Review | Building |
Review Date | 07/13/2018 |
Status | Approved |
Comments |
Sheet A-101 CODE PLAN: Please note that if restroom doors are provided with a closer and latch, 48" maneuvering clearance will be required at the push side of the doors, Section 404.2.3.2 of the 2009 ICC A117.1. FYI, closers are always required at food establishments by the Health department.*************** 06/26/18 As previously mentioned, a closer is required by the health department requirement. Therefore 48" maneuvering clearance is required from the push side. Please show on the plan that a 48" maneuvering clearance is provided.************** 07/13/18 It appears to be that the lavatory encroaches in the minimum required 48" clearance. Please show on the plan the required maneuvering clearance for the restroom doors. |
|