Permit Comments Details
 
Permit #B1902211
Address4060 CAMPBELL AVE
TypeComm Int Alt
StatusFINALED
Permit HolderK B R CORPORATION
OwnerSTREET RETAIL INC DIR OF PROP ANALYSIS
Applied Date08/09/2019
Approved Date11/19/2019
Date Issued11/19/2019
DescriptionINTERIOR ALTERATIONS TO EXISTING CVS STORE AND EXTERIOR FACADE RENOVATIONS - APPROVED ADMIN CHANGE - ZADM190408. SPECIAL INSPECTIONS REQUIRED.

 

 
ReviewEnergy
Review Date10/22/2019
StatusApproved
Comments
EN-6) comment dated 10-22-19: The previous comment has not been addressed.
********************************************
EN-6) comment dated 9-24-19: The Comcheck analysis is not correctly filled out. You selected the space by space method and associated wattage value for the retail sales area (1.6 w/sf), but applied a much larger square footage than the retail area SF listed on the cover sheet (10K rather than 7K SF) and you did not itemize the other areas of the project nor apply their specific wattage allowances from section C405.5.2. This grossly overstates the wattage allowance allowed for your lighting plan. When using the space by space method, and associated wattage allowance values, you need to apply only the square footage that matches the square footage on the code summary sheet for each area, and include all different project areas in the space by space analysis (except for the walk-in coolers). Or you may select the building area method and associated wattage value (1.4 w/sf) and include the total SF for the project without having to list each area separately. But you then need to select the correct wattage and category associated with the building area type. Retail would be an acceptable category but the w/sf would be 1.4 rather than 1.6. Revise and resubmit Comcheck interior lighting analysis.
***************************************************************EN-6) comment dated 8-23-19: Provide a stamped and signed Interior Lighting Comcheck analysis for this project. The wquare footage shall match the square footage listed in the code summary The Comcheck analysis shall demonstrate a PASS. Copy the stamped and signed Interior Lighting Comcheck onto the full size permit submission drawings, and include it on the sheet index as ‘Lighting Comcheck’. Label the light fixtures names on the lighting Comcheck with the same names and the same wattages as indicated on the light fixture schedule. Make sure you select the same code standard and year as in
the project code summary. Per VECC 109.4, and section C405.5.2.