Permit #B1803426
Address4201 WILSON BLVD
TypeCTBO
StatusFINALED
Permit HolderGR RESTORATION PAINTING INC.
OwnerJAMESTOWN PREMIER STAFFORD I LLC
Applied Date12/14/2018
Approved Date04/12/2019
Date Issued04/16/2019
DescriptionINTERIOR ALTERATION OF AN EXISTING SPACE FOR NEW TENANT, THAT INCLUDES NON-STRUCTURAL PARTITIONS, DOORS, FIXTURES AND RELATED. UNIT 140 - COREPOWER YOGA

View Event Log.      View Status.    View Required Plan Review       View Printer Version.

Review   Review       Date Status   Comments   
Building05/21/2019Approved Sheet A301-Interior Elevations: Clarify ramp construction on plans. Concrete? Wood floor on sleepers? VCC 603.1.
Building05/21/2019Approved Sheet A001-General Information: Note that the accessibility code cited is not correct. 2009 ICC/ANSI A117.1 is the correct code.
Building05/21/2019Approved Sheet A801-Door Schedule and Details: All doors must provide free egress at all times. Note for HW set 1 states "Fully Locked (locked from exterior)". That sounds like occupants can be locked in with a key. Please clarify or correct on the plans. VCC 1008.1.9.
Building05/21/2019Approved Sheet A504-Assisted Use Accessible Bathing Room: Sheets A-501-A504. Accessible transfer showers dimensions must be 36" x 36" exact. This is not a "minimum" dimension. ICC/ANSI A117.1, 608.2.1.
Building03/14/2019Approved Sheet A001-General Information: PLANS ARE APPROVED WITH FOLLOWING NOTES FOR FIELD: SUBMIT FIRE ALARM SHOP DRAWINGS FOR APPROVAL SUBMIT AUTOMATIC SUPPRESSION SHOP DRAWINGS FOR APPROVAL
Building02/04/2019Approved A Family or Assisted Use Bathing Room is required in recreational facilities where separate-sex bathing rooms or locker rooms are provided (1109.2.1). COMMENT NOT ADDRESSED 02/04/19-------------------------------------------------------------------------------- Please read the section thoroughly it appears designer is confusing toilet room requirement with bathing/shower room requirement,  more...
Building01/03/2019Approved Transfer-type shower shall comply with 2009 ICC/ANSI A117.1 Section 608.2.1. Clear floor space shall extend 12" past the seat. The shower controls shall be on the wall opposite the seat. Show clear floor space, seat, and controls on plan. See Fig. 608.2.1. Comment is applicable for the men's room accessible shower seat, it appears required 12" extension is blocked by an extended wall,  more...
Building01/03/2019Approved Each door (i.e., all doors) capable of latching or locking in a means of egress from a Group A or E occupancy with an occupant load of 50 or more shall be provided with panic or fire exit hardware (Section 1008.1.10). Panic hardware is also required for door E2 with type 2 hardware set indicates etr., please make sure door also includes panic hardware.
Building01/03/2019Approved Grab bars in restrooms shall comply with 2009 ICC/ANSI A117.1 Section 604.5. Unless previously provided, vertical grab bar(s) required. See Fig. 604.5.1 and 604.5.2. Please see toilet shower elevations on sheet A502.
Building01/03/2019Approved Please verify all provided benches are accessible per ICC A117.1 ANSI 2009, chapter 9 section 903. Please show all applicable dimensions for the bench.
DES:Water/Sewer Engineering05/21/2019Eplan Review Note ACTIVE REVISION. NO PLUMBING. APPROVED
DES:Water/Sewer Engineering03/26/2019Eplan Review Note COMMERCIAL INT ALT. 30.50 NEW DFUS. APPROVED
Energy 02/04/2019Approved Sheet P002 indicates that a hot water recirculation system is part of the scope of the permit. The pump is required by section C404.6.1 of the 2015 VECC to be fitted with automatic controls to turn off when there is no hot water demand. In the resubmission, show automatic controls that will shut down the hot water recirculation pump when there is no hot water demand. ***02/04/2019***  more...
Energy 02/04/2019Approved Section C405.2.1.1 of the 2015 VECC requires that occupant sensor controls function in a manner that automatically turns off lights within 30 minutes of all occupants leaving the space. Sheet E101 lighting key note 3 states that the hallway occupancy sensor will dim lighting to 50% when the hallway is not occupied. This does not meet code, as the code requires that the occupancy sensor control  more...
Energy 01/03/2019Approved Sheet P002 indicates that a 119 gallon tank-type electric water heater is part of the scope of the permit. The plans do not state the maximum allowable % per hour heat loss of the water heater. The 2015 Virginia Energy Conservation Code (VECC) Table C404.2 requires a maximum allowable heat loss of 0.53% per hour or less. In the resubmission, state the maximum allowable % per hour heat loss  more...
Energy 01/03/2019Approved Section C405.2.1 of the 2015 Virginia Energy Conservation Code (VECC) requires that Restrooms be controlled with occupant sensor controls. Sheet E101 does not show an occupant sensor in the Men's Changing room. In the resubmission, show an occupancy sensor in the Men's Changing room in order to comply with section C405.2.1 of the 2015 VECC.
EPlan Review04/12/2019Approved --N/A--
Plumbing 01/03/2019Approved 1-3-19 Pg A503 Please provide location of Vert Grab Bar for Mens and Womens restrooms. 2009 ANSI 604.5.1
Zoning 06/06/2019Approved no zoning issues
Zoning 05/21/2019Approved no zoning issues