COMMERCIAL PLAN REVIEW |
All projects are reviewed under the requirements outlined in the Virginia Uniform Statewide Building Code. A written response letter must accompany plan revisions. Please contact the Plans Examiner for any clarification of the comments. |
|
Permit #: B1900393 Applicable Code: VUSBC 2012 Edition |
Project Name : Plans Examiner: Mohamed Ghiwane |
Address: 3101 Wilson Blvd Discipline: Building |
Review Date: 02/21/19 Phone Number: 703-228-0578 |
Review #: 2nd Fax Number: 703-228-7046 |
Revision Date: NA Email: mghiwane@arlingtonva.us |
|
Sheet Comments Code Reference |
1. A1.0 An accessible family or assisted-use bathing room shall be provided. ************************ 03/19/19 The family assisted-use bathing room shall include an accessible shower or bathtub fixture as well as an accessible water closet and lavatory as required per Section 1109.2.1.3. Section 1109.2.1 |
2. A1.0 Doors 114 and 105 at men and women's accessible toilet compartment shall not swing into the required minimum area of the compartment. **************** 03/19/19 Resolved. Section 604.9.3 of the 2009 ICC A117.1 |
3. A1.0 Transfer type shower must be exactly 36" wide and 36" deep. **************** 03/19/19 Resolved. Section 608.2.1.1 of the 2009 ICC A117.1 |
4. A1.0 A clearance of 48" minimum in length measured perpendicular from the control wall shall be provided. Please note that forward approach is not permitted in this case. **************** 03/19/19 Resolved. Section 608.2.1.2 of the 2009 ICC A117.1 |
5. C-0 Occupant load at locker rooms shall be calculated at 50 SF/Occp. Please revise. **************** 03/19/19 It appears to be that men's and women's locker rooms is more than 173 SF (it's actually more than 1000 SF). Please revise. Table 1004.1.2 |
6. A1.0 Please clarify what is the use of VO2 Max 104 and CRYO 115 rooms. Also, please specify the occupant load factor used for each room. **************** 03/19/19 Resolved. |
7. A1.0 It appears to be that the partition at men's accessible toilet compartment extends all the way to the floor. In this case the accessible toilet compartment shall be 66" x 62" if wall-hung water closet or 66"x 65" if floor mounted water closet is used. **************** 03/19/19 Resolved. Section 604.9.2 of the 2009 ICC A117.1. |
8. A1.0 Infrared Sauna 114 must be accessible. Please provide a clear floor space complying with Section 304.3 of the 2009 A117.1. **************** 03/19/19 Resolved. Section 1109.6 |
9. A1.0 Please provide elevation details for the reception desk and show compliance with Section 904 of the 2009 ICC A117.1. **************** 03/19/19 Resolved. |
10. A1.0 A bench complying with Section 903 of the 2009 ICC A117.1 is required at both locker rooms. **************** 03/19/19 Please provide elevation details for the accessible benches to show compliance with Section 803.4 & 903 of the 2009 ICC A117.1. Section 803.4 of the 2009 ICC A117.1. |
11. A1.0 03/19/19 The family bathing room shall have a separate access without passing through the men's and women's locker rooms. |
12. A1.0 03/19/19 Please clarify what is the use of the octagon shape element in SPA 115. If this is a jacuzzi (or a water vessel that can host a person) then it must be accessible. Section 1109.1.3 of the 2009 ICC A117.1. |
13. A1.0 03/19/19 Based on the exit signs (Sheet E-1.0) and the occupant load served, door 116 must swing in into room 118. Section 1008.1.2 |
14. A1.0 03/19/19 Both existing entry and back exit doors must be provided with panic hardware. Please show on the plan that these doors are equipped with panic hardware. Section 1008.1.10 |
15. More comments can be generated during next review. |
|