Review | Building |
Review Date | 10/20/2021 |
Status | Rejected |
Comments |
Sheet A1.02a_EXISTING REQUIREMENTS AND PATH OF TRAVEL @ FIRST FLOOR: A1.02a Existing Requirements ... @ First Floor 20 October 2021 | Please identify all rooms which have an assembly use, including conference rooms, staff lounge, etc. | The occupant load of such rooms shall be based upon a floor area ratio of 15 ft²/person (Assembly, unconcentrated) or upon the chair count, whichever is greater. | 2018 VCC §1004.5; §1004.5.1; Table 1004.5 | |
|