Review | Building |
Review Date | 12/06/2021 |
Status | Approved |
Comments |
Your code analysis does not mention the number of stories. It appears to be a two story structure. You indicate the use to be A-2 for the ground level which is under going this renovation. With no separation between the stories/uses, A-2 un-sprinklered is limited to one story. That being said, for fire separation purposes VCC 303.1.1 allows your space to be classified as a B. Please show this modification to a B use in your code analysis. I also noticed your Accessibility form needs to be corrected .Feel free to reach out with any questions. | Chuck Vernon 703-228-3863 |
|