Review | Accessibility Review |
Review Date | 02/19/2019 |
Status | Rejected |
Comments |
COMMERCIAL PLAN REVIEW | All projects are reviewed under the requirements outlined in the Virginia Uniform Statewide Building Code. A written response letter must accompany plan revisions. Please contact the Plan Examiner for any clarification of the comments. | | Permit #: B1900393 Applicable Code: VUSBC 2012 Edition | Project Name: Formula Running Center Plan Examiner: Chris Martin | Address: 3101 Wilson Blvd Discipline: Accessibility | Review Date: 2/19/19 Phone Number: 703-228-3854 | Review #: 1st Fax Number: 703-228-7046 | Revision Date: Email: cmmartin@arlingtonva.us | | Sheet Comments Code Reference | Accessibility plan review comments | 1 A-1.0 Transfer showers shall be 36 inches x 36 inches ANSI 608.2.1.1 | 2 A-1.0 A clearance of 48 inches (1220 mm) minimum in length measured perpendicular from the control wall, and 36 inches (915 mm) minimum in depth shall be provided adjacent to the open face of the compartment. ANSI 608.2.1.2 | 3 A-1.0 The front partition and at least one side partition shall provide a toe clearance of 9 inches (230 mm) minimum above the floor and extending 6 inches (150 mm) beyond the compartment side face of the partition, exclusive of partition support members. ANSI 604.9.5.1 | Further comments may be forthcoming upon plan resubmission. | |
|