ReviewPlumbing
Review Date03/21/2016
StatusApproved
Comments
- Grease interceptors shall only receive waste from fixtures and equipment that allow fats and oils or grease to be discharged. Seems multi appliances are draining into the Grease Interceptor please revise or correct. -Fixture and appliances shall be dictated by 2012 IPC 1003.3.1.
-Provide complete gas piping detail to include material, total BTU, and all retailed information. 2012 IFGC 402..
-IFGC 408.4 Provide valve at all sediment trap locations.
-Please show all sinks for general hand sanitization shall be equipped with mixing valves 1070 per 2012 IPC.