental Services | 04/27/2022 | Rejected | Plans won't be fully approved until a LDA permit has been applied for an included in the permit application. |
Environmental Services | 04/27/2022 | Rejected | If possible, please provide a plumbing fixture count for the building for me to cross reference. The count will expedite the review process. Contact Aja at amoody@arlingtonva.us for any questions. |
Environmental Services | 04/27/2022 | Additional | Plans won't be fully approved until a LDA permit has been applied for an included in the permit application. |
Environmental Services | 04/27/2022 | Rejected | Plans won't be fully approved until a LDA permit has been applied for an included in the permit application. |
Environmental Services | 04/27/2022 | Rejected | If possible, please provide a plumbing fixture count for the building for me to cross reference. The count will expedite the review process. Contact Aja at amoody@arlingtonva.us for any questions. |
Environmental Services | 04/27/2022 | Additional | If possible, please provide a plumbing fixture count for the building for me to cross reference. The count will expedite the review process. Contact Aja at amoody@arlingtonva.us for any questions. |
Environmental Services | 06/28/2022 | Rejected | With no grading plan submitted please confirm the proposed size of the new water meter and whether the meter will be installed by the county or the developer |
Fire Prevention | 04/22/2022 | Approved | Sheet E2-02S - LEVEL G1 - SYSTEMS: Provide fire alarm interface for the fire pump system. Coordinate sprinkler system. Justify otherwise. |
Fire Prevention | 04/22/2022 | Approved | Sheet E2-10S - LEVEL 1 - SYSTEMS: Indicate panels detail in FCR room for clarity of review. |
Fire Prevention | 04/22/2022 | Approved | Sheet E2-11S - LEVEL 2 - SYSTEMS: Is the stair A Lobby? is open to the left as in bubble? If so how the pressurization be maintained or how the detection can be achieved. Provide clarification for review. |
Fire Prevention | 04/22/2022 | Approved | Sheet E2-27P - LEVEL PH ROOF - POWER: Provide fire alarm interface for the Generator that complies code. Justify otherwise. |
Fire Prevention | 04/22/2022 | Approved | Provide fire alarm riser diagram for review at this time. |
Fire Prevention | 04/22/2022 | Approved | Provide fire alarm sequence matrix mimic NFPA 72 2013 Fig. A.14.6.2 or justify |
Fire Prevention | 04/22/2022 | Approved | Expect more comments in future. |
Fire Prevention | 04/22/2022 | Approved | Sheet M-400 - SCHEDULES - MECHANICAL: The fan SPF-17-1 and 18-1 as shown is not reviewable at this time. Provide the following:
1. Check VCC section 909 of its entirety and include design, notes, assumptions as applicable and calculation how the fan was sized etc.
2. Check section 403.4.8 and provide standby power system and its related rated power connection as apply
3. Consult NFPA 92 applicable codes and design procedures as applicable that complies with VCC section 909
4. Calculation to be included within the drawing sheet along with riser diagram indicating duct size, fan size, injection point as chosen, exact location of stair (with name) shift and the volume must include whole path of egress to outside as shown on floor plan
5. |
Fire Prevention | 04/22/2022 | Rejected | Sheet E2-02S - LEVEL G1 - SYSTEMS: Provide fire alarm interface for the fire pump system. Coordinate sprinkler system. Justify otherwise. |
Fire Prevention | 04/22/2022 | Rejected | Sheet E2-10S - LEVEL 1 - SYSTEMS: Indicate panels detail in FCR room for clarity of review. |
Fire Prevention | 04/22/2022 | Rejected | Sheet E2-11S - LEVEL 2 - SYSTEMS: Is the stair A Lobby? is open to the left as in bubble? If so how the pressurization be maintained or how the detection can be achieved. Provide clarification for review. |
Fire Prevention | 04/22/2022 | Rejected | Sheet E2-27P - LEVEL PH ROOF - POWER: Provide fire alarm interface for the Generator that complies code. Justify otherwise. |
Fire Prevention | 04/22/2022 | Rejected | Provide fire alarm riser diagram for review at this time. |
Fire Prevention | 04/22/2022 | Rejected | Provide fire alarm sequence matrix mimic NFPA 72 2013 Fig. A.14.6.2 or justify |
Fire Prevention | 04/22/2022 | Rejected | Expect more comments in future. |
Fire Prevention | 04/22/2022 | Rejected | Sheet M-400 - SCHEDULES - MECHANICAL: The fan SPF-17-1 and 18-1 as shown is not reviewable at this time. Provide the following:
1. Check VCC section 909 of its entirety and include design, notes, assumptions as applicable and calculation how the fan was sized etc.
2. Check section 403.4.8 and provide standby power system and its related rated power connection as apply
3. Consult NFPA 92 applicable codes and design procedures as applicable that complies with VCC section 909
4. Calculation to be included within the drawing sheet along with riser diagram indicating duct size, fan size, injection point as chosen, exact location of stair (with name) shift and the volume must include whole path of egress to outside as shown on floor plan
5. |
Garage/Parking Review | 05/04/2022 | Rejected | Sheet A2-10 - FLOOR PLAN -LEVEL 01 (STREET LEVEL): Provide queue analysis at the garage entrances demonstrating that no vehicles are queuing within the public right of way. See https://topics.arlingtonva.us/building/parking-management-plan/ for more information on the requirements, guidelines and examples for the Queue Analysis |
Garage/Parking Review | 05/04/2022 | Rejected | Sheet A2-10 - FLOOR PLAN -LEVEL 01 (STREET LEVEL): Dimension the queue area in advance of the parking access and/or revenue control equipment excluding the public right of way. |
Garage/Parking Review | 05/04/2022 | Rejected | Sheet A2-02 - FLOOR PLAN -LEVEL G1: Please provide dimensions of the parking spaces and travel lanes. |
Garage/Parking Review | 05/04/2022 | Rejected | Sheet A2-10 - FLOOR PLAN -LEVEL 01 (STREET LEVEL): Provide queue analysis at the garage entrances demonstrating that no vehicles are queuing within the public right of way. See https://topics.arlingtonva.us/building/parking-management-plan/ for more information on the requirements, guidelines and examples for the Queue Analysis |
Garage/Parking Review | 05/04/2022 | Rejected | Sheet A2-10 - FLOOR PLAN -LEVEL 01 (STREET LEVEL): Dimension the queue area in advance of the parking access and/or revenue control equipment excluding the public right of way. |
Garage/Parking Review | 05/04/2022 | Rejected | Sheet A2-02 - FLOOR PLAN -LEVEL G1: Please provide dimensions of the parking spaces and travel lanes. |
Garage/Parking Review | 05/04/2022 | Additional | Sheet A2-02 - FLOOR PLAN -LEVEL G1: Please provide dimensions of the parking spaces and travel lanes. |
Garage/Parking Review | 05/04/2022 | Additional | Sheet A2-10 - FLOOR PLAN -LEVEL 01 (STREET LEVEL): Provide queue analysis at the garage entrances demonstrating that no vehicles are queuing within the public right of way. See https://topics.arlingtonva.us/building/parking-management-plan/ for more information on the requirements, guidelines and examples for the Queue Analysis |
Garage/Parking Review | 05/04/2022 | Additional | Sheet A2-10 - FLOOR PLAN -LEVEL 01 (STREET LEVEL): Dimension the queue area in advance of the parking access and/or revenue control equipment excluding the public right of way. |
Garage/Parking Review | 06/28/2022 | Rejected | Sheet A2-02 - FLOOR PLAN -LEVEL G1: Please provide dimensions of standard and compact parking spaces. |
Mechanical | 04/21/2022 | Rejected | Sheet M-102 - FLOOR PLAN - LEVEL G1 - MECHANICAL: Update architectural floor plan. |
Mechanical | 04/21/2022 | Approved | Sheet M-102 - FLOOR PLAN - LEVEL G1 - MECHANICAL: Update architectural floor plan. |
Mechanical | 04/21/2022 | Approved | Sheet M-102 - FLOOR PLAN - LEVEL G1 - MECHANICAL: Update architectural floor plan. |
Mechanical | 04/25/2022 | Approved | Please provide cleanouts regarding grease duct (KEF-1) per section 506.3.8 VMC2018 |
Mechanical | 04/25/2022 | Approved | Please provide illustrate compliance (CU-01) Condensing Units located in the garage parking area per section 303.4 VMC2018 |
Mechanical | 04/25/2022 | Approved | Provide exhaust rating for PET SPA or animal areas per section 403.2.1 and table 403.3.1.1 VMC2018
Further comments maybe forthcoming upon resubmission. |
Mechanical | 04/25/2022 | Approved | It appears the garage parking area architectural background doesn't match the drawings. |
Mechanical | 04/25/2022 | Approved | Please provide cleanouts regarding grease duct (KEF-1) per section 506.3.8 VMC2018 |
Mechanical | 04/25/2022 | Approved | Please provide illustrate compliance (CU-01) Condensing Units located in the garage parking area per section 303.4 VMC2018 |
Mechanical | 04/25/2022 | Approved | Provide exhaust rating for PET SPA or animal areas per section 403.2.1 and table 403.3.1.1 VMC2018
Further comments maybe forthcoming upon resubmission. |
Mechanical | 04/25/2022 | Approved | It appears the garage parking area architectural background doesn't match the drawings. |
Mechanical | 04/25/2022 | Rejected | Please provide cleanouts regarding grease duct (KEF-1) per section 506.3.8 VMC2018 |
Mechanical | 04/25/2022 | Rejected | Please provide illustrate compliance (CU-01) Condensing Units located in the garage parking area per section 303.4 VMC2018 |
Mechanical | 04/25/2022 | Rejected | Provide exhaust rating for PET SPA or animal areas per section 403.2.1 and table 403.3.1.1 VMC2018
Further comments maybe forthcoming upon resubmission. |
Mechanical | 04/25/2022 | Rejected | It appears the garage parking area architectural background doesn't match the drawings. |
Plumbing | 04/28/2022 | Rejected | 4-28-22 Please provide Civil sheets for plans set. |
Plumbing | 04/29/2022 | Rejected | 4-29-22 Pg P500.2 I've arrowed areas that I'm unsure what this drain is, seems to lower then rise, Running Vent, Please advise or correct. |
Plumbing | 04/29/2022 | Rejected | 4-29-22 Pg P005.2 Island vent connections incorrect, Please advise of Detail sheet Number |
Plumbing | 04/29/2022 | Rejected | 4-29-22 Review on going additional comments may follow |
Plumbing | 04/29/2022 | Rejected | 4-29-22 Pg P500.2 I've arrowed areas that I'm unsure what this drain is, seems to lower then rise, Running Vent, Please advise or correct. |
Plumbing | 04/29/2022 | Rejected | 4-29-22 Pg P005.2 Island vent connections incorrect, Please advise of Detail sheet Number |
Plumbing | 04/29/2022 | Rejected | 4-29-22 Review on going additional comments may follow |
Plumbing | 06/28/2022 | Rejected | 4-28-22 Please provide Civil sheets for plans set.
6-28-22 I looked thru all sheets and could not locate Civil Drawing please provide or advise sheet number/name |
Public Health Division | 04/20/2022 | Approved | Confirm a telephone capable of dialing the emergency number 9-1-1 will be provided by the owner and located within the swimming pool area, immediately accessible from the pool deck, with a clear and unobstructed view of the pool and with the emergency telephone number and facility's name and address posted by the telephone. |
Public Health Division | 04/20/2022 | Approved | If the pool is used after dark, confirm it will be equipped with shielded light fixtures that provide a minimum of 10-foot candles of light for the pool surface and 30-foot candles for the pool deck area measured six inches above the pool deck and water surface. |
Public Health Division | 04/20/2022 | Approved | Confirm that the pool will be completely enclosed with a perimeter fence, or equivalent barrier, at least six feet in height, measured from the highest ground elevation within three feet adjacent to the outside of the barrier and if horizontal surfaces are used that they are separated by a vertical distance greater than 45 inches and will prohibit the passage of a sphere larger than one and three-quarters inches in diameter through any opening of the enclosure, will be non-climbable from the outside of the enclosure with no handholds, footholds or other features that may aid in climbing the fence from outside the barrier with no objects within a six foot arc from the top of the fence. |
Public Health Division | 04/20/2022 | Approved | Confirm there will be a least one drinking fountain readily accessible to all patrons within the pool area. Please identify the location of the drinking fountain. |
Public Health Division | 04/20/2022 | Approved | Confirm the pool will be adequately secured to prevent unauthorized entry when not in use. |
Public Health Division | 04/20/2022 | Approved | Confirm the following placards will be posted:
a. Permanent and conspicuous signs indicating the most direct route to the pool.
b. A permanent, legible placard specifying facility rules and regulations regarding personal health and safety will be posted in plain view of patrons within the facility.
c. Confirm that the following information be posted at the entrance of the pool:
• If you have or have had diarrhea in the past two weeks, please do not use the pool.
• Shower your child and yourself before entering the pool or after using the toilet.
• Bathers who are not toilet trained or incontinent persons must wear a swim diaper.
• Do not drink pool water.
d. A permanent, water-proof, and durable sign in a location readily observable |
Public Health Division | 04/20/2022 | Approved | Confirm the following for the pool equipment room:
a. The room will be impervious to water and resistant to the chemicals necessary for the operation of the facility.
b. The floor will be designed to provide adequate drainage with a minimum floor slope of one to forty-eight and a maximum floor slope of one to twenty-four to the floor drain.
c. Will be provided with mechanical cross-ventilation.
d. There will be a minimum of two shielded light fixtures that will provide at least 30 foot-candles of illumination measured twenty-four inches above the floor at equipment and working areas.
e. The visible piping system will be marked with permanent tags, labels or markings to clearly identify the direction of flow and properly color coded.
f |
Public Health Division | 04/20/2022 | Approved | Confirm any person in the process of eating or drinking shall remain in an area designated for the consumption of food and drink. Confirm this area will be at least 10 feet from the swimming pool edge and that glass containers will not be permitted in the pool area. |
Public Health Division | 04/20/2022 | Approved | Show that the entrance to the pool equipment room is accessible from the pool deck so the pool operator can enter the room without having to exit the enclosed pool area. |
Public Health Division | 04/20/2022 | Rejected | Confirm emergency access will be provided at the entrance nearest the elevator or stairway leading to the pool. |
Public Health Division | 04/20/2022 | Rejected | Confirm that the deck will have a slope of not less than 1:48 or more than 1:24 and will be designed to conduct drainage away from the swimming pool in a manner that will not create a slip hazard or contribute to the ponding of water. Confirm that the pool deck will have a continuous deck at least five feet wide extending around the entire perimeter of the pool with the addition of deck furniture such as lounges, tables and chairs. |
Public Health Division | 04/20/2022 | Rejected | Confirm a telephone capable of dialing the emergency number 9-1-1 will be provided by the owner and located within the swimming pool area, immediately accessible from the pool deck, with a clear and unobstructed view of the pool and with the emergency telephone number and facility's name and address posted by the telephone. |
Public Health Division | 04/20/2022 | Rejected | If the pool is used after dark, confirm it will be equipped with shielded light fixtures that provide a minimum of 10-foot candles of light for the pool surface and 30-foot candles for the pool deck area measured six inches above the pool deck and water surface. |
Public Health Division | 04/20/2022 | Rejected | Confirm that the pool will be completely enclosed with a perimeter fence, or equivalent barrier, at least six feet in height, measured from the highest ground elevation within three feet adjacent to the outside of the barrier and if horizontal surfaces are used that they are separated by a vertical distance greater than 45 inches and will prohibit the passage of a sphere larger than one and three-quarters inches in diameter through any opening of the enclosure, will be non-climbable from the outside of the enclosure with no handholds, footholds or other features that may aid in climbing the fence from outside the barrier with no objects within a six foot arc from the top of the fence. |
Public Health Division | 04/20/2022 | Rejected | Confirm there will be a least one drinking fountain readily accessible to all patrons within the pool area. Please identify the location of the drinking fountain. |
Public Health Division | 04/20/2022 | Rejected | Confirm the pool will be adequately secured to prevent unauthorized entry when not in use. |
Public Health Division | 04/20/2022 | Rejected | Confirm the following placards will be posted:
a. Permanent and conspicuous signs indicating the most direct route to the pool.
b. A permanent, legible placard specifying facility rules and regulations regarding personal health and safety will be posted in plain view of patrons within the facility.
c. Confirm that the following information be posted at the entrance of the pool:
• If you have or have had diarrhea in the past two weeks, please do not use the pool.
• Shower your child and yourself before entering the pool or after using the toilet.
• Bathers who are not toilet trained or incontinent persons must wear a swim diaper.
• Do not drink pool water.
d. A permanent, water-proof, and durable sign in a location readily observable |
Public Health Division | 04/20/2022 | Rejected | Confirm the following for the pool equipment room:
a. The room will be impervious to water and resistant to the chemicals necessary for the operation of the facility.
b. The floor will be designed to provide adequate drainage with a minimum floor slope of one to forty-eight and a maximum floor slope of one to twenty-four to the floor drain.
c. Will be provided with mechanical cross-ventilation.
d. There will be a minimum of two shielded light fixtures that will provide at least 30 foot-candles of illumination measured twenty-four inches above the floor at equipment and working areas.
e. The visible piping system will be marked with permanent tags, labels or markings to clearly identify the direction of flow and properly color coded.
f |
Public Health Division | 04/20/2022 | Rejected | Confirm any person in the process of eating or drinking shall remain in an area designated for the consumption of food and drink. Confirm this area will be at least 10 feet from the swimming pool edge and that glass containers will not be permitted in the pool area. |
Public Health Division | 04/20/2022 | Rejected | Show that the entrance to the pool equipment room is accessible from the pool deck so the pool operator can enter the room without having to exit the enclosed pool area. |
Public Health Division | 04/20/2022 | Approved | Confirm emergency access will be provided at the entrance nearest the elevator or stairway leading to the pool. |
Public Health Division | 06/21/2022 | Approved | Confirm that the deck will have a slope of not less than 1:48 or more than 1:24 and will be designed to conduct drainage away from the swimming pool in a manner that will not create a slip hazard or contribute to the ponding of water. Confirm that the pool deck will have a continuous deck at least five feet wide extending around the entire perimeter of the pool with the addition of deck furniture such as lounges, tables and chairs. |
Structural | 05/02/2022 | Rejected | Special Inspections:
Please make sure to include the following when submitting the SS Packet
1. Owner, SER, SIER, GER, GC information. Including address, email, phone, and license number
2. Owner, SER, SIER signatures on the bottom of the pages
3. SER and SIER initials next to the items that will be inspected per the project scope
4. Signatures of the owner, SER, SIER, GER, and GC on the last two pages |
Structural | 05/02/2022 | Rejected | Additional comments may be forthcoming per the resubmittals |
Structural | 05/02/2022 | Approved | Please submit separate permits for both the sheeting and shoring and the foundation to grade |
Structural | 05/02/2022 | Approved | Please submit geotechnical report for review. The report shall have seal and signature |
Structural | 05/02/2022 | Approved | No longer accepting building code 2015. Please revise and make any changes to the loads, etc |
Structural | 05/02/2022 | Approved | Where will the pool be located on the penthouse
|
Structural | 05/02/2022 | Approved | Please schedule for a preconstruction meeting |
Structural | 05/02/2022 | Approved | Special Inspections: REJECTED.
Please submit the SSI packet on its own not on structural sheets. Also, missing pages and items.
See below for the link--
(1) The SSI shall cover the special inspection requirements for the completion of the project.
(2) All fields on the SSI must be completed. For irrelevant items, please mark N/A. All relevant items must be marked with the SIER/SER initials. For items not specified in the Statement, please write in the inspection in the field marked “other inspection” on page 59.
(3) The SSI shall be signed by the Structural Engineer of Record (SER), the Special Inspection Engineer of Record (SIER), General Contractor (GC), and owner on pages 60-61
There are two different statements for spec |
Structural | 05/02/2022 | Approved | Special Inspections:
Please make sure to include the following when submitting the SS Packet
1. Owner, SER, SIER, GER, GC information. Including address, email, phone, and license number
2. Owner, SER, SIER signatures on the bottom of the pages
3. SER and SIER initials next to the items that will be inspected per the project scope
4. Signatures of the owner, SER, SIER, GER, and GC on the last two pages |
Structural | 05/02/2022 | Approved | Additional comments may be forthcoming per the resubmittals |
Structural | 05/02/2022 | Rejected | Please submit separate permits for both the sheeting and shoring and the foundation to grade |
Structural | 05/02/2022 | Rejected | Please submit geotechnical report for review. The report shall have seal and signature |
Structural | 05/02/2022 | Rejected | No longer accepting building code 2015. Please revise and make any changes to the loads, etc |
Structural | 05/02/2022 | Rejected | Where will the pool be located on the penthouse
|
Structural | 05/02/2022 | Rejected | Please schedule for a preconstruction meeting |
Structural | 05/02/2022 | Rejected | Special Inspections: REJECTED.
Please submit the SSI packet on its own not on structural sheets. Also, missing pages and items.
See below for the link--
(1) The SSI shall cover the special inspection requirements for the completion of the project.
(2) All fields on the SSI must be completed. For irrelevant items, please mark N/A. All relevant items must be marked with the SIER/SER initials. For items not specified in the Statement, please write in the inspection in the field marked “other inspection” on page 59.
(3) The SSI shall be signed by the Structural Engineer of Record (SER), the Special Inspection Engineer of Record (SIER), General Contractor (GC), and owner on pages 60-61
There are two different statements for spec |
Zoning | 04/28/2022 | Rejected | At sheets A2-01 and A2-02. The number of standard parking spaces (not visitor) shown on the plans at G1 level is 12, not 14. Update the tabulation with 12 spaces instead of 14. |
Zoning | 04/28/2022 | Rejected | Provide a detail with the different type of parking spaces with the dimensions according to the Arlington County Zoning Ordinance. |
Zoning | 04/28/2022 | Rejected | On sheets A2-01 and A2-02, the bicycle tabulation at G2 level doesn't match the number shown on the drawing. Verify the total once the tabulation is updated. |
Zoning | 04/28/2022 | Rejected | On sheet A2-10 provide the loading docks dimensions, including the height clearance according to site plan condition #30. |
Zoning | 04/28/2022 | Rejected | Provide details that the area of the alley that connects Wilson Blvd. and Clarendon Blvd. it is designed in order to resist the weight of an emergency vehicle. |
Zoning | 04/28/2022 | Rejected | Add the following Zoning standard note on sheets M-101, M-102, P-101 and P-102:
“All mechanical, electrical and plumbing work, including but not limited to, ductwork, piping, fans, equipment, switches and sensors shall be installed so as not to encroach into required dimensions of parking spaces including height, width, stale and drive aisle. A minimum height clearance of 98 inches for handicap van and vanpool spaces and 84 inches for all other spaces must be maintained at all-time including the drive aisles and garage entrances used to navigate to those spaces.” |
Zoning | 04/28/2022 | Rejected | At sheets A2-01 and A2-02. The number of standard parking spaces (not visitor) shown on the plans at G1 level is 12, not 14. Update the tabulation with 12 spaces instead of 14. |
Zoning | 04/28/2022 | Rejected | The proposed 21 compact spaces represent a 28% ratio of compact spaces. On the County Board report it was approved a 26%, which represent 19 compact spaces. This proposed increase could represent that a site plan amendment will be required to allow this increase on the number of compact parking spaces. |
Zoning | 04/28/2022 | Rejected | Provide a detail with the different type of parking spaces with the dimensions according to the Arlington County Zoning Ordinance. |
Zoning | 04/28/2022 | Rejected | On sheets A2-01 and A2-02, the bicycle tabulation at G2 level doesn't match the number shown on the drawing. Verify the total once the tabulation is updated. |
Zoning | 04/28/2022 | Rejected | On sheet A2-10 provide the loading docks dimensions, including the height clearance according to site plan condition #30. |
Zoning | 04/28/2022 | Additional | The proposed 21 compact spaces represent a 28% ratio of compact spaces. On the County Board report it was approved a 26%, which represent 19 compact spaces. This proposed increase could represent that a site plan amendment will be required to allow this increase on the number of compact parking spaces. |
Zoning | 04/28/2022 | Additional | At sheets A2-01 and A2-02. The number of standard parking spaces (not visitor) shown on the plans at G1 level is 12, not 14. Update the tabulation with 12 spaces instead of 14. |
Zoning | 04/28/2022 | Additional | Provide a detail with the different type of parking spaces with the dimensions according to the Arlington County Zoning Ordinance. |
Zoning | 04/28/2022 | Additional | On sheet A2-10 provide the loading docks dimensions, including the height clearance according to site plan condition #30. |
Zoning | 04/28/2022 | Rejected | Add the following Zoning standard note on sheets M-101, M-102, P-101 and P-102:
“All mechanical, electrical and plumbing work, including but not limited to, ductwork, piping, fans, equipment, switches and sensors shall be installed so as not to encroach into required dimensions of parking spaces including height, width, stale and drive aisle. A minimum height clearance of 98 inches for handicap van and vanpool spaces and 84 inches for all other spaces must be maintained at all-time including the drive aisles and garage entrances used to navigate to those spaces.” |
Zoning | 04/28/2022 | Rejected | Provide details that the area of the alley that connects Wilson Blvd. and Clarendon Blvd. it is designed in order to resist the weight of an emergency vehicle. |
Zoning | 04/28/2022 | Additional | On sheets A2-01 and A2-02, the bicycle tabulation at G2 level doesn't match the number shown on the drawing. Verify the total once the tabulation is updated. |
Zoning | 04/28/2022 | Additional | Provide details that the area of the alley that connects Wilson Blvd. and Clarendon Blvd. it is designed in order to resist the weight of an emergency vehicle. |
Zoning | 04/28/2022 | Additional | Add the following Zoning standard note on sheets M-101, M-102, P-101 and P-102:
“All mechanical, electrical and plumbing work, including but not limited to, ductwork, piping, fans, equipment, switches and sensors shall be installed so as not to encroach into required dimensions of parking spaces including height, width, stale and drive aisle. A minimum height clearance of 98 inches for handicap van and vanpool spaces and 84 inches for all other spaces must be maintained at all-time including the drive aisles and garage entrances used to navigate to those spaces.” |
Zoning | 04/29/2022 | Additional | At the time of the review a Post 4.1 have not been submitted. More comments could be made once the Post 4.1 is submitted and a second review of this building permit is completed. |
Zoning | 04/29/2022 | Additional | Provide evidence of any safety measure to be installed at the garage exit for the protection of pedestrians according to site plan condition #40. |
Zoning | 04/29/2022 | Rejected | Provide evidence of any safety measure to be installed at the garage exit for the protection of pedestrians according to site plan condition #40. |
Zoning | 04/29/2022 | Rejected | At the time of the review a Post 4.1 have not been submitted. More comments could be made once the Post 4.1 is submitted and a second review of this building permit is completed. |
Zoning | 04/29/2022 | Rejected | Provide evidence of any safety measure to be installed at the garage exit for the protection of pedestrians according to site plan condition #40. |
Zoning | 04/29/2022 | Rejected | At the time of the review a Post 4.1 have not been submitted. More comments could be made once the Post 4.1 is submitted and a second review of this building permit is completed. |
Zoning | 06/21/2022 | Rejected | The proposed 21 compact spaces represent a 28% ratio of compact spaces. On the County Board report it was approved a 26%, which represent 19 compact spaces. This proposed increase will represent that a site plan amendment will be required to allow this increase on the number of compact parking spaces. |
Zoning | 06/24/2022 | Rejected | The tabulation on sheet G0.06 shows the maximum allowed retail square footage of 3,500 ft². But on the Garage Plan & Queue Analysis included on the second review cycle it is showing a retail square footage of 4,604 ft². Provide information about this discrepancy. Any increase on the retail square footage above the 3,500 ft² will require a site plan amendment approved by the County Board. |
Zoning | 06/24/2022 | Rejected | On sheet G1-02 it is showing a retail space of 3,534 ft². The maximum retail space is 3,500 ft² in order to avoid a site plan amendment. |