Permit #B2100851
Address1850 FORT MYER DR
TypeCTBO
StatusFINALED
Permit HolderKPS DEVELOPMENT INC
OwnerKEYBRIDGE INVESTMENTS LLC`
Applied Date04/16/2021
Approved Date06/08/2021
Date Issued06/08/2021
Description ALL EXISTING TO REMAIN U.O.N.- INTERIOR ALTERATION FOR KITCHEN.- ADD NEW SUSHI BAR.- EQUIPMENT AS SHOWN THE LIST AND ALL EXISTING KITCHEN EQUIPMENT TO REMAIN U.O.N. 1ST FLOOR UNIT 1850N **YURAKU JAPANESE RESTAURANT**

View Event Log.      View Status.    View Required Plan Review       View Printer Version.

Review   Review       Date Status   Comments   
Building05/28/2021Approved Sheet A-001 Cover Sheet and Notes: DRAWINGS ARE APPROVED WITH THE FOLLOWING FIELD COMMENTS: SEPARATE PLAN AND PERMIT REQUIRED FOR DOORS WITH SPECIAL LOCKING HARDWARE SUBMIT AUTOMATIC SUPPRESSION SHOP DRAWINGS FOR APPROVAL SUBMIT FIRE ALARM SHOP DRAWINGS FOR APPROVAL
Building05/28/2021Approved Sheet A-001 Cover Sheet and Notes: DRAWINGS ARE APPROVED WITH THE FOLLOWING FIELD COMMENTS: SEPARATE PLAN AND PERMIT REQUIRED FOR DOORS WITH SPECIAL LOCKING HARDWARE SUBMIT AUTOMATIC SUPPRESSION SHOP DRAWINGS FOR APPROVAL SUBMIT FIRE ALARM SHOP DRAWINGS FOR APPROVAL
Building05/24/2021Approved Sheet A-002 Proposed Floor Plan: There appears to be a column obstructing the code required Maneuvering Clearances at new Door #1. Please review and comply with the code requirements of ICC A117.1-2009, section 404.2.3 and figure 404.2.3.2. ***************************************************************************************************************** 05/24/2021: See markup. Door #1 with HW-2  more...
Building05/24/2021Approved Sheet A-002 Proposed Floor Plan: There appears to be a column obstructing the code required Maneuvering Clearances at new Door #1. Please review and comply with the code requirements of ICC A117.1-2009, section 404.2.3 and figure 404.2.3.2. ***************************************************************************************************************** 05/24/2021: See markup. Door #1 with HW-2  more...
Building05/24/2021Rejected Sheet A-002 Proposed Floor Plan: There appears to be a column obstructing the code required Maneuvering Clearances at new Door #1. Please review and comply with the code requirements of ICC A117.1-2009, section 404.2.3 and figure 404.2.3.2. ***************************************************************************************************************** 05/24/2021: See markup. Door #1 with HW-2  more...
Building04/30/2021Rejected Sheet A-003 Reflected Ceiling Plan: See markup, Detail 2/A-002: Does this section detail occur at the Sushi Bar?
Building04/30/2021Approved Sheet A-003 Reflected Ceiling Plan: General Comment: See markup. Your Reception Desk at the Sushi Bar arrears to be a Built-in Furniture piece with electrical outlets Built-in to it. We review powered furniture such as this like a Wall Partition. All wood blocking installed within the framing cavity shall be Fire-Retardant Treated (FRT) Wood and its enclosure shall be a Noncombustible Surface such  more...
Building04/30/2021Approved Sheet A-003 Reflected Ceiling Plan: See markup, Detail 2/A-002: Does this section detail occur at the Sushi Bar?
Building04/30/2021Approved Sheet A-003 Reflected Ceiling Plan: See markup, Detail 2/A-002: Does this section detail occur at the Sushi Bar?
Building04/30/2021Rejected Sheet A-003 Reflected Ceiling Plan: General Comment: See markup. Your Reception Desk at the Sushi Bar arrears to be a Built-in Furniture piece with electrical outlets Built-in to it. We review powered furniture such as this like a Wall Partition. All wood blocking installed within the framing cavity shall be Fire-Retardant Treated (FRT) Wood and its enclosure shall be a Noncombustible Surface such  more...
Building04/30/2021Rejected Sheet A-002 Proposed Floor Plan: There appears to be a column obstructing the code required Maneuvering Clearances at new Door #1. Please review and comply with the code requirements of ICC A117.1-2009, section 404.2.3 and figure 404.2.3.2.
Building04/30/2021Rejected Sheet A-003 Reflected Ceiling Plan: See markup, Detail 2/A-002: Does this section detail occur at the Sushi Bar?
Building04/30/2021Rejected Sheet A-003 Reflected Ceiling Plan: General Comment: See markup. Your Reception Desk at the Sushi Bar arrears to be a Built-in Furniture piece with electrical outlets Built-in to it. We review powered furniture such as this like a Wall Partition. All wood blocking installed within the framing cavity shall be Fire-Retardant Treated (FRT) Wood and its enclosure shall be a Noncombustible Surface such  more...
Building04/30/2021Approved Sheet A-003 Reflected Ceiling Plan: General Comment: See markup. Your Reception Desk at the Sushi Bar arrears to be a Built-in Furniture piece with electrical outlets Built-in to it. We review powered furniture such as this like a Wall Partition. All wood blocking installed within the framing cavity shall be Fire-Retardant Treated (FRT) Wood and its enclosure shall be a Noncombustible Surface such  more...
DES:Water/Sewer Engineering04/29/2021Approved APPROVED REESTURANT RENO 4.00 NEW DFU'S
Electrical04/29/2021Approved Each electrical panel board directory shown on sheet E-001, does not have the panel board identification shown. Refer to the 'top' portion of each directory. Please clarify. Section 109.3 of the Virginia Construction Code.
Electrical04/29/2021Approved Additional comments may be forthcoming. Section 109.3 of the Virginia Construction Code.
Electrical04/29/2021Approved Each electrical panel board directory shown on sheet E-001, does not have the panel board identification shown. Refer to the 'top' portion of each directory. Please clarify. Section 109.3 of the Virginia Construction Code.
Electrical04/29/2021Approved Additional comments may be forthcoming. Section 109.3 of the Virginia Construction Code.
Electrical04/29/2021Rejected Each electrical panel board directory shown on sheet E-001, does not have the panel board identification shown. Refer to the 'top' portion of each directory. Please clarify. Section 109.3 of the Virginia Construction Code.