Sheet P002 indicates that a 119 gallon tank-type electric water heater is part of the scope of the permit. The plans do not state the maximum allowable % per hour heat loss of the water heater. The 2015 Virginia Energy Conservation Code (VECC) Table C404.2 requires a maximum allowable heat loss of 0.53% per hour or less.
In the resubmission, state the maximum allowable % per hour heat loss for the water heater in the electric storage water heater schedule.