Permit Comments Details
 

 

 
ReviewEnergy
Review Date05/13/2019
StatusApproved
Comments
EN-2) comment dated 5-13-19: Sheet A202, Note 8 - State in note 8, for the new infill wall areas, that new air barrier shall be provided to be made continuous with existing air barrier, per Virginia Rehab Code (VRC) section 403.1 General - Alterations shall be such that the existing building or structure is no less conforming to the provisions of the International Building Code than the existing building or structure was prior to the alteration.