Permit #B1901495
Address2311 WILSON BLVD
TypeCTBO
StatusFINALED
Permit HolderECKO BUILDING SERVICES LLC
OwnerOTTER WILSON BOULEVARD LLC
Applied Date05/30/2019
Approved Date07/31/2019
Date Issued08/01/2019
DescriptionINTERIOR ALTERATIONS FOR A NEW COFFEE SHOP - FOR FIVE COFFEE ROASTERS. - REQUIRES HEALTH REVIEW

View Event Log.      View Status.    View Required Plan Review       View Printer Version.

Review   Review       Date Status   Comments   
Building07/09/2019Approved Sheet A0100 CODE ANALYSIS: With an occupant load of less than 50, the use group is now a B-use (Chapter 3).
Building07/09/2019Approved Sheet A0000 COVER SHEET: SUBMIT FIRE ALARM SHOP DRAWINGS FOR APPROVAL
Building07/09/2019Approved Sheet A0000 COVER SHEET: SEPARATE PLAN AND PERMIT REQUIRED FOR DOORS WITH SPECIAL LOCKING HARDWARE
Building07/09/2019Approved Sheet A0000 COVER SHEET: SUBMIT AUTOMATIC SUPPRESSION SHOP DRAWINGS FOR APPROVAL
Building06/10/2019Approved Sheet A0100 CODE ANALYSIS: It appears to be that the occupant load at the kitchen area was calculated as an assembly function. Kitchen occupant load can be calculated as 200 SF/Occp including the service counter, Table 1004.1.2.
Building06/10/2019Approved Sheet A0100 CODE ANALYSIS: Based on an occupant load of more than 50, the front entry door (Entry 100), the back of the house door, and the door leading to Service Lobby 110 must be provided with panic hardware and swing in the direction of egress travel, Section 1008.1.10 and 1008.1.2.
Building06/10/2019Approved Sheet A1100 PARTITION, DOOR, & HARDWARE TYPES, SCHEDULES and TYPICAL DETAILS: Please provide on the plans the door hardware schedule for the front entry door (Entry 100), the back of the house door, and the door leading to Service Lobby 110.
Building06/10/2019Approved Sheet A0000 COVER SHEET: Plans must be signed and sealed by an architect or engineer licensed in the State of Virginia.
Building05/29/2019Approved Rejected and returned per request of applicant (Betsy Stagg)
DES:Water/Sewer Engineering11/26/2019Eplan Review Note ACTIVE REVISION. NO PLUMBING. MAKING ADA CHNAGES. APPROVED
DES:Water/Sewer Engineering07/31/2019Eplan Review Note COMMERCIAL INT ALT. 29 NEW DFU'S. APPROVED
Energy 06/12/2019Approved Sheet P-000 indicates that a tank-type electric water is part of the scope of the permit. Table C404.2 of the 2012 Virginia Energy Conservation Code (VECC) requires that this water heater has a maximum standby loss of not more than 242 BTU/hour. In the resubmission, revise the Water Heater Schedule on sheet P-000 to state the maximum allowable standby loss (BTU/hour) of the water heater.
Energy 06/12/2019Approved Sheet M-700 includes a Water Source Heat Pump Unit Schedule. The 2012 Virginia Energy Conservation Code (VECC) Table C403.2.3(2) requires that Water Source Heat Pumps (WSHP) have a minimum COP of 4.2 or higher at 68 degrees F entering water temperature. The design indicates these WSHP units have a COP of 4.03 and 3.82. In the resubmission revise the WSHP schedule to indicate compliance with  more...
EPlan Review11/26/2019Approved --N/A--
EPlan Review07/31/2019Approved --N/A--
Plumbing 07/08/2019Approved 7-8-19 Pg P300 There are 2 SK-3 shown on plans, Which is a 3-compartment sink is this an error? if not please correct connection to GI and calculations. Thank you for addressing past comment..
Plumbing 07/08/2019Approved Sheet P-300 Plumbing Riser Diagrams: A Waste Water Survey Form is required. Please use the link provided. https://arlingtonva.s3.dualstack.us-east-1.amazonaws.com/wp-content/uploads/sites/4/2015/04/Arlington_IU_Survey_2014_140806mod.pdf And forward it to Wilson Dodge the pretreatment coordinator at wrdodge@arlingtonva.us
Plumbing 06/12/2019Approved 6-12-19 Pg P300 AAV will require a Relief Vent. 2012 VPC 918.3.1
Public Health Division06/13/2019Approved Sheet MENU: The asterisk must be located near the food item that is served/offered undercooked (ex. poached eggs*).
Public Health Division06/13/2019Approved A Northern Virginia certified food manager card must be obtained for the pre-opening inspection and all hours of operation. The Learn2Serve certificate may be used to obtain the Northern Virginia certified food manager card at ORS Interactive located 6066 Leesburg Pike Falls Church, VA 22041 703-533-7600.