COMMERCIAL PLAN REVIEW |
All projects are reviewed under the requirements outlined in the Virginia Uniform Statewide Building Code. A written response letter must accompany plan revisions. Please contact the Plans Examiner for any clarification of the comments. |
|
Permit #: B1900393 Applicable Code: VUSBC 2012 Edition |
Project Name : Plans Examiner: Mohamed Ghiwane |
Address: 3101 Wilson Blvd Discipline: Building |
Review Date: 02/21/19 Phone Number: 703-228-0578 |
Review #: 1st Fax Number: 703-228-7046 |
Revision Date: NA Email: mghiwane@arlingtonva.us |
|
Sheet Comments Code Reference |
1. A1.0 An accessible family or assisted-use bathing room shall be provided Section 1109.2.1 |
2. A1.0 Doors 114 and 105 at men and women's accessible toilet compartment shall not swing into the required minimum area of the compartment. Section 604.9.3 of the 2009 ICC A117.1 |
3. A1.0 Transfer type shower must be exactly 36" wide and 36" deep. Section 608.2.1.1 of the 2009 ICC A117.1 |
4. A1.0 A clearance of 48" minimum in length measured perpendicular from the control wall shall be provided. Please note that forward approach is not permitted in this case. Section 608.2.1.2 of the 2009 ICC A117.1 |
5. C-0 Occupant load at locker rooms shall be calculated at 50 SF/Occp. Please revise. Table 1004.1.2 |
6. A1.0 Please clarify what is the use of VO2 Max 104 and CRYO 115 rooms. Also, please specify the occupant load factor used for each room. |
7. A1.0 It appears to be that the partition at men's accessible toilet compartment extends all the way to the floor. In this case the accessible toilet compartment shall be 66" x 62" if wall-hung water closet or 66"x 65" if floor mounted water closet is used. Section 604.9.2 of the 2009 ICC A117.1. |
8. A1.0 Infrared Sauna 114 must be accessible. Please provide a clear floor space complying with Section 304.3 of the 2009 A117.1. Section 1109.6 |
9. A1.0 Please provide elevation details for the reception desk and show compliance with Section 904 of the 2009 ICC A117.1. |
10. A1.0 A bench complying with Section 903 of the 2009 ICC A117.1 is required at both locker rooms. Section 803.4 of the 2009 ICC A117.1. |
11. More comments can be generated during next review. |
|