Review | Building |
Review Date | 04/30/2021 |
Status | Approved |
Comments |
Sheet A-003 Reflected Ceiling Plan: General Comment: See markup. Your Reception Desk at the Sushi Bar arrears to be a Built-in Furniture piece with electrical outlets Built-in to it. We review powered furniture such as this like a Wall Partition. All wood blocking installed within the framing cavity shall be Fire-Retardant Treated (FRT) Wood and its enclosure shall be a Noncombustible Surface such as FRT Plywood or Gyp.BD., for compliance with VCC, Section 603.1.1 #1.1; as required for Types I & II Construction. Additional finish material shall be installed over the Noncombustible Surface and comply with VCC, Table 803.11 Finish Requirements. |
|