Review | Building |
Review Date | 06/07/2017 |
Status | Approved |
Comments |
Sheet I-1103 DOOR SCHEDULE AND TYPE: NOT RESOLVED: | Provide evidence that the Concealed Rod panic Device installed on each of the exterior exit doors comply with Section 1008.1.10 of the VCC 2012 which requires: | 1- Panic hardware be listed with UL 305. | 2- The actuating portion of the releasing device shall extend at least one-half of the door leaf. | 3- The maximum unlatching force shall not exceed 15 pounds (67 N). | | |
|