Review | Electrical |
Review Date | 09/20/2017 |
Status | Rejected |
Comments |
COMMERCIAL PLAN REVIEW | All projects are reviewed under the requirements outlined in the Virginia Uniform Statewide Building Code. A written response letter must accompany plan revisions. Please contact the Plan Examiner for any clarification of the comments. A detailed correction letter must be attached to the drawings for re-submittal. | | Permit: B1702047 Applicable Code: 2012 VUSBC | Project: Gyu Kaku Plan Examiner: Williams | Address: 1119 N Hudson Street Discipline: Electrical | 2nd Review Date: | 9-20-17 | | | | | Phone Number: | Email: 703-228-3973 | Crawilliams@arlingtonva.us | | | | | | | | Sheet Comments Code Reference | | | | | | 1 | E1.1, E00 | Now that the 'existing' main electrical service equipment has been added to the floor plan, there appears to be approximately 10-20' (including bending radius'), of 'unfused' service entrance conductors located inside of the building to feed 'new' panel board 'B'. Service entrance conductors are 'required' to be terminated in a service disconnect means at the "nearest point of entrance of the service conductors". NEC Article 230.70 (A) (1) and 90.4. 109.3 of the Virginia Construction Code | 2 E1.1, E00 | Additional design information is required for the county to review for code compliance. Additional comments may be forthcoming. 109.3 of the Virginia Construction Code | |
|