Review   Review       Date Status   Comments   
Building04/27/2021Approved Please do not delete any sheets that have already been submitted. For further guidance, please reference the Arlington County’s OnBase/ePlan Review Plan and Document Upload Tutorial: How to upload documents when submitting revised drawings: https://www.youtube.com/watch?v=qTzGy8GECpE&feature=youtu.be If there are any questions or a comment clarification is necessary for this review,  more...
Building04/27/2021Approved Sheet A-001-Architectural Plan: Is this equipment protruding into the egress path? Protruding objects on circulation paths shall comply with the requirements of Sections 1003.3
Building04/27/2021Approved Door schedule and hardware information is not found on the drawings. Please provide the schedule and door hardware schedule on the drawings to verify compliance with the door and hardware requirements of the Virginia Construction Code. Code Reference: VCC 2015 Sec 1010 ******************************************************************************************************************04-26-2021:  more...
Building04/27/2021Rejected Please do not delete any sheets that have already been submitted. For further guidance, please reference the Arlington County’s OnBase/ePlan Review Plan and Document Upload Tutorial: How to upload documents when submitting revised drawings: https://www.youtube.com/watch?v=qTzGy8GECpE&feature=youtu.be If there are any questions or a comment clarification is necessary for this review,  more...
Building04/27/2021Rejected Door schedule and hardware information is not found on the drawings. Please provide the schedule and door hardware schedule on the drawings to verify compliance with the door and hardware requirements of the Virginia Construction Code. Code Reference: VCC 2015 Sec 1010 ******************************************************************************************************************04-26-2021:  more...
Building04/27/2021Rejected
Building04/27/2021Rejected Sheet A-001-Architectural Plan: Is this equipment protruding into the egress path? Protruding objects on circulation paths shall comply with the requirements of Sections 1003.3
Building04/26/2021Rejected Sheet A-001-Architectural Plan: Door maneuvering clearance at push side requires 12 inches (if door has a closer) for compliance with the accessible route. Reference: 2009 ICC A117.1 Section 402.3
Building04/26/2021Rejected Sheet A-000-Cover Sheet: Change of levels on accessible route shall comply with section 303 for the 2009 ICC A117.1.
Building04/26/2021Rejected Sheet A-000-Cover Sheet: Parking spaces and marked aisle shall comply with section 502 for the 2009 ICC A117.1, including floor surfaces, signs for identification, markings and sizes.
Building04/26/2021Rejected Sheet A-000-Cover Sheet: Per Section 404.2.3.1 of the 2009 ICC A117.1, Floor surface within the maneuvering clearance of the door shall have a slope not steeper than 1:48 and shall comply with Section 302 of the 2009 ICC A117.1.
Building04/26/2021Rejected Sheet A-001-Architectural Plan: Door schedule and hardware information is not found on the drawings. Please provide the schedule and door hardware schedule on the drawings to verify compliance with the door and hardware requirements of the Virginia Construction Code. Code Reference: VCC 2015 Sec  more...
Building04/26/2021Approved Sheet A-001-Architectural Plan: Door maneuvering clearance at push side requires 12 inches (if door has a closer) for compliance with the accessible route. Reference: 2009 ICC A117.1 Section 402.3
Building04/26/2021Approved Sheet A-000-Cover Sheet: Change of levels on accessible route shall comply with section 303 for the 2009 ICC A117.1.
Building04/26/2021Approved Sheet A-000-Cover Sheet: Parking spaces and marked aisle shall comply with section 502 for the 2009 ICC A117.1, including floor surfaces, signs for identification, markings and sizes.
Building04/26/2021Approved Sheet A-000-Cover Sheet: Per Section 404.2.3.1 of the 2009 ICC A117.1, Floor surface within the maneuvering clearance of the door shall have a slope not steeper than 1:48 and shall comply with Section 302 of the 2009 ICC A117.1.
Building04/26/2021Approved Sheet A-001-Architectural Plan: Door schedule and hardware information is not found on the drawings. Please provide the schedule and door hardware schedule on the drawings to verify compliance with the door and hardware requirements of the Virginia Construction Code. Code Reference: VCC 2015 Sec  more...
Building03/16/2021Rejected The scope of work presented mentions only demolition and does not mention construction. Please revise scope of work to reflect a summary of the complete proposed. Code Reference: Virginia Construction Code Sections 109.3 Sheet(s) Reference: A-000
Building03/16/2021Rejected The project shows a change of use and occupancy from a M use group to A2 use group. Please provide a drawing showing the accessible parking and accessible route to the accessible entrance as required by the Virginia Existing Building Code (VEBC) for a complete change of occupancy. Code Reference: VEBC Section 402.3
Building03/16/2021Rejected It appears that the floorplan used for the life safety/egress plan is different from the architectural floor plan. Please coordinate and use the correct floor plan. Code Reference: Virginia Construction Code Sections 109.3 Referenced Sheet: LS-001, A-000