Building | 02/13/2020 | Approved |
Sheet A-190-Schedules and Details: Automatic sliding doors 1 and 10 shall comply with 2015 VUSBC 1010.1.4.2 and BHMA A156.10.
|
Building | 02/13/2020 | Approved |
Sheet A-190-Schedules and Details: Automatic sliding doors 1 and 10 shall comply with 2015 VUSBC 1010.1.4.2 and BHMA A156.10.
|
Building | 02/13/2020 | Approved |
Sheet A-190-Schedules and Details: Automatic sliding doors 1 and 10 shall comply with 2015 VUSBC 1010.1.4.2 and BHMA A156.10.
|
Building | 11/18/2019 | Approved |
Sheet A-190-Schedules and Details: I cannot locate the hardware schedule. Please provide schedule on plans. Door hardware 01 is required to break away. 2015 VUSBC 1010.1.4.2
|
Building | 11/18/2019 | Approved |
Sheet A-190-Schedules and Details: G2 and G6 glazing in sliding doors and adjacent fixed panels should be tempered per 2015 VUSBC section 2406.4.
|
Building | 11/18/2019 | Approved |
Sheet A-130-Entry Plan, Elevations and Details: Confirm if fixed glass panels at entry vestibule are within the 24 inch arc as measured from vertical edge of door, whereby the glazing will need to be tempered. 2015 VUSBC 2406.4.2
|
Building | 11/18/2019 | Approved |
Sheet A-180-Enlarged Plans, Details and Elevations: Provide detail on plan as to how drinking fountains will comply with 2009 A117.1 section 307.2 Protrusion Limits and cane protection. The low fountain may comply however the higher fountain may not (height from bottom of unit greater than 27"). An equipment skirt or built element may be necessary.
|
Building | 11/18/2019 | Approved |
Sheet A-190-Schedules and Details: I cannot locate the hardware schedule. Please provide schedule on plans. Door hardware 01 is required to break away. 2015 VUSBC 1010.1.4.2
|
Building | 11/18/2019 | Approved |
Sheet A-190-Schedules and Details: G2 and G6 glazing in sliding doors and adjacent fixed panels should be tempered per 2015 VUSBC section 2406.4.
|
Building | 11/18/2019 | Approved |
Sheet A-180-Enlarged Plans, Details and Elevations: Provide detail on plan as to how drinking fountains will comply with 2009 A117.1 section 307.2 Protrusion Limits and cane protection. The low fountain may comply however the higher fountain may not (height from bottom of unit greater than 27"). An equipment skirt or built element may be necessary.
|
Building | 11/18/2019 | Approved |
Sheet A-130-Entry Plan, Elevations and Details: Confirm if fixed glass panels at entry vestibule are within the 24 inch arc as measured from vertical edge of door, whereby the glazing will need to be tempered. 2015 VUSBC 2406.4.2
|
Building | 11/18/2019 | Approved |
Sheet A-190-Schedules and Details: I cannot locate the hardware schedule. Please provide schedule on plans. Door hardware 01 is required to break away. 2015 VUSBC 1010.1.4.2
|
Building | 11/18/2019 | Approved |
Sheet A-190-Schedules and Details: G2 and G6 glazing in sliding doors and adjacent fixed panels should be tempered per 2015 VUSBC section 2406.4.
|
Building | 11/18/2019 | Approved |
Sheet A-130-Entry Plan, Elevations and Details: Confirm if fixed glass panels at entry vestibule are within the 24 inch arc as measured from vertical edge of door, whereby the glazing will need to be tempered. 2015 VUSBC 2406.4.2
|
Building | 11/18/2019 | Approved |
Sheet A-180-Enlarged Plans, Details and Elevations: Provide detail on plan as to how drinking fountains will comply with 2009 A117.1 section 307.2 Protrusion Limits and cane protection. The low fountain may comply however the higher fountain may not (height from bottom of unit greater than 27"). An equipment skirt or built element may be necessary.
|
DES:Engineering | 10/09/2020 | Approved |
DEMO BUILDING AND BUILD NEW CVS 19 NEW DFUS NO EXISTING FIXTURES SHOWN WATER METER TO REMAIN
|
DES:Water/Sewer Engineering | 01/05/2022 | Approved |
ACTIVE REVISION. STRUCTURAL CHANGES ONLY. NO PLUMBING. APPROVED
|
DES:Water/Sewer Engineering | 10/09/2020 | Approved |
DEMO BUILDING AND BUILD NEW CVS 19 NEW DFUS NO EXISTING FIXTURES SHOWN WATER METER TO REMAIN
|
Electrical | 11/22/2019 | Approved |
Provide Roof top rec per NEC 2014, Article 210.63
|
Electrical | 11/22/2019 | Approved |
Provide show window receptacle per NEC 2014, Article 210.62
|