Permit #B2101411
Address900 ARMY NAVY DR
TypeCTBO
StatusACTIVE
Permit HolderJENNINGS L F INC
OwnerSTREET RETAIL INC
Applied Date06/15/2021
Approved Date09/13/2021
Date Issued09/13/2021
DescriptionTENANT FIT-OUT FOR NEW 33,970 SF TARGET STORE TO INCLUDE RETAIL SALES OF MERCHANDISE AND GROCERIES IN PREVIOUS BED BATH AND BEYOND SPACE. NO FOOD OR BEVERAGE PREPARATION. SPECIAL INSPECTION REQUIRED

View Event Log.      View Status.    View Required Plan Review       View Printer Version.

Review   Review       Date Status   Comments   
Building08/11/2021Approved Sheet A-611 OPENING SCHEDULE: SEPARATE PLAN AND PERMIT REQUIRED FOR DOORS WITH SPECIAL LOCKING HARDWARE ***Plan sheet comment, No response required
Building08/11/2021Approved Sheet A-611 OPENING SCHEDULE: SEPARATE PLAN AND PERMIT REQUIRED FOR DOORS WITH SPECIAL LOCKING HARDWARE ***Plan sheet comment, No response required
Building08/11/2021Approved Sheet A-611 OPENING SCHEDULE: SEPARATE PLAN AND PERMIT REQUIRED FOR DOORS WITH SPECIAL LOCKING HARDWARE ***Plan sheet comment, No response required
Building08/11/2021Approved Sheet A-611 OPENING SCHEDULE: SEPARATE PLAN AND PERMIT REQUIRED FOR DOORS WITH SPECIAL LOCKING HARDWARE ***Plan sheet comment, No response required
Building08/11/2021Approved Sheet A-611 OPENING SCHEDULE: SEPARATE PLAN AND PERMIT REQUIRED FOR DOORS WITH SPECIAL LOCKING HARDWARE ***Plan sheet comment, No response required
Building07/01/2021Approved Sheet A-456 COOLER FREEZER: Detail 7 shows pressure treated plywood. This building is required to have non combustible partition construction. The plywood attached to the studs would need to be non-combustible or FRT in compliance with VCC 603.
Building07/01/2021Rejected Sheet A-456 COOLER FREEZER: Detail 7 shows pressure treated plywood. This building is required to have non combustible partition construction. The plywood attached to the studs would need to be non-combustible or FRT in compliance with VCC 603.
Building07/01/2021Approved Sheet A-456 COOLER FREEZER: Detail 7 shows pressure treated plywood. This building is required to have non combustible partition construction. The plywood attached to the studs would need to be non-combustible or FRT in compliance with VCC 603.
Building07/01/2021Approved Sheet A-456 COOLER FREEZER: Detail 7 shows pressure treated plywood. This building is required to have non combustible partition construction. The plywood attached to the studs would need to be non-combustible or FRT in compliance with VCC 603.
Building07/01/2021Approved Sheet A-456 COOLER FREEZER: Detail 7 shows pressure treated plywood. This building is required to have non combustible partition construction. The plywood attached to the studs would need to be non-combustible or FRT in compliance with VCC 603.
Building07/01/2021Approved Sheet A-456 COOLER FREEZER: Detail 7 shows pressure treated plywood. This building is required to have non combustible partition construction. The plywood attached to the studs would need to be non-combustible or FRT in compliance with VCC 603.
Building06/28/2021Approved Sheet A-611 OPENING SCHEDULE: Unable to locate door hardware schedule within this plan set. Please provide location information or submit door hardware schedule.
Building06/28/2021Approved Sheet A-456 COOLER FREEZER: Is this wood blocking? If so it will need to be FRT.
Building06/28/2021Approved Sheet A-454 COOLER FREEZER PLANS: Coolers/freezers shall comply with VCC 603 #26 and 2603.4.1.2. Plan sheet note. No response required if coolers/freezers are compliant with the referenced codes.
Building06/28/2021Approved Sheet A-000G COVERSHEET: SUBMIT AUTOMATIC SUPPRESSION SHOP DRAWINGS FOR APPROVAL SUBMIT FIRE ALARM SHOP DRAWINGS FOR APPROVAL***** plan sheet comment, no response required.
Building06/28/2021Approved Sheet A-611 OPENING SCHEDULE: Unable to locate door hardware schedule within this plan set. Please provide location information or submit door hardware schedule.
Building06/28/2021Approved Sheet A-456 COOLER FREEZER: Is this wood blocking? If so it will need to be FRT.
Building06/28/2021Approved Sheet A-454 COOLER FREEZER PLANS: Coolers/freezers shall comply with VCC 603 #26 and 2603.4.1.2. Plan sheet note. No response required if coolers/freezers are compliant with the referenced codes.
Building06/28/2021Approved Sheet A-000G COVERSHEET: SUBMIT AUTOMATIC SUPPRESSION SHOP DRAWINGS FOR APPROVAL SUBMIT FIRE ALARM SHOP DRAWINGS FOR APPROVAL***** plan sheet comment, no response required.
Building06/28/2021Approved Sheet A-611 OPENING SCHEDULE: Unable to locate door hardware schedule within this plan set. Please provide location information or submit door hardware schedule.