Building | 02/25/2022 | Approved |
CTBO-38940 20 October 2021
Given the nature and extent of this project, additional concerns may come to light as the foregoing comments are addressed and resolved.
|
Building | 02/25/2022 | Approved |
CTBO-38940 25 February 2022
It appears the current (Review Cycle 6) submittal is for Electrical revisions only.
For a project of this size, it would certainly help the review process to include either a statement describing the permit alteration or a response letter addressing the prior review comments.
|
Building | 10/20/2021 | Approved |
Sheet A1.02a_EXISTING REQUIREMENTS AND PATH OF TRAVEL @ FIRST FLOOR: A1.02a Existing Requirements ... @ First Floor 20 October 2021
Please identify all rooms which have an assembly use, including conference rooms, staff lounge, etc.
The occupant load of such rooms shall be based upon a floor area ratio of 15 ft²/person (Assembly, unconcentrated) or upon the chair count, whichever is more...
|
Building | 10/20/2021 | Approved |
A0.00 Cover Sheet 20 October 2021
Project Scope/Notes: For new furniture with data and power, identify whether the furniture is electrified systems furniture or if power and data are provided via wall outlet at each workstation.
|
Building | 10/20/2021 | Approved |
Sheet A2.01b_CONSTRUCTION & FINISH PLAN @ SECOND FLOOR: A2.01b Construction & Finish Plan @ Second Floor 20 October 2021
Please identify the proposed use of the spaces where the lockers are being removed.
|
Building | 10/20/2021 | Approved |
A9.02 Door, Hardware & Window Schedules 19 October 2021
WHERE ARE THE DOORS WHICH ARE TO BE WIDENED PER DETAIL 11/S-200?
|
Building | 10/20/2021 | Approved |
A3.01a Reflected Ceiling Plan @ First Floor 20 October 2021
Please identify the item marked by the symbol [F].
|
Building | 10/20/2021 | Approved |
Sheet A7.01_SOLAR ROOF TILE & GRAPHIC WALL DETAILS: A7.01 Solar Roof Tile 20 October 2021
Please clarify. This graphic does not appear to have anything to do with electric automobiles?
|
Building | 10/20/2021 | Approved |
Sheet S-200_DETAILS: S-200 Structural - Detail Sheet 20 October 2021
Verify whether this wall is required to be fire rated. If so, the structural support must also be fire rated.
VCC §703; §707
|
Building | 10/20/2021 | Approved |
A0.00 Cover Sheet 20 October 2021
Code/Project Information: Please provide the floor area of each floor level in addition to the building footprint area.
- Identify the Use Group B Business areas, the Use Group F Factory/Industrial areas and the Use Group S Storage areas.
- The building occupancy appears to be Nonseparated Mixed Use in accordance with VCC §508. Please verify.
|
Building | 10/20/2021 | Approved |
CTBO-38940 20 October 2021
Given the nature and extent of this project, additional concerns may come to light as the foregoing comments are addressed and resolved.
|
Building | 10/20/2021 | Approved |
Sheet A1.02a_EXISTING REQUIREMENTS AND PATH OF TRAVEL @ FIRST FLOOR: A1.02a Existing Requirements ... @ First Floor 20 October 2021
Please identify all rooms which have an assembly use, including conference rooms, staff lounge, etc.
The occupant load of such rooms shall be based upon a floor area ratio of 15 ft²/person (Assembly, unconcentrated) or upon the chair count, whichever is more...
|
Building | 10/20/2021 | Approved |
A0.00 Cover Sheet 20 October 2021
Project Scope/Notes: For new furniture with data and power, identify whether the furniture is electrified systems furniture or if power and data are provided via wall outlet at each workstation.
|
Building | 10/20/2021 | Approved |
Sheet A2.01b_CONSTRUCTION & FINISH PLAN @ SECOND FLOOR: A2.01b Construction & Finish Plan @ Second Floor 20 October 2021
Please identify the proposed use of the spaces where the lockers are being removed.
|
Building | 10/20/2021 | Approved |
A9.02 Door, Hardware & Window Schedules 19 October 2021
WHERE ARE THE DOORS WHICH ARE TO BE WIDENED PER DETAIL 11/S-200?
|
Building | 10/20/2021 | Approved |
A3.01a Reflected Ceiling Plan @ First Floor 20 October 2021
Please identify the item marked by the symbol [F].
|
Building | 10/20/2021 | Approved |
Sheet A7.01_SOLAR ROOF TILE & GRAPHIC WALL DETAILS: A7.01 Solar Roof Tile 20 October 2021
Please clarify. This graphic does not appear to have anything to do with electric automobiles?
|
Building | 10/20/2021 | Approved |
Sheet S-200_DETAILS: S-200 Structural - Detail Sheet 20 October 2021
Verify whether this wall is required to be fire rated. If so, the structural support must also be fire rated.
VCC §703; §707
|
Building | 10/20/2021 | Approved |
A0.00 Cover Sheet 20 October 2021
Code/Project Information: Please provide the floor area of each floor level in addition to the building footprint area.
- Identify the Use Group B Business areas, the Use Group F Factory/Industrial areas and the Use Group S Storage areas.
- The building occupancy appears to be Nonseparated Mixed Use in accordance with VCC §508. Please verify.
|
Building | 10/20/2021 | Approved |
CTBO-38940 20 October 2021
Given the nature and extent of this project, additional concerns may come to light as the foregoing comments are addressed and resolved.
|
1 2 3 4 5 6 7 8 |