Building | 05/28/2021 | Approved |
Sheet A-001 Cover Sheet and Notes: DRAWINGS ARE APPROVED WITH THE FOLLOWING FIELD COMMENTS:
SEPARATE PLAN AND PERMIT
REQUIRED FOR DOORS WITH
SPECIAL LOCKING HARDWARE
SUBMIT AUTOMATIC SUPPRESSION
SHOP DRAWINGS FOR APPROVAL
SUBMIT FIRE ALARM SHOP
DRAWINGS FOR APPROVAL
|
Building | 05/28/2021 | Approved |
Sheet A-001 Cover Sheet and Notes: DRAWINGS ARE APPROVED WITH THE FOLLOWING FIELD COMMENTS:
SEPARATE PLAN AND PERMIT
REQUIRED FOR DOORS WITH
SPECIAL LOCKING HARDWARE
SUBMIT AUTOMATIC SUPPRESSION
SHOP DRAWINGS FOR APPROVAL
SUBMIT FIRE ALARM SHOP
DRAWINGS FOR APPROVAL
|
Building | 05/24/2021 | Approved |
Sheet A-002 Proposed Floor Plan: There appears to be a column obstructing the code required Maneuvering Clearances at new Door #1. Please review and comply with the code requirements of ICC A117.1-2009, section 404.2.3 and figure 404.2.3.2. *****************************************************************************************************************
05/24/2021: See markup. Door #1 with HW-2 more...
|
Building | 05/24/2021 | Approved |
Sheet A-002 Proposed Floor Plan: There appears to be a column obstructing the code required Maneuvering Clearances at new Door #1. Please review and comply with the code requirements of ICC A117.1-2009, section 404.2.3 and figure 404.2.3.2. *****************************************************************************************************************
05/24/2021: See markup. Door #1 with HW-2 more...
|
Building | 05/24/2021 | Rejected |
Sheet A-002 Proposed Floor Plan: There appears to be a column obstructing the code required Maneuvering Clearances at new Door #1. Please review and comply with the code requirements of ICC A117.1-2009, section 404.2.3 and figure 404.2.3.2. *****************************************************************************************************************
05/24/2021: See markup. Door #1 with HW-2 more...
|
Building | 04/30/2021 | Rejected |
Sheet A-003 Reflected Ceiling Plan: See markup, Detail 2/A-002: Does this section detail occur at the Sushi Bar?
|
Building | 04/30/2021 | Approved |
Sheet A-003 Reflected Ceiling Plan: General Comment: See markup. Your Reception Desk at the Sushi Bar arrears to be a Built-in Furniture piece with electrical outlets Built-in to it. We review powered furniture such as this like a Wall Partition. All wood blocking installed within the framing cavity shall be Fire-Retardant Treated (FRT) Wood and its enclosure shall be a Noncombustible Surface such more...
|
Building | 04/30/2021 | Approved |
Sheet A-003 Reflected Ceiling Plan: See markup, Detail 2/A-002: Does this section detail occur at the Sushi Bar?
|
Building | 04/30/2021 | Approved |
Sheet A-003 Reflected Ceiling Plan: See markup, Detail 2/A-002: Does this section detail occur at the Sushi Bar?
|
Building | 04/30/2021 | Rejected |
Sheet A-003 Reflected Ceiling Plan: General Comment: See markup. Your Reception Desk at the Sushi Bar arrears to be a Built-in Furniture piece with electrical outlets Built-in to it. We review powered furniture such as this like a Wall Partition. All wood blocking installed within the framing cavity shall be Fire-Retardant Treated (FRT) Wood and its enclosure shall be a Noncombustible Surface such more...
|
Building | 04/30/2021 | Rejected |
Sheet A-002 Proposed Floor Plan: There appears to be a column obstructing the code required Maneuvering Clearances at new Door #1. Please review and comply with the code requirements of ICC A117.1-2009, section 404.2.3 and figure 404.2.3.2.
|
Building | 04/30/2021 | Rejected |
Sheet A-003 Reflected Ceiling Plan: See markup, Detail 2/A-002: Does this section detail occur at the Sushi Bar?
|
Building | 04/30/2021 | Rejected |
Sheet A-003 Reflected Ceiling Plan: General Comment: See markup. Your Reception Desk at the Sushi Bar arrears to be a Built-in Furniture piece with electrical outlets Built-in to it. We review powered furniture such as this like a Wall Partition. All wood blocking installed within the framing cavity shall be Fire-Retardant Treated (FRT) Wood and its enclosure shall be a Noncombustible Surface such more...
|
Building | 04/30/2021 | Approved |
Sheet A-003 Reflected Ceiling Plan: General Comment: See markup. Your Reception Desk at the Sushi Bar arrears to be a Built-in Furniture piece with electrical outlets Built-in to it. We review powered furniture such as this like a Wall Partition. All wood blocking installed within the framing cavity shall be Fire-Retardant Treated (FRT) Wood and its enclosure shall be a Noncombustible Surface such more...
|
DES:Water/Sewer Engineering | 04/29/2021 | Approved |
APPROVED REESTURANT RENO 4.00 NEW DFU'S
|
Electrical | 04/29/2021 | Approved |
Each electrical panel board directory shown on sheet E-001, does not have the panel board identification shown. Refer to the 'top' portion of each directory. Please clarify. Section 109.3 of the Virginia Construction Code.
|
Electrical | 04/29/2021 | Approved |
Additional comments may be forthcoming. Section 109.3 of the Virginia Construction Code.
|
Electrical | 04/29/2021 | Approved |
Each electrical panel board directory shown on sheet E-001, does not have the panel board identification shown. Refer to the 'top' portion of each directory. Please clarify. Section 109.3 of the Virginia Construction Code.
|
Electrical | 04/29/2021 | Approved |
Additional comments may be forthcoming. Section 109.3 of the Virginia Construction Code.
|
Electrical | 04/29/2021 | Rejected |
Each electrical panel board directory shown on sheet E-001, does not have the panel board identification shown. Refer to the 'top' portion of each directory. Please clarify. Section 109.3 of the Virginia Construction Code.
|