Permit #B2000288
Address1770 CRYSTAL DR
TypeCTBO
StatusFINALED
Permit HolderVENTURE CONSTRUCTION COMPANY
OwnerCESC SQUARE LLC JBG SMITH PROPERTIES
Applied Date02/05/2020
Approved Date04/07/2021
Date Issued04/13/2021
DescriptionNEW TENANT BUILDOUT IN AN EXISTING SPACE TO THE 1ST FLOOR UNIT 115 **SOLIDCORE**

View Event Log.      View Status.    View Required Plan Review       View Printer Version.

Review   Review       Date Status   Comments   
Building10/23/2020Approved Sheet A-000-COVER SHEET: NOTE: SUBMIT AUTOMATIC SUPPRESSION SHOP DRAWINGS FOR APPROVAL SUBMIT FIRE ALARM SHOP DRAWINGS FOR APPROVAL
Building10/23/2020Approved Sheet A-000-COVER SHEET: NOTE: SUBMIT AUTOMATIC SUPPRESSION SHOP DRAWINGS FOR APPROVAL SUBMIT FIRE ALARM SHOP DRAWINGS FOR APPROVAL
Building03/17/2020Approved Sheet A-301-SECTIONS: Water supply and drain pipes under lavatories and sinks shall be insulated or otherwise configured to protect against contact. [ICC A117.1-2009 Section 606.6]. Detail for lavatory / sink (1/A301) does not show any for form of protection. Please clearly show compliance with referenced code section. *********************************************3/17/2020 Comment not  more...
Building03/17/2020Approved Sheet A-301-SECTIONS: Water supply and drain pipes under lavatories and sinks shall be insulated or otherwise configured to protect against contact. [ICC A117.1-2009 Section 606.6]. Detail for lavatory / sink (1/A301) does not show any for form of protection. Please clearly show compliance with referenced code section. *********************************************3/17/2020 Comment not  more...
Building03/13/2020Approved Sheet A-100-PARTITION TYPES: UL design listing acknowledged on the drawing. Please include actual listed construction detail on the drawings. Actual details of the referenced UL assembly are necessary for new construction and inspection of the listed assembly. Example: Please provide actual UL design detail for any new partition that references UL listed assembly Code Reference: VCC Sec  more...
Building03/13/2020Approved Sheet A-101-CONSTRUCTION PLAN: There appears to be omissions of partitions on the construction plan. UL design listing acknowledged on the drawing. Please include actual listed construction detail on the drawings. Actual details of the referenced UL assembly are necessary for proper construction and inspection of the listed assembly. Example: The label for partition type C1 is shown, but  more...
Building03/13/2020Approved Sheet A-101-CONSTRUCTION PLAN: On the door schedule, it appears that a single hardware set is inadvertently assigned to most of the doors. Please verify each door is assigned appropriate hardware.
Building03/13/2020Approved Sheet A-101-CONSTRUCTION PLAN: There appears to be omissions of partitions on the construction plan. UL design listing acknowledged on the drawing. Please include actual listed construction detail on the drawings. Actual details of the referenced UL assembly are necessary for proper construction and inspection of the listed assembly. Example: The label for partition type C1 is shown, but  more...
Building03/13/2020Approved Sheet A-100-PARTITION TYPES: UL design listing acknowledged on the drawing. Please include actual listed construction detail on the drawings. Actual details of the referenced UL assembly are necessary for new construction and inspection of the listed assembly. Example: Please provide actual UL design detail for any new partition that references UL listed assembly Code Reference: VCC Sec  more...
Building03/13/2020Approved Sheet A-101-CONSTRUCTION PLAN: On the door schedule, it appears that a single hardware set is inadvertently assigned to most of the doors. Please verify each door is assigned appropriate hardware.
Building02/12/2020Approved Sheet A-201-INTERIOR ELEVATIONS: Where lockers are provided in required accessible spaces, at least 5 percent, but not less than one shall be accessible. [2015 VCC Section 1109.9] For example, 6/A201 appears to be lockers or similar storage, please indicate a compliant accessible locker or storage element.
Building02/12/2020Approved Sheet A-201-INTERIOR ELEVATIONS: Where lockers are provided in required accessible spaces, at least 5 percent, but not less than one shall be accessible. [2015 VCC Section 1109.9] For example, 6/A201 appears to be lockers or similar storage, please indicate a compliant accessible locker or storage element.
Building02/11/2020Approved Sheet A-201-INTERIOR ELEVATIONS: Reach ranges shall comply with ICC A117.1-2009 Sec. 308. For example, please show on the drawings that unobstructed forward, or side reach for coat rack is compliant.
Building02/11/2020Approved Sheet A-101-CONSTRUCTION PLAN: At least one of each type of exercise machine and equipment shall be on an accessible route. [2015 VCC Sec. 1110.4.10] Please clearly show compliance with the referenced section of the code by indicating the route, designated equipment and clear floor space required.
Building02/11/2020Approved Sheet A-101-CONSTRUCTION PLAN: Please clearly show compliance with the accessibility requirements for dressing rooms in the area labeled Changing Room (102). [ICC A117.1-2009 Sec. 803]. For example show that the provisions for turning space, door swing and benches are met.
Building02/11/2020Approved Sheet A-201-INTERIOR ELEVATIONS: Reach ranges shall comply with ICC A117.1-2009 Sec. 308. For example, please show on the drawings that unobstructed forward, or side reach for coat rack is compliant.
Building02/11/2020Approved Sheet A-101-CONSTRUCTION PLAN: At least one of each type of exercise machine and equipment shall be on an accessible route. [2015 VCC Sec. 1110.4.10] Please clearly show compliance with the referenced section of the code by indicating the route, designated equipment and clear floor space required.
Building02/11/2020Approved Sheet A-101-CONSTRUCTION PLAN: Please clearly show compliance with the accessibility requirements for dressing rooms in the area labeled Changing Room (102). [ICC A117.1-2009 Sec. 803]. For example show that the provisions for turning space, door swing and benches are met.
DES:Water/Sewer Engineering05/03/2021Approved ACTIVE REVISION. NO PLUMBING. APPROVED
DES:Water/Sewer Engineering11/04/2020Eplan Review Note COMMERCIAL INT ALT. 12 NEW DFUS APPROVED