StatusRejected
Comments
06/07/2022 Under the prescriptive compliance approach, slab edge insulation must be R-10 minimum at the slab perimeter, with an overall length (horizontal and/or vertical) of 2 feet.
Ref. 2018 IRC with Virginia Amendments Table (N1102.1.1).
The slab edge need be insulated only when the slab (or some portion of its perimeter) is within 12" of grade;
(Ref. Section R1102.2.9.
When the slab itself is heated (e.g., via embedded hot water pipes), slab edge insulation must be increased to R15 where it is at or near grade.