Review | Energy |
Review Date | 06/27/2016 |
Status | Approved |
Comments |
The drawings include several lighting schedules on different sheets. These schedules do not list the total input power of each lighting fixture type. The schedules must list the total input power of each fixture type, including existing fixtures to remain for all spaces where new fixtures will be installed. In the resubmission include an additional column for each lighting schedule that lists the total input power for each fixture. Coordinate this power with the power reported in the Interior Lighting COMcheck. |
|