Review | Energy |
Review Date | 06/23/2016 |
Status | Approved |
Comments |
Sheet 0009 includes a door schedule that specifies several new doors that are part of the building thermal envelope. These doors are shown on the plans as Door 200, 201, 201A 203 and 204. Table C402.2 of the 2012 Virginia Energy Conservation Code requires that these doors have a maximum U-factor of not more than U-0.61. In the resubmission, include an additional column in the door schedule that indicates the maximum U-factor for doors 200, 201, 201A 203 and 204. |
|