Permit #B2000207
Address1550 CRYSTAL DR
TypeCTBO
StatusACTIVE
Permit HolderTEEL CONSTRUCTION INC
OwnerCESC SQUARE LLC %JBG SMITH PROPERTIES
Applied Date01/27/2020
Approved Date05/21/2020
Date Issued05/21/2020
DescriptionINTERIOR ALT FOR A NEW RETAIL SHOP PROVIDING PACKAGED SALADS, SANDWICHES, ENTREES, SOUPS & VARIOUS BEVERAGES. SELF APP CHECK-OUT SPECIAL INSPECTIONS REQUIRED

View Event Log.      View Status.    View Required Plan Review       View Printer Version.

Review   Review       Date Status   Comments   
Building08/05/2021Rejected Sheet A-102_GROCERY LEVEL CONSTRUCTION PLAN BOH: Provide maneuvering clearances at ingress side of door 119A. 404.2.3 A117.1 2009.
Building08/05/2021Rejected Sheet A-102_GROCERY LEVEL CONSTRUCTION PLAN BOH: I don't see a scheduled hardware set for door 119A. This door cannot lock, as it is part of the egress for the floor which requires access to two exits. If someone is in Corridor 2 and door 119C is blocked, re-entry through 119A is required. This space requires access to two exits.
Building08/05/2021Approved Sheet A-102_GROCERY LEVEL CONSTRUCTION PLAN BOH: Provide maneuvering clearances at ingress side of door 119A. 404.2.3 A117.1 2009.
Building08/05/2021Approved Sheet A-102_GROCERY LEVEL CONSTRUCTION PLAN BOH: I don't see a scheduled hardware set for door 119A. This door cannot lock, as it is part of the egress for the floor which requires access to two exits. If someone is in Corridor 2 and door 119C is blocked, re-entry through 119A is required. This space requires access to two exits.
Building08/02/2021Approved Sheet A-122_COOLER AND FREEZER SECTIONS: Please note plywood on new steel platform to be FRT. Non-combustible construction required, or FRT, Class A material.
Building08/02/2021Rejected Sheet A-122_COOLER AND FREEZER SECTIONS: Please note plywood on new steel platform to be FRT. Non-combustible construction required, or FRT, Class A material.
Building03/16/2021Rejected Sheet 0G-001_COVER SHEET: Approved Engineering judgement letter referencing structural foam insulation and signed by the Building Official is attached to the Architect's Response letter dated 3.01.2021.
Building03/16/2021Rejected Sheet 0G-001_COVER SHEET: 3M Anti Graffiti Window film product data sheet is attached to the Architect's Response letter dated 3.01.2021.
Building03/16/2021Rejected Sheet 0G-001_COVER SHEET: Arlington County Industrial/Commercial Wastewater User Survey is attached to Architect's Response letter dated 3.01.2021.
Building03/16/2021Rejected Sheet A-600_DOOR TYPES, SCHEDULES, & DETAILS: Provide the hardware set on the plan for door 119C which should be 1-1/2 rated with fire hardware in an exit passageway. --------------------------------------------------------------------------------------------------------------------- UPDATED REVIEW COMMENT 3/16/2021: NOTE FOR HARDWARE SET 8, CONCEALED VERTICAL ROD SPECIFIED, NO DELAYED EGRESS  more...
Building03/16/2021Approved Sheet 0G-001_COVER SHEET: Approved Engineering judgement letter referencing structural foam insulation and signed by the Building Official is attached to the Architect's Response letter dated 3.01.2021.
Building03/16/2021Approved Sheet 0G-001_COVER SHEET: 3M Anti Graffiti Window film product data sheet is attached to the Architect's Response letter dated 3.01.2021.
Building03/16/2021Approved Sheet 0G-001_COVER SHEET: Arlington County Industrial/Commercial Wastewater User Survey is attached to Architect's Response letter dated 3.01.2021.
Building03/16/2021Approved Sheet A-600_DOOR TYPES, SCHEDULES, & DETAILS: Provide the hardware set on the plan for door 119C which should be 1-1/2 rated with fire hardware in an exit passageway. --------------------------------------------------------------------------------------------------------------------- UPDATED REVIEW COMMENT 3/16/2021: NOTE FOR HARDWARE SET 8, CONCEALED VERTICAL ROD SPECIFIED, NO DELAYED EGRESS  more...
Building03/16/2021Approved Sheet A-600_DOOR TYPES, SCHEDULES, & DETAILS: Provide the hardware set on the plan for door 119C which should be 1-1/2 rated with fire hardware in an exit passageway. --------------------------------------------------------------------------------------------------------------------- UPDATED REVIEW COMMENT 3/16/2021: NOTE FOR HARDWARE SET 8, CONCEALED VERTICAL ROD SPECIFIED, NO DELAYED EGRESS  more...
Building03/16/2021Approved Sheet A-600_DOOR TYPES, SCHEDULES, & DETAILS: Provide the hardware set on the plan for door 119C which should be 1-1/2 rated with fire hardware in an exit passageway. --------------------------------------------------------------------------------------------------------------------- UPDATED REVIEW COMMENT 3/16/2021: NOTE FOR HARDWARE SET 8, CONCEALED VERTICAL ROD SPECIFIED, NO DELAYED EGRESS  more...
Building03/16/2021Approved Sheet 0G-001_COVER SHEET: Approved Engineering judgement letter referencing structural foam insulation and signed by the Building Official is attached to the Architect's Response letter dated 3.01.2021.
Building03/16/2021Approved Sheet 0G-001_COVER SHEET: 3M Anti Graffiti Window film product data sheet is attached to the Architect's Response letter dated 3.01.2021.
Building03/16/2021Approved Sheet 0G-001_COVER SHEET: Arlington County Industrial/Commercial Wastewater User Survey is attached to Architect's Response letter dated 3.01.2021.
Building03/16/2021Approved Sheet 0G-001_COVER SHEET: Approved Engineering judgement letter referencing structural foam insulation and signed by the Building Official is attached to the Architect's Response letter dated 3.01.2021.