Permit #B2102303
Address2710 S GLEBE RD
TypeCTBO
StatusFINALED
Permit HolderRUSSCO
OwnerMMV ASSOCIATES LLC
Applied Date09/28/2021
Approved Date01/04/2022
Date Issued01/19/2022
DescriptionTENANT IMPROVEMENT FOR "TESLA, INC" AUTO SALES, DELIVERY AND VEHICLE SERVICE, INCLUDE 1) MINOR INTERIOR NON LOAD-BEARING PARTITION BUILD UP 2) NEW FURNITURE WITH DATA AND POWER 3) INSTALLATION OF NEW EQUIPMENT, AS NOTED IN THE EQUIPMENT SCHEDULE, ETC SPECIAL INSPECTION REQUIRED

View Event Log.      View Status.    View Required Plan Review       View Printer Version.

Review   Review       Date Status   Comments   
Building02/25/2022Approved CTBO-38940 20 October 2021 Given the nature and extent of this project, additional concerns may come to light as the foregoing comments are addressed and resolved.
Building02/25/2022Approved CTBO-38940 25 February 2022 It appears the current (Review Cycle 6) submittal is for Electrical revisions only. For a project of this size, it would certainly help the review process to include either a statement describing the permit alteration or a response letter addressing the prior review comments.
Building10/20/2021Approved Sheet A1.02a_EXISTING REQUIREMENTS AND PATH OF TRAVEL @ FIRST FLOOR: A1.02a Existing Requirements ... @ First Floor 20 October 2021 Please identify all rooms which have an assembly use, including conference rooms, staff lounge, etc. The occupant load of such rooms shall be based upon a floor area ratio of 15 ft²/person (Assembly, unconcentrated) or upon the chair count, whichever is  more...
Building10/20/2021Approved A0.00 Cover Sheet 20 October 2021 Project Scope/Notes: For new furniture with data and power, identify whether the furniture is electrified systems furniture or if power and data are provided via wall outlet at each workstation.
Building10/20/2021Approved Sheet A2.01b_CONSTRUCTION & FINISH PLAN @ SECOND FLOOR: A2.01b Construction & Finish Plan @ Second Floor 20 October 2021 Please identify the proposed use of the spaces where the lockers are being removed.
Building10/20/2021Approved A9.02 Door, Hardware & Window Schedules 19 October 2021 WHERE ARE THE DOORS WHICH ARE TO BE WIDENED PER DETAIL 11/S-200?
Building10/20/2021Approved A3.01a Reflected Ceiling Plan @ First Floor 20 October 2021 Please identify the item marked by the symbol [F].
Building10/20/2021Approved Sheet A7.01_SOLAR ROOF TILE & GRAPHIC WALL DETAILS: A7.01 Solar Roof Tile 20 October 2021 Please clarify. This graphic does not appear to have anything to do with electric automobiles?
Building10/20/2021Approved Sheet S-200_DETAILS: S-200 Structural - Detail Sheet 20 October 2021 Verify whether this wall is required to be fire rated. If so, the structural support must also be fire rated. VCC §703; §707
Building10/20/2021Approved A0.00 Cover Sheet 20 October 2021 Code/Project Information: Please provide the floor area of each floor level in addition to the building footprint area. - Identify the Use Group B Business areas, the Use Group F Factory/Industrial areas and the Use Group S Storage areas. - The building occupancy appears to be Nonseparated Mixed Use in accordance with VCC §508. Please verify.
Building10/20/2021Approved CTBO-38940 20 October 2021 Given the nature and extent of this project, additional concerns may come to light as the foregoing comments are addressed and resolved.
Building10/20/2021Approved Sheet A1.02a_EXISTING REQUIREMENTS AND PATH OF TRAVEL @ FIRST FLOOR: A1.02a Existing Requirements ... @ First Floor 20 October 2021 Please identify all rooms which have an assembly use, including conference rooms, staff lounge, etc. The occupant load of such rooms shall be based upon a floor area ratio of 15 ft²/person (Assembly, unconcentrated) or upon the chair count, whichever is  more...
Building10/20/2021Approved A0.00 Cover Sheet 20 October 2021 Project Scope/Notes: For new furniture with data and power, identify whether the furniture is electrified systems furniture or if power and data are provided via wall outlet at each workstation.
Building10/20/2021Approved Sheet A2.01b_CONSTRUCTION & FINISH PLAN @ SECOND FLOOR: A2.01b Construction & Finish Plan @ Second Floor 20 October 2021 Please identify the proposed use of the spaces where the lockers are being removed.
Building10/20/2021Approved A9.02 Door, Hardware & Window Schedules 19 October 2021 WHERE ARE THE DOORS WHICH ARE TO BE WIDENED PER DETAIL 11/S-200?
Building10/20/2021Approved A3.01a Reflected Ceiling Plan @ First Floor 20 October 2021 Please identify the item marked by the symbol [F].
Building10/20/2021Approved Sheet A7.01_SOLAR ROOF TILE & GRAPHIC WALL DETAILS: A7.01 Solar Roof Tile 20 October 2021 Please clarify. This graphic does not appear to have anything to do with electric automobiles?
Building10/20/2021Approved Sheet S-200_DETAILS: S-200 Structural - Detail Sheet 20 October 2021 Verify whether this wall is required to be fire rated. If so, the structural support must also be fire rated. VCC §703; §707
Building10/20/2021Approved A0.00 Cover Sheet 20 October 2021 Code/Project Information: Please provide the floor area of each floor level in addition to the building footprint area. - Identify the Use Group B Business areas, the Use Group F Factory/Industrial areas and the Use Group S Storage areas. - The building occupancy appears to be Nonseparated Mixed Use in accordance with VCC §508. Please verify.
Building10/20/2021Approved CTBO-38940 20 October 2021 Given the nature and extent of this project, additional concerns may come to light as the foregoing comments are addressed and resolved.