Review | Building |
Review Date | 12/22/2016 |
Status | Approved |
Comments |
Sheet A110. An elevator is required for a level over 3,000 sf. I calculate the floor area to be about 3,300 sf. VCC 1104.4 | | 10/13/16 This is a gross floor area calculation that includes the restrooms, janitor's closet, built-in furniture (i.e., bar) and landings of open stairways. It is not clear how you are calculating the floor area at less than 3,000 sf. | | 12/22/16 Note that the roof area of 3,000 sf. meets the requirements of the Virginia Construction Code, but may not meet the requirements of the Americans with Disabilities Act. Comment is resolved in accordance with the VCC. |
|