Review | Electrical |
Review Date | 07/03/2019 |
Status | Rejected |
Comments |
COMMERCIAL PLAN REVIEW | All projects are reviewed under the requirements outlined in the Virginia Uniform Statewide Building Code. A written response letter must accompany plan revisions. Please contact the Plan Examiner for any clarification of the comments. A detailed correction letter must be attached to the drawings for re-submittal. | | Permit: B1901790 Applicable Code: 2012 VUSBC | Project: Orange Plan Examiner: Williams | Address: 4231 Columbia Pike Suite 106 Discipline: Electrical | Review Date: | 7-3-19 | | | | | | | Phone Number: | Email: 703-228-3973 | Crawilliams@arlingtonva.us | | | | | | | | | | | 1 | E-1 Indicate on the drawings how this 'new' 200 ampere Electrical Service will be properly grounded. Provide the size of the grounding electrode conductor and the type(s) of grounding electrode(s). NEC Article 250.20 (B), 250.24 (A)(1), and 90.4. 109.3 of the Virginia Construction Code | | 2 | E-1 Please clarify on the drawings whether, this 'new' 200 ampere Electrical Service is the only service on the existing 1500 ampere Retail Service. 109.3 of the Virginia Construction Code | 3 Based on the lack of information provided, additional comments may be forthcoming. 109.3 of the Virginia Construction Code | |
|