Building | 10/23/2020 | Approved |
Sheet A-000-COVER SHEET: NOTE:
SUBMIT AUTOMATIC SUPPRESSION
SHOP DRAWINGS FOR APPROVAL
SUBMIT FIRE ALARM SHOP
DRAWINGS FOR APPROVAL
|
Building | 10/23/2020 | Approved |
Sheet A-000-COVER SHEET: NOTE:
SUBMIT AUTOMATIC SUPPRESSION
SHOP DRAWINGS FOR APPROVAL
SUBMIT FIRE ALARM SHOP
DRAWINGS FOR APPROVAL
|
Building | 03/17/2020 | Approved |
Sheet A-301-SECTIONS: Water supply and drain pipes under lavatories and sinks shall be insulated or otherwise configured to protect against contact. [ICC A117.1-2009 Section 606.6]. Detail for lavatory / sink (1/A301) does not show any for form of protection. Please clearly show compliance with referenced code section.
*********************************************3/17/2020
Comment not more...
|
Building | 03/17/2020 | Approved |
Sheet A-301-SECTIONS: Water supply and drain pipes under lavatories and sinks shall be insulated or otherwise configured to protect against contact. [ICC A117.1-2009 Section 606.6]. Detail for lavatory / sink (1/A301) does not show any for form of protection. Please clearly show compliance with referenced code section.
*********************************************3/17/2020
Comment not more...
|
Building | 03/13/2020 | Approved |
Sheet A-100-PARTITION TYPES: UL design listing acknowledged on the drawing. Please include actual listed construction detail on the drawings. Actual details of the referenced UL assembly are necessary for new construction and inspection of the listed assembly.
Example: Please provide actual UL design detail for any new partition that references UL listed assembly
Code Reference: VCC Sec more...
|
Building | 03/13/2020 | Approved |
Sheet A-101-CONSTRUCTION PLAN: There appears to be omissions of partitions on the construction plan.
UL design listing acknowledged on the drawing. Please include actual listed construction detail on the drawings. Actual details of the referenced UL assembly are necessary for proper construction and inspection of the listed assembly.
Example: The label for partition type C1 is shown, but more...
|
Building | 03/13/2020 | Approved |
Sheet A-101-CONSTRUCTION PLAN: On the door schedule, it appears that a single hardware set is inadvertently assigned to most of the doors. Please verify each door is assigned appropriate hardware.
|
Building | 03/13/2020 | Approved |
Sheet A-101-CONSTRUCTION PLAN: There appears to be omissions of partitions on the construction plan.
UL design listing acknowledged on the drawing. Please include actual listed construction detail on the drawings. Actual details of the referenced UL assembly are necessary for proper construction and inspection of the listed assembly.
Example: The label for partition type C1 is shown, but more...
|
Building | 03/13/2020 | Approved |
Sheet A-100-PARTITION TYPES: UL design listing acknowledged on the drawing. Please include actual listed construction detail on the drawings. Actual details of the referenced UL assembly are necessary for new construction and inspection of the listed assembly.
Example: Please provide actual UL design detail for any new partition that references UL listed assembly
Code Reference: VCC Sec more...
|
Building | 03/13/2020 | Approved |
Sheet A-101-CONSTRUCTION PLAN: On the door schedule, it appears that a single hardware set is inadvertently assigned to most of the doors. Please verify each door is assigned appropriate hardware.
|
Building | 02/12/2020 | Approved |
Sheet A-201-INTERIOR ELEVATIONS: Where lockers are provided in required accessible spaces, at least 5 percent, but not less than one shall be accessible. [2015 VCC Section 1109.9] For example, 6/A201 appears to be lockers or similar storage, please indicate a compliant accessible locker or storage element.
|
Building | 02/12/2020 | Approved |
Sheet A-201-INTERIOR ELEVATIONS: Where lockers are provided in required accessible spaces, at least 5 percent, but not less than one shall be accessible. [2015 VCC Section 1109.9] For example, 6/A201 appears to be lockers or similar storage, please indicate a compliant accessible locker or storage element.
|
Building | 02/11/2020 | Approved |
Sheet A-201-INTERIOR ELEVATIONS: Reach ranges shall comply with ICC A117.1-2009 Sec. 308. For example, please show on the drawings that unobstructed forward, or side reach for coat rack is compliant.
|
Building | 02/11/2020 | Approved |
Sheet A-101-CONSTRUCTION PLAN: At least one of each type of exercise machine and equipment shall be on an accessible route. [2015 VCC Sec. 1110.4.10] Please clearly show compliance with the referenced section of the code by indicating the route, designated equipment and clear floor space required.
|
Building | 02/11/2020 | Approved |
Sheet A-101-CONSTRUCTION PLAN: Please clearly show compliance with the accessibility requirements for dressing rooms in the area labeled Changing Room (102). [ICC A117.1-2009 Sec. 803]. For example show that the provisions for turning space, door swing and benches are met.
|
Building | 02/11/2020 | Approved |
Sheet A-201-INTERIOR ELEVATIONS: Reach ranges shall comply with ICC A117.1-2009 Sec. 308. For example, please show on the drawings that unobstructed forward, or side reach for coat rack is compliant.
|
Building | 02/11/2020 | Approved |
Sheet A-101-CONSTRUCTION PLAN: At least one of each type of exercise machine and equipment shall be on an accessible route. [2015 VCC Sec. 1110.4.10] Please clearly show compliance with the referenced section of the code by indicating the route, designated equipment and clear floor space required.
|
Building | 02/11/2020 | Approved |
Sheet A-101-CONSTRUCTION PLAN: Please clearly show compliance with the accessibility requirements for dressing rooms in the area labeled Changing Room (102). [ICC A117.1-2009 Sec. 803]. For example show that the provisions for turning space, door swing and benches are met.
|
DES:Water/Sewer Engineering | 05/03/2021 | Approved |
ACTIVE REVISION. NO PLUMBING. APPROVED
|
DES:Water/Sewer Engineering | 11/04/2020 | Eplan Review Note |
COMMERCIAL INT ALT. 12 NEW DFUS APPROVED
|